20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
25
TASK 2
S
ET
THE
IP A
DDRESS
AND
P
ROTOCOL
2.1 Determine the Best Method for Setting the IP Address
There are two methods for setting the IP address on an RBE2-8. Table T2.1 below outlines the available
methods and when you can use them.
Table T2.1 Methods for Setting the IP Address
There is a MAC address label on each RBE2-8. It is located on the side of the painted alumi-
num frame near the RJ-45 connectors. There is an additional label next to the MAC address
label that has a writable surface. There is room on the label for writing the programmed IP
address of the unit. It is a best practice to use this label to document the IP address of the unit
in case it is ever repurposed.
The AMCI NET Configurator utility can also be used to configure the IP Address of the
RBE2-8. However, it is a more complicated method, that requires a software download and
installation. If you are already familiar and comfortable with the NET Configurator software,
feel free to use it.
In order to conform to the ODVA specification for EtherNet/IP, the RBE2-8 also supports the
DHCP protocol. You can use an EtherNet/IP DHCP server, such as the one available from
Rockwell Automation, to save the IP address to flash memory. It is supported, but AMCI
encourages you to use the embedded web server.
2.2a Use Factory Default Settings
The factory default address for the RBE2-8 is 192.168.0.50 with a subnet mask of 255.255.255.0. The easiest
way to verify this address is with the ping command as described in
Configuring Network Interfaces
which
https://www.wireshark.org/
) can be used to determine the address of the unit.
Task Complete
This section is intended for the engineer or technician responsible for setting the
IP address of an AMCI RBE2-8. The factory default IP address is 192.168.0.50. This
address is stored in flash memory and can be changed as described below.
Method
Restrictions
Section
1) The machine must use 192.168.0.xxx subnet.
2) The 192.168.0.50 address must be available.
No restrictions on use. This is the preferred method.
The internal webserver can be used to set the
RBE2-8 to any IPv4 address. The IP address and
protocol will be stored in nonvolatile memory and
used on subsequent power-ups.
Summary of Contents for RBE2-8
Page 14: ...RBE2 8 INTRODUCTION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 14 Notes ...
Page 30: ...PROTOCOL SPECIFIC INFORMATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 30 Notes ...
Page 48: ...MODBUS TCP CONFIGURATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 48 Notes ...
Page 54: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...