background image

9

WARRANTY

Units carry a 15 year warranty on the heat recovery core
and a 2 year replacement parts warranty.

HRV 1200SFD/1200SDD PLUS

HEAT RECOVERY VENTILATOR

PRODUCT

SPECIFICATIIONS

AND ENGINEERING

INFORMATION

DIMENSIONS 1200SFD/SDD PLUS 

inches (mm)

SPECIFICATIONS

CORES - Modular (3 section) patented aluminum heat recovery
cores arranged for efficient cross-flow ventilation.
MOTORS - Two PSC, 3 speed double shafted, 120 VAC, 9.4
Amps each (18.8 total on high speed). HP - 1/2, 1625 RPM.
Watts - total on high speed - 2256.
FILTERS - Washable air filters in exhaust and supply air
streams.
BLOWERS - Centrifugal type rated at 1200 cfm (566 L/s) free
air delivery.  Each air stream has one double shafted motor
driving 2 centrifugal blowers.
CONNECTION DUCT SIZES - Four - 20” x 8” (508 mm x 200 mm).
MOUNTING - Unit to be set on support brackets hung by
threaded rod type apparatus (brackets and rods not provided).
CASE - 20 gauge prepainted galvanized steel (G60) for superior
corrosion resistance.  Insulated with foil faced insulation where
required to prevent exterior condensation.  Drain connections,
2 - 1/2” (12 mm) O.D.
CONTROLS & FUNCTION - Integrated microprocessor circuit
board.  Built-in interlock contacts.  Automatic Self Test.  Optional
remote speed control.
DEFROST CONTROLS
Model 1200SFD PLUS - Interrupts supply air while exhaust air
defrosts core.
Model 1200SDD PLUS - Supply bypass routes indoor air to
defrost core.
WEIGHT - 210 lbs. (95 kg) SHIPPING WEIGHT - 234 lbs. (106 kg)

OPTIONS

28 998

Sixty Minute Timer (2 Wire)

28  879

Digital Electronic Timer - 20, 40, 60 Minute (3 Wire)

28 883

Dehumidistat Ventilation Control (DVC) Remote

dehumidistat and on/off control (3 Wire)

28 882

Dehumidistat Control - Remote Wall Mount, Low

Voltage 20-80% RH (2 Wire)

28 885

3 Speed Control (4 Wire)

All units conform to CSA and UL standards.

HIGH SPEED

MED. SPEED

LOW SPEED

Summary of Contents for HRV 700SDD

Page 1: ...e requirements of modern tightly built and highly in sulated buildings It provides a consistent supply of fresh air while lowering heating costs during the winter by transferring heat from the exhaust air to the fresh air stream During the summer it also reduces the load on the air conditioner by lowering the temperature of the fresh outdoor air The system pro vides an economical solution for exce...

Page 2: ...tomatic operation Defrost Model 700SDD Supply bypass routes indoor air to defrost core Model 700SFD Supply fan shuts off while exhaust contin ues to defrost core Defrost light indicates defrost mode Preset 27 F 3 C Duct Connections Four 14 X 8 356mm X 200mm Model 700SDD has fifth 14 x 8 duct connection on top surface Drain Connections Two 1 2 O D Mounting Unit to be set in support brackets hung by...

Page 3: ... filters in exhaust and supply air streams BLOWERS Centrifugal type rated at 329 L s 700 CFM free air delivery Each air stream has one single shafted motor driving a centrifugal blower CONNECTION DUCT SIZES Four 14 x 8 356 mm x 200 mm MOUNTING Unit to be set on support brackets hung by threaded rod type apparatus brackets and rods not provided CASE 20 gauge prepainted galvanized steel G60 for supe...

Page 4: ... wetted deck areas up to 700 square feet Thepoolmodelhasthreemodes of operation to meet the unique needs of pools The normal ventilation mode provides ex haust of humid air and supply of fresh outdoor air with heat re covery in the efficient aluminum cores This mode is controlled by an adjustable dehumidistat that opens the fresh air damper to the outdoor air intake and operates both the supply an...

Page 5: ...Motors Two efficient three speed PSC double shafted motors 120 VAC 2 75 Amps each 5 5 Amps total on high speed 1 10 HP 1625 RPM Watts total on high speed 648 Blowers Centrifugal type rated at 700 CFM 329 L s free air delivery Each air stream has one double shafted motor driving a centrifugal blower Rubber isolated mounts Controls Illuminated power switch 3 speed blower control low voltage 24 VAC t...

Page 6: ...humidity odors stuffiness and other indoor air pollutants Asthetwoairstreamspassthrough theHRV theyareseparatedbythin plates of aluminum in the core The air streams do not mix so there is no recontamination of the fresh air by stale air Heat passes through the thermally conductive aluminum from the warmer air stream to the colder air stream recovering most of the energy otherwise lost to the outdo...

Page 7: ...PSC motors and rubber isolated mounts Three speed motors 120VAC 60 Hz 1 ph Controls Illuminated power switch three speed blower control low voltage 24 VAC terminals for connection of remote controls and defrost light indicating automatic operation Defrost Supply bypass damper directs indoor air to defrost core Defrost light indicates when automatic damper defrost occurs preset 27 F 3 C Operating C...

Page 8: ...assrooms dormitories res taurants health clubs etc It is a technically advanced con trolled mechanical ventilation sys tem to meet the requirements of modern tightly built and highly in sulated buildings It provides a consistent supply of fresh air while lowering heating costs during the winter by transferring heat from the exhaust air to the fresh air stream During the summer it also reduces the ...

Page 9: ...ors Two efficient three speed PSC double shafted motors 120 V 4 Amps each 8 1 Amps total on high speed 1 ph 1 4 HP 1625 RPM Watts total on high speed 972 Blowers Centrifugal type rated at 1200 CFM 566 L s free air delivery Each air stream has one double shafted motor driving a centrifugal blower Rubber isolated mounts Controls Illuminated power switch 3 speed blower control low voltage 24 VAC term...

Page 10: ...upport brackets hung by threaded rod type apparatus brackets and rods not provided CASE 20 gauge prepainted galvanized steel G60 for superior corrosion resistance Insulated with foil faced insulation where required to prevent exterior condensation Drain connections 2 1 2 12 mm O D CONTROLS FUNCTION Integrated microprocessor circuit board Built in interlock contacts Automatic Self Test Optional rem...

Page 11: ...eet the unique needs of pools The normal ventilation mode provides ex haust of humid air and supply of fresh outdoor air with heat re covery in the efficient aluminum cores This mode is controlled by an adjustable dehumidistat that opens the fresh air damper to the outdoor air intake and operates both the supply and exhaust fans A duct heater or hot water coil may be installed in the supply duct t...

Page 12: ...nsulation where surface is ex posed to cold air Access door is hinged and latch Disconnect switch engaged by door panel Condensate pan has drain connections Heat Exchange Core Three modules aluminum plate heat ex change core assembly Air filter Six washable filters Motors Two efficient three speed PSC double shafted motors 120 VAC 4 Amps each 8 1 Amps total on high speed 1 4 HP 1625 RPM Watts tota...

Page 13: ...1 3442 www americanaldes com e mail info aldes us com 1232 2 05 MATHEWS GRAPHIC DESIGN 941 358 0862 HRV 1500IFD HEAT RECOVERY VENTILATOR OPTIONS 28 879 Digital Electronic Timer 20 40 60 min 3 wire 28 883 Dehumidistat Ventilation Control DVC 28 882 Remote Wall Mount Dehumidistat Control 24 VAC only 28 99 500 3 Speed Control ...

Page 14: ...al 1 5 hp BLOWERS Two belt drive centrifugal blowers with adjustable pulley airstream FILTERS Two 16 x 25 x 2 pleated filters in each airstream MERV 6 efficiency 60 4 69 microns DUCT CONNECTIONS Four 18 x 22 CABINET 20 gauge powder coated steel for superior corrosion resistance Unit includes metal lined sides and roof panels with 2 fibreglass insulation R8 between linings DRAIN Two powder coated g...

Page 15: ...ES Eight patented aluminum heat recovery cores arranged for efficient cross flow ventilation MOTORS Two single speed single shaft 208 240VAC 8 0 Amps 16 0 TOTAL 1 5 hp BLOWERS Two belt drive centrifugal blowers with adjustable pulleys one per airstream FILTERS Two 16 x 25 x 2 pleated filters in each airstream MERV 6 efficiency 60 4 69 microns DUCT CONNECTIONS Two 20 x 19 hoods included with washab...

Page 16: ...m recovering most of the energy oth erwise lost to the outdoors The Model 2500 is available with two mounting options The Model 2500SFD is intended for installa tion indoors The duct connections to the outdoors are conveniently locatednearthetop topermitduct ing up through a roof or turning horizontally for side wall intake and discharge The Model 2500SFDE mounts on an insulated roof curb supplied...

Page 17: ...while exhaust air defrosts core Duct Connections Four 24 x 16 610mm x 406mm Drain Two stainless steel drain pans with 3 4 drain spouts Mounting Unit to be set on support brackets hung by threaded rod type apparatus Brackets and rods not included Weight 700 lbs Shipping Weight 780 lbs Manufacturer AmericanALDESVentilationCorp 4537NorthgateCourt Sarasota FL34234 OPTIONS AND ACCESSORIES 28 998 CRANK ...

Reviews: