American Standard 2A7A1018A Installer'S Manual Download Page 2

PAGE 2

Pub. No. 11-AC11D2-5

INSTALLER'S GUIDE

SEALING CAP

ADAPTER

FLOW CONTROL
CHECK VALVE
(F.C.C.V.) ORIFICE

FIELD SUPPLIED
LIQUID LINE

AS SHIPPED

BODY

ACCUTRON

TM

COMPONENTS

C. ACCUTRON™ FLOW CONTROL VALVE

If the indoor unit System Refrigerant Flow control is an
Accutron™ orifice and check valve assembly, an orifice size
change may be necessary.  See Figure 3.

The outdoor model determines the required orifice size.  Check
the listed orifice size on nameplate of the selected outdoor model.
If the indoor unit is factory shipped with a different orifice size,
the orifice must be changed to obtain system rated performance.

IMPORTANT:

The outdoor unit is shipped with the proper size

orifice and a stick-on orifice size label in an envelope attached to
the outdoor unit.  Outdoor unit nameplate will have correct
orifice size specified as BAYFCCV --- A for rated performance.

D. INSTALLING REFRIGERANT LINES

▲ 

CAUTION:

 If using existing refrigerant lines

make certain that all joints are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor unit
for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may be
straight or with a 90 degree bend, depending upon situation
requirements.  This should be thoroughly checked out before
ordering refrigerant line sets.

The gas line must always be insulated.

▲ 

CAUTION:

  In scroll compressor applica-

tions, dome temperatures may be hot. Do not touch top of
compressor, may cause minor to severe burning.

The units are factory charged with the system charge required
when using fifteen (15) feet of connecting line.  Unit nameplate
charge is the same.

Final refrigerant charge adjustment is necessary. Use the
Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space limitations.

NOTE:  Large diameter tubing will be very difficult to rebend once
it has been shaped.

3. Determine the best starting point for routing the refrigerant
tubing — INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both liquid
and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and properly
secure the tubing before making connections.

8. To prevent a noise within the building structure due to
vibration transmission from the refrigerant lines, the following
precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation type hangers.

b. Isolation hangers should also be used when refrigerant

lines are run in stud spaces or enclosed ceilings.

c. Where the refrigerant lines run through a wall or sill, they

should be insulated and isolated.

d. Isolate the lines from all ductwork.

E. SERVICE VALVE OPERATION

BRASS LIQUID AND GAS LINE SERVICE VALVES

The Brass Liquid and Gas Line Service Valves are factory
shipped in the seated position to hold factory charge.  The
pressure tap service port (when depressed) opens only to the field
brazing side of the valve when the valve is in the seated position.
The liquid line valve is not a back seating valve (see WARNING
that follows).

▲ 

WARNING:

 Extreme caution should be ex-

ercised when opening the Liquid Line Service Valve.
Turn valve stem counterclockwise only until the stem
contacts the rolled edge. (See Figure 4) No torque is
required.

BASEPAN TAB REMOVAL

2

BRAZE TYPE INDOOR END

3

Summary of Contents for 2A7A1018A

Page 1: ...el support pad at least as large as the unit base pan such as a concrete slab If this is not the application used please reference ALG APG0 EN latest revi sion number 3 The support pad must NOT be in...

Page 2: ...nameplate charge is the same Final refrigerant charge adjustment is necessary Use the Charging Charts in the outdoor unit Service Facts 1 Determine the most practical way to run the lines 2 Consider t...

Page 3: ...ld refrigerant lines with dry nitrogen to 350 400 psi Use soap bubbles or other leak checking methods to see that all field joints are leak free If not release pressure then repair SYSTEM EVACUATION N...

Page 4: ...ed within one mile of salt water including seacoasts and inland waterways require the addition of BAYSEAC001 Seacoast Kit at the time of installation IMPORTANT See Limited Warranty information in Use...

Page 5: ...grounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to...

Page 6: ...1 4 457 18 2A7A2048A 3 1 933 36 3 4 829 32 5 8 756 29 3 4 1 1 8 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2A7A2060B 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3...

Page 7: ...Pub No 11 AC11D2 5 PAGE 7 INSTALLER S GUIDE MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 1...

Page 8: ...instructions with thermostat 11 Is correct speed tap being used Indoor blower motor 12 Operate complete system in each mode to insure safe operation INDOOR THERMOSTAT SWITCH SETTING 1 1 Fan Switch TO...

Reviews: