background image

INSTALLATION AND OPERATING INSTRUCTIONS

72-0106    02-26-16                                                                                                                                                                                                                            

                               7013482      314 SKSM 215 B

Page 10

WARNING

     SECTION 10: WARNING PLACARDS

     SECTION 11: ROOM CONSTRUCTION

For safety purpose sauna 

door must open out and not 

lock.

Never use a wood stain, seal 
or preservative on the inside 

of your sauna room.

Light xtures get very hot 

during operation.  Locate 

light xture where it will not 

be a burn hazard.

Two metal placards are included in the Installation Instruction Envelope 
packaged with every Sauna Heater. The CAUTION placard must be attached 
to the interior wall of the sauna room directly above the heater where it is 
visible to the bather. The WARNING placard must be attached to the door of 
the sauna room.

The "CAUTION" and 

"WARNING" placards must be 

mounted in accordance with 

Section 10.

For safety and reliability, the following rules must be addressed.
• No permanent locking or latch system is to be used on the sauna door.  • 
Acceptable door ttings are:  magnetic catches, friction catches, spring
    or gravity loaded closures.  The door must always open outwards.
• No shower may be installed in a sauna room.
• No electrical receptacle shall be installed inside the sauna room.
• The enclosed WARNING:  Reduce the risk of overheating … warning
    plate must be mounted on or alongside the door outside the sauna room
    at about eye level.
• The enclosed CAUTION:  Reduce the risk of re … caution plate must be
    mounted on the interior wall above the heater.
• The heater should not be operated without its container properly lled
    with rocks and the rock guard in place.
• If an intercom speaker is installed, it should be away from the heater and
    as close to the oor as possible.
• If a room light is installed, it should be a surface mounted bracket type.
    Wall mounted lights should be about 70" above the oor.  Ceiling
    mounted lights should be of an approved type with a junction box that is
    remote to the xture itself.  Use only a xture that uses A.F. or xture
    type internal wiring.  A 60 watt bulb should provide sufcient lighting.
• Fire sprinkler systems installed inside any sauna room should be
    properly rated for sauna room temperatures.
• Always mount the heater according to these installation instructions.

     SECTION 12: VENTILATION

VENTILATION  In a sauna, the air should be changed about 6 times an hour.  
This can be achieved by making a vent opening (fresh air inlet) in the sauna 
wall directly below the heater.  The air outlet must be lower than the upper 
benches, as far as possible from the heater and about two feet higher than 
the fresh air inlet vent, See Diagram 9. It is recommended that ventilation 
openings meet the requirements of UL Specication 875.  The minimum 
opening should be determined using one of the following formulas:
             For     R< 31,     V 

³ 

9.3,      For     R 

³ 

31,     V 

³ 

0.3R

where    R = the oor area of the room in square feet and
             V = the minimum vent size in square inches

Summary of Contents for Designer 4.5

Page 1: ...ntrol Type 1601 31 and 1601 31 1 Read all instructions carefully before installation Please leave all instructions and warranty with the owner WARNING Prolonged exposure to elevated temperatures is ca...

Page 2: ...STANCE B DISTANCE C DISTANCE D DISTANCE K DISTANCE Designer 4 5 3 0 3 5 8 4 0 11 1 2 23 Designer 6 0 4 0 4 5 8 5 0 11 1 2 23 Designer 8 0 5 0 5 5 8 6 0 11 1 2 23 HEATER MINIMUM WIRE SIZE Floor Area Ce...

Page 3: ...rvice to this equipment should be performed by quali ed licensed personnel in accordance with local and national codes Do not construct sauna room so as to restrict air ow through the bottom of the he...

Page 4: ...above the heater Insert screwdriver tip here to unsnap sensor cover from sensor Note vertical orientation of cover before removing Diagram 4 was intentionally left blank Sensor protective cover Locat...

Page 5: ...2 3 02 26 2016 P1 P2 P3 1 3 5 7 A1 2 4 6 8 A2 X1 X2 X3 X5 X7 X4 X6 X8 X9 X10 N N H Trans former 120 Volt Light Output 2 0 Amp Max Connect L1 to terminals 1 2 and 5 Connect L2 to terminals 3 4 and 6 C...

Page 6: ...26 2016 P1 P2 P3 1 3 5 7 A1 2 4 6 8 A2 X1 X2 X3 X5 X7 X4 X6 X8 X9 X10 N N H 2 3 Trans former 120 Volt Light Output 2 0 Amp Max 3 Phase Connection Connect L1 to terminals 1 and 2 Connect L3 to terminal...

Page 7: ...the control and push any excess cable into wall cavity before securing control to the wall Maximum control cable length is 50 feet Remove the adhesive tape from the back of the the control place the c...

Page 8: ...stopped Some sauna bathers enjoy the soothing effect of steam by splashing water on the heated sauna rocks Use only one dipper full approx cup at a time and keep clear of the steam as it rises off the...

Page 9: ...and the outer wall will reduce cycling of the heater b Rocks must be placed between the elements and the wall of the rock compartment Incorrect Placement of Rocks a Loosely place rocks between the ele...

Page 10: ...The enclosed CAUTION Reduce the risk of re caution plate must be mounted on the interior wall above the heater The heater should not be operated without its container properly lled with rocks and the...

Page 11: ...a oor mopped and dried in a conventional manner and the duckboard thoroughly scrubbed and dried before returning to the sauna room The sauna heater should be wiped down occasionally with a damp cloth...

Page 12: ...scale of the control The fault error code will be displayed with a constant LED light or a ashing LED light See the list below for fault codes Constant LED Fault Code ones marked with n a are not in...

Reviews: