Pub. No. 11-BC14D1-2

INSTALLER'S GUIDE

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

service valve.  A 1/4" Open End or Adjustable wrench is required to
open gas line valve.  A 3/4" Open End wrench is required to take off
the valve stem cap.

9. The liquid line shut-off valve can now be opened.  Remove shut-
off valve cap.  Fully insert hex wrench into the stem and back out
counterclockwise until valve stem just touches rolled edge (ap-
proximately five [5] turns) observing 

WARNING

 statement on

page 2.  See Figure 3.

10. Replace liquid service pressure tap port cap and valve stem
cap.  These caps 

MUST BE REPLACED

 to prevent leaks.

Replace valve stem and pressure tap cap finger tight, then
tighten an additional 1/6 turn.

11. The gas valve can now be opened.  For a ball type gas valve,
open the gas valve by removing the shut-off valve cap and turning
the valve stem 1/4 turn counterclockwise, using 1/4" Open End or
Adjustable wrench.  See Figure 4. For brass gas line service valve
opening, follow 9 and 10 above. See Figure 5.

12. The gas valve is now open for refrigerant flow. Replace valve
stem cap to prevent leaks. Again, these caps 

MUST BE RE-

PLACED

 to prevent leaks.  Replace valve stem and pressure tap

cap finger tight, then tighten an additional 1/6 turn.  See Figure 4.

If refrigerant lines are longer than 15 feet and/or a different size
than recommended, it will be necessary to adjust system refriger-
ant charge upon completion of installation. See unit Service Facts.

E. ELECTRICAL CONNECTIONS

▲ 

WARNING:

 When installing or servicing

this equipment, ALWAYS exercise basic safety precau-
tions to avoid the possibility of electric shock.

1. Power wiring and grounding of equipment must comply with
local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration trans-
mission may create a noise problem within the structure.

6. The use of color coded low voltage wire is recommended to
simplify connections between the outdoor unit, the thermostat

coil temperature.  The difference between the ambient and the
colder coil temperature is the difference or delta-T measurement.
This delta-T measurement is representative of the operating
state and relative capacity of the heat pump system.  By measur-
ing the change in delta-T, we can determine the need for defrost.
The coil sensor also serves to sense outdoor coil temperature for
termination of the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the defrost
control inside the heat pump control box.

In normal operation, the defrost control light will flash once each
second. If the light is flashing more than once per second or not
at all, refer to the service manual for that unit.

PIN IDENTIFICATION

 (See Figure 6)

1. TEST_COMMON (Shorting any of the other pins to this pin
causes the function of the other pin to be executed. Leaving this
pin open results in the normal mode of operation.)

2. TST  =  Test  (Shorting TEST_COMMON to this pin speeds up
all defrost board timings.)

FRC_DFT

TEST_COMMON

TST

LOW_FAN

PIN IDENTIFICATION

6

(

*

applicable to 2A6H4 Models only)

*

and the indoor unit.

Table 1 — NEC Class II Wiring

7. Table 1 defines maximum

 total

 length of low voltage wiring

from outdoor unit, to indoor unit, and to thermostat.

8. Mount the indoor thermostat in accordance with instruction
included with the thermostat. Wire per appropriate hookup
diagram (included in these instructions).

F. DEFROST CONTROL

The demand defrost control measures heat pump outdoor ambi-
ent temperature with a sensor located outside the outdoor coil.  A
second sensor located on the outdoor coil is used to measure the

3. FRC_DFT  =  Forced Defrost  (Short TEST_COMMON to this
pin for two [2] seconds to initiate a forced defrost. Remove the
short after defrost initiates.)

DEFROST CONTROL CHECKOUT

Normal operation requires:

a

LED on board flashing 1 time/second.

b. 24V AC between R & B

c. 24V AC between Y & B with unit operating

d. Defrost initiation when FRC_DFT pin is shorted to

TEST_COMMON pin.

If a defrost control problem is suspected, refer to the service
information in control box.

▲ 

WARNING:

 Do NOT connect 24 VAC to T1

(ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.

G. COMPRESSOR START-UP

After all electrical wiring is complete, SET THE THERMOSTAT
SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR
WILL NOT RUN, and apply power by closing the system main
disconnect switch.  This will activate the compressor sump heat
(where used).  Do not change the Thermostat System Switch

Summary of Contents for 2A6H3018A

Page 1: ...th stand and operate in severe winter conditions However there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit It i...

Page 2: ...epending upon situation requirements This should be thoroughly checked out before ordering refrigerant line sets The gas line must always be insulated CAUTION In scroll compressor applica tions dome t...

Page 3: ...port while brazing 8 Braze using accepted good brazing techniques LEAK CHECK IMPORTANT Replace pressure tap port valve core before attaching hoses for evacuation After the brazing operation of refrig...

Page 4: ...thedifferenceordelta Tmeasurement This delta T measurement is representative of the operating state and relative capacity of the heat pump system By measur ing the change in delta T we can determine t...

Page 5: ...ound in the Service Facts I ELECTRIC HEATERS Electric heaters if used are to be installed in the air handling deviceaccordingtotheinstructionsaccompanyingtheairhandler and the heaters J START CONTROL...

Page 6: ...5 5 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2A6H3030A 3 1 933 36 3 4 829 32 5 8 756 29 3 4 3 4 5 16 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2A6H3036A 4 1 943 37 1 8 946 37 1 4 870 34 1 4 7 8 3 8 15...

Page 7: ...Pub No 11 BC14D1 2 PAGE 7 INSTALLER S GUIDE MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 1...

Page 8: ...Blower Won t Start DEFROST Unit Won t Initiate Defrost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H I G H V O L T A G E W I R I N G C O M P R E S S O...

Reviews: