american flame AF-1000 Series Instruction Manual Download Page 8

 

 

 

REV. 1/9/2010    

Page 8 of 9

   

 
 
 
 

 
Equipment Danger Hazard. Improper adjustment of gas input and burner can cause carboning and/or unnecessary 
shutdown of the system.

 

1.  Do not exceed the input rating stamped on the appliance nameplate, or manufacture recommended burner orifice pressure 

for size orifice(s) used. Be sure primary air supply to the main burner is properly adjusted for complete combustion. Follow 
the instructions of the appliance manufacturer. 

2.  IF CHECKING GAS INPUT BY CLOCKING GAS METER: Be sure there is no gas flow through the meter other that to the 

appliance being checked. Other appliances must remain off with the pilots extinguished (or the consumption must be 
deducted from the meter reading). Convert the flow rate to Btuh as described in the GAS Controls Handbook, from 70-2602, 
and compare to the Btuh input rating on the appliance nameplate. 

 
Check Safety Shutdown Performance 
 
 
 
 
 
Fire or explosion hazard. Can cause property damage, severe injury or death. 

1.  Preform the safety shutdown test any time work is done on a gas system. Place the gas control knob in the PILOT position. 

Main burner should go off and the pilot should remain lit. 

2.  Extingush the pilot flame. The AF-1000 pilot gas flow should stop within three (3) minutes when using a standard 

thermocouple. When using a quick drop out thermocouple, the pilot gas flow should stop within thirty (30) seconds. Safety 
shutoff of the pilot gas proves complete shutdown because safety shutoff valve prohibits main burner and pilot gas flow. 

3.  Relight pilot burner and operate the system through one (1) complete cycle to ensure all controls operate properly. 

 
MAINTENANCE 

 
 
 
Fire or explosion hazard. Can cause property damage, severe injury or death. 

Do not attempt to take apart the gas control or to clean it. Improper assembly and cleaning can cause unreliable operation. 
Regular preventive maintenance is important in applications that place a heavy load on the system such as those used in 
commerical cooking, agricultural, and industrial application because: 
 

  In many such applications, particularly commerical cooking, the equipment operates 100,000 to 200,000 cycles per year. 

Such heavy cycling can wear out the gas control in one to two years. 

  Exposure to water, dirt, chemicals, and heat can damage the gas control and shut down the control system. 

The maintance program should include regular checkout of the system as outlined in the Checkout section, and checkout of the 
system as discribed in the appliance manufacturers literature.  
Maintance frequency must be determined individually for each application, Some considerations are: 
 

  Cycling frequency. Appliances that may cycle 20,000 times annually should be checked monthly. 

  Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use. 

  Consequence of unexpected shutdown, Where the cost of an unexpected shutdown would be high, the system should be 

checked more often. 

  Dusty, wet, or corrosive envirornment. Because these environments can cause the gas control to deteriorate more rapidly, 

the system should be checked more often. 

Any control should be replaced if it does not perform properly on checkout or service. In addition, replace any module if it is wet 
or looks like it has been wet. 

 

 
 
 
Fire or explosion hazard. Can cause property damage, servere injury or death. 

Do not disassemble the gas control; it contains non replaceable components. Attempted disassembly or repair can damage the 
control. 

 

 

 

 

f i r e - p a r t s . c o m

Summary of Contents for AF-1000 Series

Page 1: ...pe of Valve 0 Vented Control Valve 1 Ventfree Control Valve FEATURES Multi positional All Plans Versatile Mounting Power unit powered by 30mv thermocouple CSA rated capacity 80 000 BTU hr at 1 wc pres...

Page 2: ...lead Option 8mm x1 0 connection Ventfree Thermocouple location Back of valve Ambient Temperature Range 0 0 F to 225 0 F 18 0 C to 107 0 C Voltage 30 mV Thermocouple Approvals CSA International Report...

Page 3: ...REV 1 9 2010 Page 3 of 9 DIMENSIONS fire parts com...

Page 4: ...rce or any attempt to repair the gas control valve can result in fire or explosion Location Locate the AF 1000 gas control where it cannot be affected by steam cleaning high humidity dripping water co...

Page 5: ...ents main gas flow through the valve 2 ON Permits main burner and pilot flow Gas control and remote control of main burner gas flow 3 PILOT Opens pilot valve and allows gas flow to pilot burner NOTE W...

Page 6: ...stment per test standard Shut off Procedure 1 To shut OFF the system turn the gas control knob clockwise to the OFF position This action will close the main gas valve and disengages the safety pilot v...

Page 7: ...property damage servere injury or death 1 Stand away from the main burner while lighting Hidden gas leaks can cause flashbacks in the appliance 2 Check for gas leaks with rich soap and water solution...

Page 8: ...explosion hazard Can cause property damage severe injury or death Do not attempt to take apart the gas control or to clean it Improper assembly and cleaning can cause unreliable operation Regular pre...

Page 9: ...mocouple You must press and hold the gas control knob in the PILOT position to maintain the gas flow to the pilot If the output does not meet the minimum voltage replace the thermocouple The power uni...

Reviews: