If using line cord—

REGULATORY REQUIREMENT:  Use only polarized 
plug/cordsets; non-polarized plugs invalidate regula- 
tory approvals!  The cord must be type H05 VV-F or 
H05 VV H2-F, with minimum conductor size of .75 mm 
and fitted with a connector rated at 10 A.  The cord 
anchor will accept cords with an outer diameter in the 
range of 5mm to 9mm.  A butt terminal must be 
installed on the stranded-wire yellow-green ground 
wire.

Place the cord anchor in the knockout, and pass a 
length of cord thru the anchor.
Remove the outer sheath and cut the length of the 
three wires inside so that the ground wire will be the 
last to break if the anchor fails—REGULATORY 
REQUIREMENT. The line and neutral wires connect to 
TB3; the ground wire connects to the ground lug.
Connect the line and neutral leads to TB3 using the 
adjacent table—50 or 60 Hz.
Install butt terminal on ground wire.  For cords with a 
wire size of 18 - 22 guage, use butt terminal 
2141-0035-01 from the install kit.  For cords with a 
wire size of 14 - 16 guage, use terminal 2141-0035-02 
from the install kit.
Attach ground wire to ground lug on enclosure.
Tie wrap the line and neutral leads close to the TB3 
terminal block—REGULATORY REQUIREMENT.
Tighten cord anchor in place to secure the cord.

J-Box, cover removed

D.  Connect Power to J-Box

1.
2.

3.

If using conduit—
Route electrical power into J-box thru small knockout.
Connect electrical service using the table below—50 
or 60 Hz.
Make sure ground wire is secured to ground lug on 
enclosure—REGULATORY REQUIREMENT.

E.  Secure Cover and Test Installation

Sheet 2

Jones Connectors 

TB3, AC Line Power
Terminal Block

Video Channel

Data Cable Spring- 
loaded Terminal Blk

11"

Plate Assy Screws

Enclosure

Enclosure/Bumper 
Mounting Holes
7 mm (.28 in) dia.

28 cm (11 in)

43.2 cm

(17 in)

1

Mtg/Bracket Holes

(top of J-Box) 

Ground Lug 

2

60 Hz Line Cord

60 Hz Conduit

Hot

Neutral

Ground

Hot

Neutral

Ground

(brown)

(blue)

(green)

TB3-1

TB3-2

Gnd Lug

50 Hz Line Cord

50 Hz Conduit

L (Hot)

N (Neutral)

Ground (green/yellow 

or copper)

L (Hot)

N (Neutral)

Ground

TB3-1

TB3-2

Gnd Lug

V8000-0320-01    Rev  D

(60 Hz version shown; 50 Hz has 2 xfmrs.)

RJ860AP/RJ860AP1/RJ860AP2 50/60 Hz J-Box Installation