American Standard AccuLink Platinum 850 Installation Manual Download Page 22

Installation Guide

22  

11-HD14D1-9-EN

9.  Troubleshooting

SYMPTOM

POSSIBLE CAUSES

ACTION

Control displays an alert code on 
the screen.

A critical or major alert is present.

Navigate to the Diagnostic screen on the 850 Control 
for a Problem Description and Possible Cause.

Display will not come on

Loss of 24VAC between R & B at the Control.

1) Check wiring between R & B to see if R & D, or B & 
D have been reversed.
2) Check transformer for 24VAC output.
3) Check for broken or shorted thermostat wire.

Indoor temperature display is 
incorrect.

1) Control requires one hour to acclimate to 
environment.
2) Indoor temperature display needs calibration. 
3) Heat from touch screen is being trapped 
within the thermostat body. See section 3.1 for 
mounting location guidelines.

1) Allow one hour before proceeding with troubleshoot-
ing process.
2) Calibrate temperature sensor from Control menu.
3) Move thermostat away from competing air stream or 
use a remote temperature sensor

Indoor humidity display is incor-
rect.

Indoor humidity display needs calibration.

Calibrate humidity sensor from the Control menu.

Room temperature overshoots 
when the Heat/Cool setting is 
changed more than 2°.

1) Oversized heating/cooling equipment under 
current conditions.  Control cannot respond fast 
enough to prevent overshooting.
2) Improper location of Control.

1) Compare heat load calculation to equipment chosen.
2) Relocate Control (or use remote sensor) if Control is 
in “dead” spot (poor or no air circulation).  

Heating will not come on.

1) System mode is not set to Heat/Auto or set-
point is set too low.
2) Minimum off time delay is being enforced.
3) Heating system may require service.

1) Set mode to heat and raise the setpoint above the 
room temperature.
2) Wait for 5 minutes and recheck heating equipment.
3) Check/repair system.

Cooling will not come on.

1) System mode is not set to Cool/Auto or the 
setpoint is too high.
2) Minimum off time delay is being enforced.
3) Cooling system may require service.

1) Set mode to cool and lower the setpoint below the 
room temperature.
2) Wait for 5 minutes and recheck cooling equipment.
3) Check/repair system.

Heating or Cooling is displayed, 
but no warm or cool air is coming 
from the registers.

1) There is a fan delay as the heating or cooling 
equipment turns on.
2) Equipment is not working properly.

1) Wait a minute for blower delays and recheck regis-
ters.
2) Check/repair system.

Fan runs all the time

1) Fan mode is set to On, Circulate or Clean 
mode
2) There is a failure in the indoor unit 

1) Check Control settings to see if fan is set to On, 
Circulate or Clean mode.
2) Check indoor unit for failures (such as tripped heat-
ing limit).

“+” symbol appears on Home 
Screen beneath Indoor 
Temperature readout

Both compressor heat and indoor heat are being 
called simultaneously

 

No action required, symbol is for informational purposes 
only

Fan is set to ON but not running.

1) Humidity Control is engaged.  
2) Blower motor is not functioning.

1) If indoor humidity is higher than desired setpoint, 
the blower will cycle off with the equipment. A humidity 
icon will be displayed on the Fan Mode button when 
the blower operation is being inhibited due too high 
humidity.
2) Check/repair system.

Cooling or Heating cycles too 
fast or too slow (narrow or wide 
temperature swings).

1) Check the location of the Control for drafts.
2) Cycles per hour or aggressive recovery is 
improperly set.

1) Seal air leaks behind Control.  Relocate Control or 
apply remote indoor temperature sensor.
2) Adjust cycle rates and aggressive recovery features 
in the advanced installer set up.

Heat pump is not turning on; only 
furnace or electric heat strips are 
running.

1) Outdoor temperature is below compressor 
lockout temperature setting.
2) Compressor heating lockout is enabled and 
outdoor temp sensor is out of calibration or 
failed.
3) The outdoor unit is not reporting (Err.126.00)

1) Adjust the compressor lockout temperature setting 
if desired.
2) Check/repair outdoor sensor or wiring. 
3) Check communication status of outdoor unit.

Cannot change system mode to 
desired setting. 

Equipment is not configured properly.

Check the standard installer set up screen to ensure 
equipment is properly configured.  

Screen does not respond prop-
erly to a button press

1) Screen is out of calibration.
2) Internal Control fault

1) Remove Control from sub base and reset. Follow the 
calibration instructions when the Control reboots.
2) Remove Control from sub base and reset.   

Summary of Contents for AccuLink Platinum 850

Page 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furthe...

Page 2: ...3 1 Overview 3 3 2 Contents 3 3 3 Accessories 3 4 Installation 4 4 1 Location 4 4 2 Network Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 7 5 1 Power...

Page 3: ...e 0 to 100 1 resolution Minimum Cycle Off Time Delay Compressor 5 minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer...

Page 4: ...e Control s communication i e wireless phones security systems wireless Internet cameras Do not mount the Control in recessed areas near metal objects or near structures i e doors appliances entertain...

Page 5: ...s extend through the hole in the Sub base see Figure 4 on page 5 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4...

Page 6: ...r Optional Remote Sensor Communicating Indoor w Non Communicating Outdoor COMMUNICATING INDOOR UNIT excluding TAM8 24V SINGLE STAGE COOLING OUTDOOR 850 COMFORT CONTROL Caution Do not run Outdoor Remot...

Page 7: ...the navigational steps and screen prompts installer s are guided through the Time and Date Installer Setup see 5 4 Installer Setup Screens on page 8 for detailed descriptions of each of the Installer...

Page 8: ...ment Settings MENU ITEM OPTIONS DEFAULT DESCRIPTION Compressor Cooling Cycles Per Hour 2 6 Cph 3 Select of cycles per hour during cooling operation 1st Stage Compressor Cooling Cycles Per Hour 2 6 Cph...

Page 9: ...elect whether the indoor blower operates on a call for ventilation Ventilation Minimum Outdoor Temperature 10 F 50 F 0 Select the minimum outdoor temperature that ventilation is allowed Ventilation Ma...

Page 10: ...or additional information Aggressive Recovery 2 Setpoint Change Enable Disable Select whether the 10 minute staging inhibit is disabled heating or cooling mode with a setpoint change greater than 2 Se...

Page 11: ...minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating operation VS Blower Off Delay Comp Htg No Delay 1 5 Minutes 100...

Page 12: ...frost above this temperature Compressor Cooling 1st Stage Lockout Disable Enable Enable compressor cooling 1st stage lockout Compressor Cooling 1st Stage Lockout Setting 80 F 120 F Select an outdoor t...

Page 13: ...0 475 Two Stage Heat Pump 3 Stage Gas Oil Heat 6 3 Load Value Cooling 0 100 Single Stage Compressor 0 200 Two Stage Compressor A Load Value of 50 represents a request of 50 demand for single stage co...

Page 14: ...STAGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 7 Stage Inhibits When the stage threshold is exceeded a stage inhibit is...

Page 15: ...only limit Daytime operation only limit Nighttime or limit Daytime and Nighttime to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Quiet Mode take...

Page 16: ...hen indoor humidity exceeds the desired cooling RH This feature can be enabled in the Installer Settings Comfort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 850 has the abili...

Page 17: ...outs The 850 has the following lockouts AN OUTDOOR TEMPERATURE SENSOR MUST BE ENABLED FOR LOCKOUT SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lo...

Page 18: ...ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the minimum or maximum outdoor temperature selections If outdoor temperat...

Page 19: ...ated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must be within 55F to 120F and indoo...

Page 20: ...Normal alerts are only displayed in the Diagnostic screen Diagnostics can be accessed by navigating to Service Menu Diagnostics 8 3 2 Summary Table The 850 Control has a Summary Table which lists all...

Page 21: ...eens Operating State Stage Requested Capacity Delivered Compressor Speed Load Value Fan Mode Air Flow Indoor Outdoor Temperatures Heating Cooling Set Points Indoor RH Heating Cooling RH Set Points 8 6...

Page 22: ...ating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is not working properly 1 Wait a minu...

Page 23: ...cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the...

Page 24: ...D1 9 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Reviews: