background image

© 2005 American Standard Inc.  All Rights Reserved

Since the manufacturer has a policy of continuous product
and product data improvement, it reserves the right to
change design and specifications without notice.

11-AC11D2-5

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service information pack
upon completion of work.

These instructions do not cover all variations in systems
nor provide for every possible contingency to be met in
connection with installation.  All phases of this installa-
tion must comply with NATIONAL, STATE AND LOCAL
CODES. 
Should further information be desired or should par-
ticular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to your
installing dealer or local distributor.

A. GENERAL

The following instructions cover 2A7A5, 2A7A4, 2A7A2, & 2A7A1
Condensing Units.

NOTE: The 2A7A4, 2A7A2,& 2A7A1 outdoor units, except
for the 5 ton models, may be used with indoor units
equipped with Thermostatic Expansion Valve or Accutron™
Flow Control Check Valve (F.C.C.V.) assembly for refriger-
ant flow control only. The 2A7A5 & all 5 ton outdoor units
must be used with indoor units equipped with Thermo-
static Expansion Valve only.

Check for transportation damage after unit is uncrated.  Report
promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit, refer
to the nameplate of the unit.  The electrical power available must
agree with that listed on the nameplate.

B. LOCATION & PREPARATION OF THE UNIT

1. When removing unit from the pallet, notice the tabs on the
basepan. Remove tabs by cutting with a sharp tool as shown in
Figure 2 (see page 2).

2. The unit should be set on a level support pad at least as large
as the unit base pan, such as a concrete slab. If this is not the
application used please reference ALG-APG0*-EN (*latest revi-
sion number).

3. The support pad must NOT be in direct contact with any
structure.  Unit must be positioned a minimum of 12" from any
wall or surrounding shrubbery to insure adequate airflow.
Clearance must be provided in front of control box (access
panels) & any other side requiring service access to meet
National Electrical Code.  Also, the unit location must be far
enough away from any structure to prevent excess roof run-off
water from pouring directly on the unit. When choosing the
location of the unit(s), sound transmission through air and

Condensing Units

Models:

2A7A5024-048, 2A7A4018-060,

2A7A2018-060 & 2A7A1018-060

INSTALLER'S GUIDE

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

TOP DISCHARGE — UNRESTRICTED

5 FT. ABOVE UNIT

1

refrigerant lineset should be taken into consideration. It is
recommended to locate unit(s) away from areas (bedrooms, etc.)
where such sound could be objectionable.

4. The top discharge area must be unrestricted for at least
five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the roof
will support the unit’s weight. Properly selected isolation is
recommended to prevent transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to
indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler, maximum
lift should not exceed sixty (60) feet (suction line).  If air handler
is mounted above condensing unit, maximum lift should not
exceed sixty (60) feet (liquid line).

8. Locate and install indoor coil or air handler in accordance
with instruction included with that unit.

NOTE:  Refer to “Refrigerant Piping Software” Pub. No.
32-3312-0*, and “Refrigerant Piping Manual” Pub. No.
32-3009-0* (the position of the * denotes latest revision
number).

Summary of Contents for 2A7A1018A

Page 1: ...el support pad at least as large as the unit base pan such as a concrete slab If this is not the application used please reference ALG APG0 EN latest revi sion number 3 The support pad must NOT be in...

Page 2: ...nameplate charge is the same Final refrigerant charge adjustment is necessary Use the Charging Charts in the outdoor unit Service Facts 1 Determine the most practical way to run the lines 2 Consider t...

Page 3: ...ld refrigerant lines with dry nitrogen to 350 400 psi Use soap bubbles or other leak checking methods to see that all field joints are leak free If not release pressure then repair SYSTEM EVACUATION N...

Page 4: ...ed within one mile of salt water including seacoasts and inland waterways require the addition of BAYSEAC001 Seacoast Kit at the time of installation IMPORTANT See Limited Warranty information in Use...

Page 5: ...grounding of equipment must comply with local codes 3 Low voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to...

Page 6: ...1 4 457 18 2A7A2048A 3 1 933 36 3 4 829 32 5 8 756 29 3 4 1 1 8 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2A7A2060B 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3...

Page 7: ...Pub No 11 AC11D2 5 PAGE 7 INSTALLER S GUIDE MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 1...

Page 8: ...instructions with thermostat 11 Is correct speed tap being used Indoor blower motor 12 Operate complete system in each mode to insure safe operation INDOOR THERMOSTAT SWITCH SETTING 1 1 Fan Switch TO...

Reviews: