background image

11

Ducting - General

Drains

Connect the drain pans in the bottom of the HRV to a drain
line fastened to the holes provided. Create a “P” trap to
prevent odors from being drawn through. Make sure the
drain line slopes down to drain properly and if this is not
possible a condensate pump will be required for removal
of the water. Note that stagnant water is a leading cause of
indoor air quality problems; confirm drainage after installa-
tion by pouring water into trays. Drain line must be installed
where it will not freeze.

The Ductwork System

A well designed ducting system will allow the HRV to oper-
ate at its maximum efficiency. Avoid the use of undersized
ducting and sharp radius bends and tees which can signifi-
cantly increase the system pressure drop and reduce the
air flows.

NOTE: Fully insulated ducting with an integral vapor bar-

rier must be used on all runs passing through un-
heated areas in order to avoid condensation prob-
lems and energy losses from the air streams.

* Consult local Codes

To minimize pressure drop and noise, galvanized metal
ducts sized for 1200 fpm (6.09 m/s) (maximum velocity)
are recommended. Keep ducting as short as possible and
use a minimum of elbows and tees. Connecting sections
and shorter runs may be flexible ducting one size larger
than the metal duct. Use flexible duct connectors at the
HRV to avoid noise transmission. All duct joints must be
secured with screws, rivets or duct sealant and sealed with
aluminum duct tape to prevent leakage.

Outside Weatherhoods

The HRV 1500 SFDE is shipped with 2 weatherhoods inside
the cabinet which attach to the outer ends of the cabinet
using bolts provided. The HRV 1500 SFD requires exterior
hoods to be provided by the contractor.

NOTE: It is extremely important to design and install the

fresh air intake in an area where the hoods will
gather the freshest air, free from restriction.

Recommended:

No less than 10 ft. (3 m) apart from each other, or per
local code restriction.

At least 18 in. (46 cm) above ground level.

Away from sources of contaminants, such as automobile
exhaust fumes, gas meters, garbage containers, cooling
towers, etc.

Not exposed to prevailing winds, whenever reasonably
possible.

The outside perimeter of the weatherhood must be caulked
to prevent leakage into the building. The design and size
of the weatherhoods or louvers chosen by the installer must
allow for adequate free area. Water and snow penetration
of the system is minimized when the airflow does not ex-
ceed 750 FPM (3.81m/s) free area velocity.

Ducting from the Weatherhoods

Galvanized sheet metal ducting with sufficient cross sec-
tion with an integral single piece vapor barrier should be
used to connect the HRV to the weatherhoods. All ducting
must meet ULC Class 1 Fire Rating. A minimum R value of
insulation should be equal to 4 (RSI 0.75), or as stated in
local codes. A good bead of high quality caulking (prefer-
ably acoustical sealant) and taping with a high quality alu-
minum foil tape is recommended to seal the duct to both
the HRV and the weatherhood.

Warmside Ducting - General

Ducting from the HRV to different areas within the building
should be galvanized metal whenever possible. To mini-
mize airflow losses in the ductwork system, all ducts should
be as short as possible and with as few bends or elbows as
possible. 45° elbows are preferred to 90° elbows, when-
ever possible. Use Y tees instead of 90° tees whenever
possible. All duct joints must be fastened securely and
wrapped with a quality duct tape to prevent leakage. We
recommend aluminum foil tape.

Summary of Contents for 1500 SFDE

Page 1: ...l failure may result in the backdrafting or improper function ing of vented combustion equipment TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION ___________________________________________________________________ Installing Contractor ___________________________________________________________________ Telephone Contact ___________________________________________________________________ Serial Num...

Page 2: ...s being exhausted These instructions are intended as a general guide and do not supercede local codes in any way Con sult authorities who have jurisdiction before install ing INTRODUCTION TABLE OF CONTENTS Cover Installation Information 1 General 2 Engineering Data 3 4 Function and Controls 5 Additional Features 6 Servicing 7 Mounting the 1500 8 Roof CurbAssembly Instructions 9 Roof Curb Detail 10...

Page 3: ...s with 1 2 O D drain connections MOUNTING Unit to be set on support brackets hung by threaded rod type apparatus Brackets and rod not included CONTROLS FUNCTION Integrated microprocessor circuit board 3 independently adjustable motor speeds WEIGHT 480 lbs 218 kg SHIPPING WEIGHT 525 lbs 238 kg Engineering Data Model HRV 1500 SFD DIMENSIONS 1500SFD inches A B C D E F G H I J L SFD 18 2 5 18 12 37 66...

Page 4: ...oated steel insulated 1 thick Elastomeric insulation DRAIN Two powder coated galvanized steel drain pans with 1 2 O D drain connections MOUNTING Rooftop mounted on optional roof curb Part No 28 125 CONTROLS FUNCTION Integrated microprocessor circuit board 3 independently adjustable motor speeds WEIGHT 480 lbs 218 kg SHIPPING WEIGHT 525 lbs 238 kg DIMENSIONS 1500SFDE inches A B C D E F G H I J K L ...

Page 5: ...he designated speed taps A jumper wire is factory installed in the low speed position Note It is recommended to use the optional speed control Part 28 895 in order to obtain full fan speed control Optional Speed Control Part 28 885 Micro Processor Board Optional Remote Dehumidistat Part 28 882 Boosts unit to high speed when humidity is higher than setpoint Optional DVC Control Part 28 883 Same as ...

Page 6: ... desired airflow This is done on the ECM circuit board located within the Additional Features electrical box Both motors contain a separate ECM circuit board to allow for independent adjustment of the motors The adjust tap will change the airflows on all three of the speeds Please note that this unit has been factory set to obtain 1500CFM at 1 w g external static pressure Adjust ment of the high s...

Page 7: ...in access to either side of the unit Servicing Filters 1 Remove filter service panel one or both sides 2 Remove first set of filters 3 Remove filter divider panels if only accessing from one side 4 Remove filters from behind filter divider panel 5 Replace all filters Ensure that filter divider panels are reinserted into unit Servicing Cores 1 Remove core service panel one or both sides 2 Slide cor...

Page 8: ...8 Option 1 Unit can be suspended with U channels and Threaded Rod Mounting the 1500 Option 2 Unit can be placed on blocks sleepers ...

Page 9: ...having adequate structural strength or on roof sup ports under deck Securing the Frame To ensure proper mating with unit it is critical that mount ing frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of frame 2 Measure frame diagonally from one corner to the oppo site corner Repeat with the remaining two corners These dime...

Page 10: ...10 Roof Curb Detail for Model HRV 1500 SFDE ...

Page 11: ...uires exterior hoods to be provided by the contractor NOTE It is extremely important to design and install the fresh air intake in an area where the hoods will gather the freshest air free from restriction Recommended No less than 10 ft 3 m apart from each other or per local code restriction At least 18 in 46 cm above ground level Away from sources of contaminants such as automobile exhaust fumes ...

Page 12: ...ve the contaminants while not allowing them to enter the breathing zone of the occupants For contaminants that are lighter than air grilles should be located high on the wall If contaminants are heavier than air a lower placement of the grilles will be required Information on a contaminants specific gravity and toxicity should be available from the chemical data sheets Fresh Air Supply System The ...

Page 13: ... 1500 SFD SFDE have been programmed to provide constant airflow on each airstream for external static pres sures of up to 1 w g but at a location closer to the air handler The air handler would have a constant running blower to effectively distrib ute the fresh air and remove the stale air Balancing damp ers would be located in both the HRV supply and exhaust ducts between the return air plenum an...

Page 14: ...n the ductwork Procedure should be performed with the HRV on high speed The first step is to operate all mechanical systems on high speed which have an influence on the ventilation system i e the HRV itself and the forced air fur nace or air handler if applicable This will provide the maximum pressure that the HRV will need to overcome and allow for a more accurate balance of the unit Drill a smal...

Page 15: ...15 Wiring Diagram ...

Page 16: ...arasota FL 941 351 3441 or fax 941 351 3442 to find the name of your nearest dealer in order to repair the product The labor required to install any replacement part s shall be dealt with at the option of the customer in either of the following ways a The customer may supply labor at their own expense or b If the product was purchased from a dealer then the dealer will supply labor at cost to the ...

Reviews: