Installer’s Guide

Power switch plate must 
be above cover. 
Tab on power switch plate
must slide into slot on cover

Tab on power tray must be 
on outside of flange on cover

Figure 13. Assembling Power Tray and Cover

FuseHolder

POWER UNIT REMOVAL AND REPLACE-
MENT

To replace a faulty power tray or gain access to the ozone
reduction jumper or fuse, observe the following procedure.
1. Disconnect power cord from the power door and remove
power door from air cleaner.
2. On the inside of the door, remove four screws holding the
power pack to the door and remove power pack.
3. Separate power tray and cover.
NOTE: When reassembling the power tray and cover, ensure
that tray wiring is positioned to avoid interference
4. After servicing the ozone switch or fuse or after replacing
a faulty power tray, reassemble the cover and power tray.
When reassembling, be sure that power switch plate is on
the outside of the cover and the tab on the power switch
plate slides into the opening on the cover. Be sure also
that tab on bottom of power tray is on the outside of the
cover (see fig 13 ).
5. Position power unit on door and reattach using four
screws previously removed. Replace power cord.

Summary of Contents for TFE145A9FR0

Page 1: ...oes not fit into the outlet contact a qualified person nel to install the proper outlet Do not alter the plug in any way WARNING This information is for use by individuals having adequate backgrounds...

Page 2: ...nace air handler See Figure 2 for example Select a location that meets the following 1 The face of the cell must be at a right angle to the air stream 2 Allow a minimum of 28 inches clearance in front...

Page 3: ...cabinet to the furnace Use inner mounting holes for Side Installation Figure 5 Side Installation Details Install gasket material toward inner edge Cut to length required Bottom MOUNT Furnaces or Air...

Page 4: ...ween the female polarized connector on the heater and the male polarized connector from the air handler control box See Figure 8 The polarized connectors are keyed to aid in preventing incorrect assem...

Page 5: ...CE For maximum efficiency the air cleaner cells and pre filter should be inspected and cleaned on a regular basis MAINTENANCE REPLACEMENT SCHEDULE Fan ON Continuous Fan AUTO Dusty Normal Dusty Normal...

Page 6: ...d as follows 1 Remove all pieces of broken wire Make sure supports at each end are in good condition and not bent out of shape 2 Hook the new wire onto the support at one end 3 Hold your finger agains...

Page 7: ...n a removable metal tray attached to the door If a power supply fails the complete power tray must be replaced as a unit Input voltage Furnace or Air Handler Units 120 VAC 60 Hz Air Handler Units 208...

Page 8: ...rve the following procedure 1 Disconnect power cord from the power door and remove power door from air cleaner 2 On the inside of the door remove four screws holding the power pack to the door and rem...

Reviews: