AMERICAN METAL AMERIVENT HS Installation & Assembly Instructions Manual Download Page 7

7

AmeriVent Model HS/HSS All-Fuel Chimney

Installation Instructions

b. For wall thickness less than 8 inches, use a 12-inch

long piece of chimney.  For walls 8 inches or thicker,
you must use an 18-inch or 24-inch long piece of
chimney.  Make sure that the 4½-inch minimum
dimension shown in Figure 26 is maintained.  Attach
the chimney section to the chimney tee branch in the
same manner described in A.2., Page 2.  Slide this
assembly of chimney and tee through the thimble as
shown in Figure 24.  The tee cap fits on the inner wall
at the bottom end of the tee trunk (see Figure 23).
When the chimney tee is fixed securely in place, add a
bead of high-temperature silicone sealant at the
interface where the tee branch passes through the wall
thimble on the exterior surface to prevent air infiltration.

c. Install wall support per separate wall support

instructions, and secure support to wall with lag
screws or toggle bolts (see Figure 26).

3.

Assemble Chimney Sections

a. Assemble per Section A.2., Page 2.
b. Support Bracket Assembly must be used every other

section or every 6 feet, and must be secured to wall by
lag screws or toggle bolts to provide lateral support of
the chimney and to ensure correct spacing to wall.

4.

For Overhanging Roofs

a. If roof overhangs the wall of the structure so that

passage of the chimney is obstructed, it is necessary
to cut a hole in the overhang.  Leave a minimum of 2-
inch clearance and install the flashing and storm collar
per Section A.6.a-e., Page 4 (see Figure 14).

b. Alternate Method:  Cut away the portion of overhang

as shown in Figure 25, allowing for minimum 2-inch
clearance to combustible material.  Do not use 30°
offsets to overcome overhang.

5.

Chimney Cap

Install the chimney cap per Section A.6.f., Page 5.

6.

Extended Height

If the chimney extends more than 5 feet above the roof, it
will require additional bracing.  We suggest using a Roof
Brace Kit or a field-fabricated assembly per section A.6.g.

7.

Connect Appliance to Chimney

a. Slip the black single-wall adapter furnished with the

tee over the inner liner of the branch of the chimney
tee with the adapter’s 45° flange toward the tee (see
Figure 26).  Position the black pipe end plate over the
single-wall adapter and over the end of tee branch.
Fasten pipe end plate to outer wall of the tee branch,
using a minimum of two (2) ³/

8

-inch sheet metal

screws furnished with end plate.

b. Connect the appliance to the chimney’s single-wall

adapter (see Figure 26) by using a minimum 24-gauge
single-wall connector pipe.  Clearances from
connector pipe to combustible material shall be as
specified in Chapter 5 of the National Fire Protection
Association (NFPA) Standard 211.

NOTE:

For reduced clearance applications or mobile
home installations, AmeriVent Model DCC
Double-Wall Chimney Connector is also available.

Summary of Contents for AMERIVENT HS

Page 1: ...is galvanized steel This chimney is listed UL 103 TYPE HT for venting flue gases not exceeding 1000 F under continuous operating conditions In addition UL has conducted additional tests at 1400 F for...

Page 2: ...ey installation requirements AmeriVent Model HS all fuel chimneys may be connected directly to a masonry fireplace by using an AmeriVent anchor plate instead of a standard support IMPROPER INSTALLATIO...

Page 3: ...irestop must be installed on the top of joist in the same manner described in Section a 4 Attic Insulation Shield Cat No 6 8 HS AIS If the chimney passes through an attic space one of the following me...

Page 4: ...upport Bracket Assembly see Figure 10 You may need to temporarily support the offset during assembly The offsets use the same locking system as the pipe sections described in Section A 2 Page 2 6 Chim...

Page 5: ...ing is completed nail through all four sides of roof support into framework installed in Step b Use a minimum of sixteen 16 8d nails f Install the single wall adapter furnished with the support by pus...

Page 6: ...o 6 8 HS WTP a Install the wall thimble through opening in wall with the black painted surface on the inside wall see Figure 22 Screw each trim plate in place through the four 4 prepunched holes on ea...

Page 7: ...ssage of the chimney is obstructed it is necessary to cut a hole in the overhang Leave a minimum of 2 inch clearance and install the flashing and storm collar per Section A 6 a e Page 4 see Figure 14...

Page 8: ...vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flu...

Reviews: