American Standard ACONT402AN32DA Installer'S Manual Download Page 13

Pub. No.  11-HD03D3-3

13

Installer’s Guide

Table 4   

                                                                          

Troubleshooting

Symptom

Possible Cause

Action

Display will not come on.

1. Blown fuse or tripped circuit breaker.
2. Furnace power switch OFF.
3. Furnace blower compartment door or panel

    loose or not properly installed.

1. Replace fuse or reset breaker.

2. Turn switch to ON.
3. Replace door panel in proper position to engage safety interlock or
    door  switch.

Indoor temperature display is
incorrect.

Temperature display needs calibration.

Calibrate Sensor - User Setup Step 59.

Outdoor temperature display is
incorrect.

Temperature display needs calibration.

1. Calibrate Sensor - User Setup Step 60.

2. Disconnect outdoor sensor from controls terminal block and check the
    sensor and field wiring resistance value - Table 2.

Outdoor temperature display
shows "--" and Service indicator
on solid.

1. Outdoor temperature sensor open or shorted.
2. Outdoor sensor field wiring open or shorted.

1. Replace outdoor sensor.

2. Check / repair outdoor sensor field wiring.

Cannot  set Heating setpoint
above 80 degrees

Deadband between Heating and Cooling set to high.

Decrease Deadband setting - User Setup Step 52.

Service indicator flashing on and
off at ISU steps 5 and 8 or Service
and Heat indicators flashing on
and off.

JP1 Dual Fuel jumper setting does not agree with

ISU selections.

Cut JP1 for Dual Fuel applications.

Service indicator flashing on and
off.

Control EEPROM write error.

Press any key and Check / Re-enter Setup Choices.

Service indicator solid on and "--"
in temperature display.

Indoor temperature sensor open or shorted.

Replace Control

Temperature setting will not
change. (Example: Cannot set

heating higher or cooling lower).

1. Upper and/or lower temperature limits were

    reached.
2. "Keypad locked" is displayed on LCD.

1. Check the temperature setpoints:

    Heating limits are 40 - 85F.
    Cooling limits are 65 - 90F.
2. Unlock keypad - press Up+Down arrow together until icon disappears.

Room temperature overshoots

when Energy Savings Key ($) is

used or the Heat/Cool settings is
changed more than 2 degrees.

Oversized heating or cooling equipment. Control
cannot respond fast enough to prevent
overshooting.

Set Control Response rate to "Fast" - ISU Step 34.

Heating will not come on.

1. System Mode not set to Heat.
2. Minimum off time delay being enforced.
3. Loose connection to control or system.
4. Heating system requires service or

    control requires replacement.

1. Set Mode to heat and raise the setpoint above room temperature.

2. If heating does not come on within 5 minutes, Check Heating.
3. Check / Repair connections.
4. Repair system / Replace control.

Cooling will not come on.

1. System Mode not set to Cool.
2. Minimum off time delay being enforced
3. Loose connection to control or system.
4. Cooling system requires service or

    control requires replacement.

1. Set Mode to cool and lower the setpoint below room temperature.

2. If cooling does not come on within 15 minutes, contact servicer.
3. Repair connections.
4. Repair system / Replace control.

Cool ON  or Heat ON is displayed,
but no warm or cool air is coming
from the registers.

1. The heating equipment turns on the

    fan when the furnace has warmed up to a
    setpoint.
2. Heating or cooling equipment is not
    operating.

1. Wait one minute after Heat ON is displayed

    and then check the registers.
2. Check Heating and Cooling system.

Control does not respond to
keypad presses.

1. "Keypad locked" is displayed on LCD.
2. Keypad failure.

1. Unlock keypad - press Up+Down arrow together until "Keypad locked"

   disappears.
2. Replace Control.

Fan does not operate properly in
heat or cool mode.

1. Incorrect wiring.
2. Heating or cooling equipment inoperative.

1. Correct wiring.

2. Repair system.

Note: BK operation is required for 2 stage / 2 step operation.

Fan runs all the time.

1. Fan mode set to ON.
2. Shorted control wiring.

1. Set fan mode to AUTO.

2. Check / Repair wiring.

Cooling cycle too fast or too slow.
(Narrow or wide temperature
swing).

The location of the control and/or the size of the
cooling system may be influencing the cycle rate.

Verify cycle rate adjustment ISU Steps  20 & 22.

Heating cycle too fast or too slow.
(Narrow or wide temperature
swing).

The location of the control and/or the size of the

heating system may be influencing the cycle rate.

Verify cycle rate adjustment ISU Steps 24.26.28.30 & 32.

Summary of Contents for ACONT402AN32DA

Page 1: ...ER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which could result in minor personal injury or product and property damage Note Read the entire instruction manu...

Page 2: ...se non hardening caulk putty or insulation 3 Avoid locations such as near dryer vents or placing the sensor close to or directly above the outdoor unit where it would be exposed to hot discharge air from the condenser fan 4 Maximum length of field wiring cable to sensor is 200 feet 5 Minimum wire gauge is 18AWG Mounting and Wiring 1 Turn OFF all power to heating and cooling equipment 2 If an exist...

Page 3: ...on display See Figure 6 Enter USER Setup See Table 3A steps 50 62 for option details Press and hold Mode and Fan at the same time Note Allow a minimum of 5 seconds after saving selections Step 99 SA for the control to write selections to memory If power is lost or removed prior to the 5 second elapsed time the selections may be lost and must be reentered If the SERVICE icon is flashing on the cont...

Page 4: ...OFF Table 2 T deg F RESISTANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62 3 60 15 3 105 5 2 15 53 5 65 13 5 110 4 7 20 46 1 70 11 9 115 4 2 25 39 8 75 10 5 120 3 8 30 34 5 Figure 8 2 Set Fan to AUTO 3 Pr...

Page 5: ...Temp OT2 O D Sensor Note C For Dual Fuel cut the JP1 jumper on the Comfort Control NOTE See Fig OIL 1 for external relay connections for oil furnaces R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL DUAL FUEL ONE OR TWO STAGE OR TWO STEP HEAT PUMP TWO STAGE VS GAS FURNACE BK ENABLED FAN SOV COOL HEAT 1st STAGE HEATING 3rd STAGE HEATING 4th STAGE W2 O R G W2 Y1 YLO Y1 B ONE OR TWO STAGE OR TWO ...

Page 6: ...AT 1st STAGE HEATING 2nd STAGE HEATING 3rd STAGE W2 O W3 Y2 BK R G W W1 W2 Y Y B SINGLE STAGE HEAT PUMP O R T NON V S ONE OR TWO STAGE GAS FURNACE B C X2 O D Temp OT1 O D Temp OT2 O D Sensor Note C For Dual Fuel cut the JP1 jumper on the Comfort Control NOTE See Fig OIL 1 for external relay connections for oil furnaces Figure DF 5 P2 JP1 Cut for Dual Fuel Applications JP 1 Location ...

Page 7: ...IL VARIABLE SPEED AIR HANDLER BK ENABLED FAN SOV COOL HEAT 1st STAGE HEATING 3rd STAGE HEATING 4th STAGE W2 O R G W1 W2 Y1 YLO Y B TWO SEPARATE HEAT PUMPS VS AIR HANDLER ELECTRIC HEAT W3 HEATING 5th STAGE Y2 COOL HEAT 2nd STAGE BK VS MODE fan Y Y2 Y BK B SECOND STAGE FIRST STAGE X2 O O X2 A B 9 6 3 7 4 R R B O D Temp OT1 O D Temp OT2 O D Sensor T T W3 O Note B Cut remove the factory installed BK j...

Page 8: ...E BK Y Y2 Y1 BK W3 O O R O D Temp OT1 O D Temp OT2 O D Sensor T X2 Note A The installer must jumper R to O at the LVTB Note B Cut remove the factory installed BK jumper at the indoor unit R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL SINGLE STAGE HEAT PUMP VARIABLE SPEED AIR HANDLER BK DISABLED FAN SOV COOL HEAT 1st STAGE HEATING 2nd STAGE HEATING 3rd STAGE W2 O R G W1 W2 Y1 YLO B SINGLE ST...

Page 9: ... W1 B 24VAC HOT 24VAC common COMFORT CONTROL TWO STEP COOLING VARIABLE SPEED INDOOR BK DISABLED FAN COOLING 1st HEATING 1st HEATING 2nd W2 O R G W1 W2 Y1 YLO B TWO STEP AIR CONDITIONER TWO STAGE VS GAS FURNACE or VS AIR HANDLER ELECTRIC HEAT B C W3 HEATING 3rd Y2 COOLING 2nd BK Y Y2 Y1 BK O Y2 W3 Note A The installer must jumper R to O at the LVTB Note B Cut remove the factory installed BK jumper ...

Page 10: ...ections for oil furnaces NOTE Two additional wires are required for Outdoor Temperature Sensor Figure CL 5 Figure CL 7 Figure CL 6 Figure OIL 1 R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL SINGLE STAGE COOLING SINGLE STAGE OIL FURNACE BK DISABLED FAN COOLING HEATING W2 O R G W W2 Y Y B SINGLE STAGE AIR CONDITIONER SINGLE STAGE OIL FURNACE B C W3 Y2 BK W3 R1 R1 NOTE Two additional wires are...

Page 11: ...ancel CL Clears History and Service Data only CS Clears Setups FD Factory Default 99 Exit Table 3 INSTALLER SETUP ISU see notes at the bottom of setup ISU Table 3A 1 Set System MODE to OFF 2 Set FAN to AUTO 3 Press and hold MODE and Up arrow at the same time Menu Item Factory Setting Setting Choices Press UP or DOWN arrow Step Press Mode Fan Error Count 0 None 1 Software Version None 2 Configurati...

Page 12: ...ages 0 None Steps 28 33 38 39 43 44 46 49 not available Step 9 Heater Stages 1 Single Stage Steps 30 33 48 49 not available Step 9 Heater Stages 2 Two Stage Steps 32 33 49 not available Step 10 Outdoor Sensor 0 None Steps 40 49 60 not available Step 10 Outdoor Sensor 1 Display Only Steps 41 49 not available Step 11 BK Output 0 BK Disabled Steps 12 15 40 not available Step 11 BK Output 1 BK Enabled...

Page 13: ...es Oversized heating or cooling equipment Control cannot respond fast enough to prevent overshooting Set Control Response rate to Fast ISU Step 34 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or system 4 Heating system requires service or control requires replacement 1 Set Mode to heat and raise the setpoint above room...

Page 14: ...rrides ISU Step 45 when enabled Cooling Efficiency Booster Single Stage Compressor Only BK Enabled The indoor air flow is reduced to 80 at outdoor temperatures below 87 F in cooling mode The outdoor temperature sensor must be installed and enabled in ISU Step 10 Control Response Rate A set of higher gain Proportion Integral control constants can be chosen to increase the responsiveness of the temp...

Page 15: ...the system Minimum off time delays will be enforced on the next cycle Wait Indicator Waiting will illuminate when the indoor setpoint is moved in the direction of calling for additional system capacity Waiting indicates system time delays are being enforced and that the control is adjusting to the new settings Calibrate Indoor Temperature This option allows calibration of the room temperature sens...

Page 16: ...ransition from furnace operation to heat pump operation there is a minimum comfort control time delay of 45 seconds between the furnace turning off and the heat pump turning on RESTRICTED MODE Requires Outdoor Temperature Sensor The Heat Pump Restricted Mode Outdoor Temperature changeover point ISU Step 43 must be set at or above the application or economic balance point of the system At any tempe...

Page 17: ...Pub No 11 HD03D3 3 17 Installer s Guide ...

Page 18: ...y of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75707 For more information contact your local dealer distributor ...

Reviews: