2.4C Ducting for Fresh Air 

Fresh air can be brought into the structure continuously 
by connecting a duct from outside to the DH-100V inlet 
and by turning on the fan switch. Advantages of this form 
of ventilation include: 
1. 

Outside air is filtered before entering the building. 

2. 

Outside air will be dehumidified before entering if 
the DH-100V is running. 

3. 

Drawing air from outside and blowing inside aids in 
pressurizing the structure. This helps prevent unfil-
tered and humid air from entering elsewhere. It also 
reduces the potential for carcinogenic radon gas to 
enter. 

4.  The need for an alternate ventilation device may be 

eliminated. 

(Note: Aldes Model DHV-100V is specifically 
designed for dehumidification and 
ventilation.)

 

An insulated 6" diameter duct is generally sufficient to 
provide up to 100 CFM of outside air. An adjustable 
damper is recommended for controlling the airflow. 
Large quantities of outside air will impact the DH-100V’s 
performance positively or negatively, depending upon 
the difference between inside and outside air conditions. 
Consult the factory by calling 1-800-255-7749 for 
recommendations regarding the use of higher flows with 
your specific application. 

The outside air duct should be connected into the main 
inlet duct close to the unit. If no other inlet duct is used, 
locate the outside air duct end on top of and as close as 
possible to the DH-100V air filter. 

3 Operation

 

3.1 Humidity Control Adjustment

 

Set the humidity control to the desired humidity level for 
the home. The dehumidifier will run continuously until the 
relative humidity (RH) is reduced to the humidity control 
dial setting. Setting the humidity control to lower RH 
levels will 

NOT

 increase the unit's dehumidification rate; 

the unit will simply run longer to reduce the area's RH to 
the setting. The ALDES DHV-100V unit (and refrigerant 
based dehumidifiers in general) will reduce a warm 
space's RH to a lower level than that of a cool space. It 
is therefore pointless to set the humidity control to 
excessively low levels in cool rooms; doing so will result 
in long periods of ineffective dehumidifier run time. 

Quality humidity meters are available from the factory 
and are recommended to accurately monitor humidity 
levels. 

3.2 Blower Switch

 

Turning ON the fan switch will cause the unit's internal 
blower to run continuously, whether the unit is 
dehumidifying or not. This function is desirable if the unit 
is used for air circulation or fresh air ventilation. 

4 Maintenance

 

4.1 Air Filters

 

The DH-100V is equipped with 2 air filters. A foam 
prefilter followed by a pleated fabric filter. These should 
be checked monthly. Operating the unit with dirty filters 
will reduce dehumidifier capacity and efficiency and may 
cause the compressor to cycle off and on unnecessarily 
on the defrost control. 

If dirty, the foam prefilter can be vacuumed or carefully 
hand washed with warm water and mild detergent, then 
rinsed. The pleated fabric filter can generally be 
vacuumed clean several times before needing 
replacement. Replacement filters can be ordered from 
the factory or purchased locally if available. 

DO NOT

 

operate the unit without the filters or with a less effective 
filter. The heat exchange coils inside the unit could 
become clogged and require disassembly to clean. 

4.2 Blower Oiling

 

The blower motor is factory lubricated for many years of 
normal operation. However, periodic oiling will extend 
motor bearing life. To oil, remove the plastic cap from the 
two oiling tubes extending from the unit above the 
humidity control (see Figure 3). Add 3 to 5 drops of SAE 
20 non-detergent oil to each port every 6 months. DO 
NOT use thinner oil or penetrating oil. Blower life can 
actually be decreased by such oil. 

 

Summary of Contents for DH-100V

Page 1: ...to obtain maximum benefit from your DH 100V dehumidifier 1 Specifications Model DH 100V Dehumidifier Electrical 110 120 VAC 6 8 Amps grounded Capacity 100 pints day 80 F 60 RH Operating Temp Range 53 F min 105 F max Air Flow 255 CFM without external ducting 170 CFM 0 15 in wg external static Refrigerant Charge 1 lbs 14oz R 22 Optional Duct connections 8 round inlet outlet Size w o duct collars 20 ...

Page 2: ...ied air into the room in which it s located An adequate airflow path must exist between the two rooms for this method to work well An additional humidity control may need to be mounted in the humid area and wired to the DH 100V to accurately maintain the desired humidity Local electrical codes must be followed when wiring the control 2 2 Electrical Requirements The DH 100V plugs into a common grou...

Page 3: ...onger to reduce the area s RH to the setting The ALDES DHV 100V unit and refrigerant based dehumidifiers in general will reduce a warm space s RH to a lower level than that of a cool space It is therefore pointless to set the humidity control to excessively low levels in cool rooms doing so will result in long periods of ineffective dehumidifier run time Quality humidity meters are available from ...

Page 4: ...ture across the entire coil from inlet to outlet The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil The accumulator prevents any liquid refrigerant from reaching the compressor The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature to repeat the process 5 3 Troubleshooting No dehumid...

Page 5: ...mpressor circuit Test each component for continuity see the appropriate section if a defect is suspected 3 Unplug the unit then disconnect the red and yellow wires from compressor terminals R S Using an ohmmeter check continuity between the points listed below 4 Compressor terminals C and S No continuity indi cates an open start winding The compressor must be replaced Normal start winding resistan...

Page 6: ... not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour An alternate method of removing moisture and non condensibles from the system requires evacuation to 29 Hg vacuum Then break the vacuum with 35 to 50 PSIG refrigerant vapor charge Leave the vapor charge in the system for at least 5 minut...

Page 7: ...Figure 2 Electrical Schematic of the DH 100V Dehumidifier 7 ...

Page 8: ...35 MFD 370V 4017799 1 Compressor Run Capacitor for Tecumseh 25 MFD 440V 9 4021396 1 Condenser Coil 10 4021409 1 Cord Wire Harness 11 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 11 12 4021395 1 Evaporator Coil 13 4020955 1 Filter Drier 14 4021626 1 Hose Drain 56 ID x 8 15 4021469 1 Humidity Controller 16 4021495 1 Knob Humidity Controller 17 4020554 1 Switch SPDT fo...

Page 9: ...nd American ALDES Ventilation Corporation s reasonable control Limitations and Exclusions If any American ALDES Dehumifier Dehumidifying Ventilator part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto All warranty periods shall be extended by the period of time if any that the unit is out of service while awaiting co...

Page 10: ...10 ...

Reviews: