background image

2

1. Adequate air supply must be provided for combustion
and venting of appliance. Local codes or NFPA 54 specify
minimum requirements for combustion ventilation and
dilution air.

NOTE: Failure to provide adequate air may result in
extreme hazards to life.

2. Ameri-Vent  Gas Vent is suitable for installation inside
or outside. However,the sizing tables in NFPA 54 are for
vents not exposed to the outdoors below the roof line.
Outside vents could reduce venting action; therefore,
such installations are not recommended. In the event
outside venting is necessary, vents should be sized as
close to maximum capacity as possible. Whenever pos-
sible outside vents should be enclosed inside a chase
which maintains the minimum one (1) inch clearance to
combustibles. Appliances served by an outside vent
must have an adequate air supply to balance inside
and outside air pressure to reduce the possibility of
reverse venting action.

3. The vent should be sized for the sea level name
plate input rating of the appliance in accordance with
the procedures set forth in NFPA 54 (The National Fuel
Gas Code), or the American Metal Products Gas Vent
Capacity Tables (EP-GVC).

4. When installing, make sure arrow on the Ameri-Vent
part is pointed up or away from the appliance.

5. When installed as a Type B Gas Vent, a minimum of
one (1) inch air space clearance to combustible mate-
rial is required. For Type B 2x4 and BW Vents see
Section 2, page 9 for clearance to combustibles. All
locking joints are to be securely snap-locked together.
See the rear page of these instructions for detailed
information about locking and unlocking vent sections.
The first vent section must be screwed to the appliance
outlet collar.

6. Ameri-Flex Model FC Gas Vent Connector should
be installed in accordance with our installation instruc-
tions. Unlisted single wall connector pipe shall be
securely supported and joints fastened with sheet
metal screws, rivets or other approved means. At the
point of connection of the single wall connector pipe to
the double wall gas vent, three sheet metal screws or
rivets may be used as an approved means.

NOTE: Do not use sheet metal screws at the lock
joints of Ameri-Vent Model E, R, and O Gas Vents

7. Wherever possible, install vertical vents directly
above appliances before beginning any lateral runs.
Lateral venting should be kept to a minimum to avoid
vent resistance. Horizontal runs to vents should either
be in accordance with the appropriate tables in NFPA
54, or should not exceed 75% of the vertical height of
the vent. Laterals should be supported. Excessive

General Installation Guidelines

number of fittings, such as elbows and tees, should be
avoided.

8. Maintain a pitch or rise from the appliance to the vent
cap on horizontal runs. The pitch shall not be less than 1/4
inch to the foot.

9. Vents must terminate vertically above the roof line.
Refer to the Termination of Vent Structure section on page
10 for details.

10. Strap or support vents securely in position to maintain
a minimum of one (1) inch air space clearance to
combustibles.

11. Firestops must be used where vents pass through
floors or ceilings.

12. More than one gas appliance may be vented into a
common vent. Close attention should be paid to vent
sizing to assure adequate venting action.

13. Portions of gas vents which may extend through
accessible spaces are to be enclosed to:

a) Maintain the one (1) inch minimum air space

clearance.

b) Avoid personal contact with the vent.

c) Avoid damage to the vent.

IMPORTANT:The enclosure must provide a minimum
of one (1) inch air space to all combustible material
and building insulation. Refer to section 2, page 9 for
Type B 2x4 and BW clearances.

14. In many types of buildings, such as multi-family
residential, high-rise and others, vents which pass through
floors or ceilings must be located in fire rated shafts or
chases with no openings, except for inspection access.
Consult local building code for proper wall construction,
access, clearance, support, initial penetration of breeching
and method of termination, or refer to the National Fuel
Gas Code (NFPA 54).

15. Never vent gas appliances into an unlined masonry
chimney. Install either Type B Gas Vent or a listed metal
relining system inside chimney to reduce condensation
and reduce the chances of improper venting which could
occur in unlined chimneys.

NOTE: While handling sheet metal parts, it is
advisable to wear gloves to avoid personal injury
from sharp edges or projections.

16. If a power vent fan is used, make sure it is located at
the terminus so as to maintain negative pressure within
the vent.

17. The gas venting system should be inspected prior to
the heating season by a qualified technician. This
inspection should include removal of the cap to confirm an
unrestricted vent.

Summary of Contents for AMERI-VENT E

Page 1: ...NT AND ACCES SORIES ARE NOT TO BE USED WITH INCINERATORS OR WITH APPLIANCES BURNING SOLID OR LIQUID FUELS Vent sizing and installation are to be made in accordance with all applicable local building c...

Page 2: ...eginning any lateral runs Lateral venting should be kept to a minimum to avoid vent resistance Horizontal runs to vents should either be in accordance with the appropriate tables in NFPA 54 or should...

Page 3: ...rews Each joint of the singlewall system must be connected with three 3 sheet metal screws Singlewall connector must not penetrate any walls or ceilings or be used in any cold or non routinely inspect...

Page 4: ...he bucket Attach the mounting tabs with sheet metal screws 3 Provide additional strapping or hangers for connector offsets Firestop Supports The Firestop Support FSP and Support Bracket SB are designe...

Page 5: ...ports must not in any case exceed 30 feet 2 The circular cutout in the Round Support Plate is designed to engage the uppermost recess in the female end of the Vent Pipe See Fig 10 3 Surround the Vent...

Page 6: ...sition at each opening where a support is to be used The Adjustable Length Section also provides relief for linear thermal expansion The Adjustable Length Section should be positioned directly under t...

Page 7: ...e outer wall of the Vent Pipe and the hole cut in the structure In attics the Firestop should be placed on top of the framed ceiling opening to pre vent insulation and debris from coming into contact...

Page 8: ...thTwo 45 Vent Elbows One One One One One One One Size A B ONLY 6 Length 12 Length 18 Length 24 Length 3 Length 4 Length 5 Length 3 3 2 3 4 3 1 4 6 3 4 11 15 1 4 19 1 2 28 36 1 2 45 4 3 7 8 3 1 16 3 1...

Page 9: ...for the following applications and clearances to combustibles as shown in Table 5 Type B Oval Gas Vent Type B Oval Gas Vent is available in sizes 4 5 and 6 inch and requires a 1 inch clearance to com...

Page 10: ...Shield In some areas the building code requires the use of an attic insulation shield AVS on single story Type B W installations Termination of Vent Structure The Ameri Vent Gas Vent is available for...

Page 11: ...gin venting action Hold a lighted match along the rim of the draft hood relief opening of the appliance Proper venting will draw the flame up or into the draft hood Improper venting indicated by escap...

Page 12: ...together until couplers SNAP LOCK 3 Pipes are now firmly connected FORM NO 100571D BVERO II COPYRIGHT 1999 AMERICAN METAL PRODUCTS Model O Model E and R 1 Place female coupler over preceding male coup...

Reviews: