92
18-CE12D1-1D-EN
1.
Remove 3” plug on right side of unit. To be used for condensate
trap.
2.
Install condensate trap grommet.
3.
Remove 3” plugs on the left side of the cabinet. To be used for
combustion air inlet.
4.
Reuse the two 3” plugs to seal the two 3” default openings on the
top of the furnace.
1.
Remove three inducer screws.
2.
While the inducer is loose, remove condensate drain plug from top
right location on cold header.
3.
Place condensate drain plug onto the cold header outlet located
on the bottom left of the cold header.
4.
Rotate the inducer 180 degrees so that the elbow is pointing
towards the left.
5.
Use the three inducer screws to reattach the inducer to the cold
header. Torque to 30 in.-lbs. Do not overtighten.
2
3