53
•
If RTD (Resistive Temperature Device) probe is defective, replace the probe.
NOTE
: If
ALL
systems check out fine, call the
ADC
Service Department at (508) 678-9000.
2. No Control Power (“
BLUE
” Light Off)
a. PROBABLE CAUSES;
1a) Line voltage from main fused disconnected.
2a) Main disconnect on the ADG-464 is turned off.
3a) OL11 (overload #11) tripped.
4a) Fuse #1 is blown.
b. POSSIBLE SOLUTIONS;
1b) Verify main line voltage to ADG-464
• If line voltage is present go to
paragraph #2b below
.
• If line voltage is not present check fused disconnect and retest.
2b) Attempt to turn the ADG-464 main power handle to the “ON” position.
•
If the switch does not engage, verify that sprinkler power is “ON” (“
RED
” light on main door).
•
If “no,” refer to
paragraph #1b above
.
3) Open main enclosure and verify that OL11 has not tripped.
•
If yes, check circuit, restart and test.
•
If no go to
section #3 on page 54
.
•
Verify that fuse #1 has not blown, check that the “
RED
” L.E.D. indicator is off.
•
If “on” (fuse block L.E.D. “ON”), check circuit, replace fuse and test.