Write Two Point Configuration Command
In applications where the sensor is already mounted in an existing machine, you may not have access to sen-
sitivity and displacement information. In these cases, use the following command to set the Excitation Volt-
age and Excitation Frequency parameters only. When configuring the ANR2, use this command or the
, which is described on page 44. Do not attempt to use both to configure the
ANR2.
If you use this command, you must use the Two Point Linear method while in Alignment
Mode. By using this method, the ANR2 will calculate the required input amplifier gains to
work with your sensor.
Figure 6.5 Command Format: Write Two Point Configuration
ANR2 Response
The ANR2 responds to a Write Two Point Configuration command by setting the
Acknowledge Bit
in the
Module Status word as well as the appropriate error code in bits 03 through 00 of that word. If the command
is accepted without error, the four error bits will equal zero. See
starting on
page 38 for a full description of the response bits.
At this point, you must reset the
Transmit Bit
(Output Word 0, bit 15), before the ANR2 will accept another
command. The easiest way to do this is to write a value of zero into the Command Word. The ANR2 will
respond by resetting the
Acknowledge Bit
.
If there is an error response from the ANR2, correct your data and send another Write Configuration Data
command to the unit.
Save to Flash and Exit Command
Configuration parameter changes are not accepted until you exit Configuration Mode. They are lost if you do
not store the parameters in flash memory when you exit the mode. If the ANR2 experiences a hardware reset
or power loss while in Configuration Mode, the parameter changes are also lost. If you wish to store the con-
figuration data you just wrote to the ANR2, then you must exit Configuration Mode with this command.
Figure 6.6 Save and Exit Command: Network Output Data
Word
Configuration Data
Range
0
Command Word
16#A002
1
Configuration Word
See page 44
2
Excitation Voltage
800 to 12,000 (0.8 to 12 Vrms)
3
Excitation Frequency
400 to 10,000 (Hz)
4-9
Not Used
Set to 16#0000
ANR2
Word
Value
Description
0
16#800E
Command Word to exit Configuration Mode and
save parameters to flash memory.
1 – 9
16#0000
Not Used
Summary of Contents for ANR2
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A032...
Page 14: ...INTRODUCTION TO THE ANR2 ADVANCED MICRO CONTROLS INC 1 14 Notes...
Page 18: ...OPERATING MODES ADVANCED MICRO CONTROLS INC 2 18 Notes...
Page 32: ...INSTALLING THE ANR2 ADVANCED MICRO CONTROLS INC 3 32 Notes...
Page 36: ...AMCI NET CONFIGURATOR SOFTWARE ADVANCED MICRO CONTROLS INC 4 36 Notes...
Page 48: ...CONFIGURATION MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 6 48 Notes...
Page 58: ...ALIGNMENT MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 7 58 Notes...