American Standard 2A6H1018-060 Installer'S Manual Download Page 2

PAGE 2

Pub. No. 11-BC08D2-5

INSTALLER'S GUIDE

4. The top discharge area must be unrestricted for at least
five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the roof
will support the unit’s weight. Properly selected isolation is
recommended to prevent transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to
indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler, maximum
lift should not exceed sixty (60) feet (suction line).  If air handler
is mounted above condensing unit, maximum lift should not
exceed sixty (60) feet (liquid line).

8. Locate and install indoor coil or air handler in accordance
with instruction included with that unit.

C. ACCUTRON™  FLOW CONTROL VALVE

If the indoor unit System Refrigerant Flow control is an
Accutron™ orifice and check valve assembly, an orifice size
change may be necessary.

The outdoor model determines the required orifice size.  Check
the listed orifice size on nameplate of the selected outdoor model.
If the indoor unit is factory shipped with a different orifice size,
the orifice must be changed to obtain system rated performance.

IMPORTANT:

  The outdoor unit is shipped with the proper size

orifice and a stick-on orifice size label in an envelope attached to
the outdoor unit. Outdoor unit nameplate will have correct
orifice size specified as BAYFCCV --- A for rated performance.

D. INSTALLING REFRIGERANT LINES

▲ 

CAUTION:

If using existing refrigerant lines

make certain that all joints are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor unit
for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may be
straight or with a 90 degree bend, depending upon situation
requirements. This should be thoroughly checked out before
ordering refrigerant line sets.

The gas line must always be insulated.

▲ 

CAUTION:

In scroll compressor applica-

tions, dome temperatures may be hot. Do not touch top of
compressor, may cause minor to severe burning.

The units are factory charged with the system charge required
when using  fifteen (15) feet of connecting line.  Unit nameplate
charge is the same.

Final refrigerant charge adjustment is necessary. 

Use the

Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space limitations.

NOTE:

  Large diameter tubing will be very difficult to rebend once

it has been shaped.

3. Determine the best starting point for routing the refrigerant
tubing — INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both liquid
and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and properly
secure the tubing before making connections.

8. To prevent a noise within the building structure due to
vibration transmission from the refrigerant lines, the following
precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation type hangers.

b. Isolation hangers should also be used when refrigerant

lines are run in stud spaces or enclosed ceilings.

BASEPAN TAB REMOVAL

2

BRAZE TYPE INDOOR END

3

SEALING CAP

ADAPTER

FLOW CONTROL
CHECK VALVE
(F.C.C.V.) ORIFICE

FIELD SUPPLIED
LIQUID LINE

AS SHIPPED

BODY

ACCUTRON

TM

COMPONENTS

LIQUID LINE SERVICE VALVE

4

Summary of Contents for 2A6H1018-060

Page 1: ...levated Insure that drain holes in unit base pan are not obstructed prevent ing draining of defrost water 2 If possible avoid locations that are likely to accumulate snow drifts If not possible a snow drift barrier should be installed around the unit to prevent a buildup of snow on the sides of the unit and should be of sufficient distance from the unit to prevent restriction of airflow to and fro...

Page 2: ...ves of outdoor unit for compressor suction and liquid pressures The indoor end of the recommended refrigerant line sets may be straight or with a 90 degree bend depending upon situation requirements This should be thoroughly checked out before ordering refrigerant line sets The gas line must always be insulated CAUTION In scroll compressor applica tions dome temperatures may be hot Do not touch to...

Page 3: ...rt valve core be removed and a wet rag wrapped around the valve body NOTE Usecaretomakesurethatnomoistureenterspressuretap port while wet rag is being used NOTE Precautions should be taken to avoid heat damage to basepan during brazing It is recommended to keep the flame directly off of the basepan 7 Use a Dry Nitrogen Purge and Brazing Alloy without flux whenbrazingthefieldlinetothecopperfactoryc...

Page 4: ...te disconnect switch at the outdoor unit 4 Ground the outdoor unit per local code requirements 5 Provide flexible electrical conduit whenever vibration trans mission may create a noise problem within the structure 6 The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit the thermostat and the indoor unit Table 1 NEC Class II Wiring FRC_DFT TEST_COMM...

Page 5: ...l and Checkout Procedures which are found in this instruction on page 8 To obtain proper performance all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts J ELECTRIC HEATERS Electric heaters if used are to be installed in the air handling device according to the instructions accompanying the air han dler and the heaters K START CONTROL Some...

Page 6: ...2A6H2042A 3 1 832 32 3 4 829 32 5 8 756 29 3 4 7 8 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2A6H2048A 3 1 933 36 3 4 829 32 5 8 756 29 3 4 1 1 8 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2A6H2060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2A6H4018B 3 2 832 32 3 4 829 32 5 8 756 29 3 4 5 8 1 4 137 5 3 8 86 3 3 8 210 8 1 4 79 3 1 8 508 20...

Page 7: ...Pub No 11 BC08D2 5 PAGE 7 INSTALLER S GUIDE MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 1 ...

Page 8: ... Blower Won t Start DEFROST Unit Won t Initiate Defrost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H I G H V O L T A G E W I R I N G C O M P R E S S O R I O L R U N C A P A C I T O R S T A R T C A P A C I T O R S T A R T R E L A Y C O N T A C T O R C O N T A C T S L O W V O L T A G E W I R I N G C O N T R O L T R A N S F O R M E R T H E R M O S T A...

Reviews: