The SR135 FIRE 24 V is a high-power back-up battery sounder (105 dB at 3 m) protected against tampering 

(opening, tearing off). It features a 10 W flasher and a sound/flash timer, variable with adjustable trimmer from 

1 min. to 7 min., which trips in case of prolonged alarm (e.g.. connection cable cutting). It has a first switch-on 

stop function to prevent the sounder from tripping during installation (for enabling the sounder for normal use 

it is necessary  to activate/deactivate alarm start).

ADJUSTMENTS AND CONNECTIONS

Rated power voltage:    

 

 

 

 

24 Vdc

Operating limit voltages:                     

 

 

20 ÷ 25 Vdc

Amp draw at max power:      

 

 

 

1.5 A

Amp draw when not operating: 

 

 

 

2.5 mA

Sound pressure (at Vn=12VDC):        

 

 

110 dB (A) at 3 m

Light power:   

 

     

 

 

 

10W

Sound and flash timer:  

         

 

 

from 1 min to 7 min ± 20%

Buffer battery:  

                  

 

 

 

12 Vdc , 2 Ah

Dimensions:                 

 

 

 

 

236 mm (L) x 280 mm (H) x 99 mm (P)

Weight (with battery):                          

 

 

2700 g

Operating temperature:               

 

 

 

- 25 °C ÷ + 55 °C

Flashing short-circuit protection fuse:       

 

 

2 A

IP grade 

 

 

 

 

 

 

54

TECHNICAL SPECIFICATIONS

Trimmer TR1 : sound and flashing timer adjustment from 1’ to 7’ ± 20%

TAMPER terminals : N.C. contact for opening and rip-off

SUPPLY terminals : 24 VDC power supply ( rated )

START terminal :

positive missing

”  

Jumper J11=    

 

open

     

 

 

Jumper J12=    

 

jumper on B

     

 

 

Jumper LAUNCHING =  

female jumper on OFF

negative missing

” 

Jumper J11=    

 

closed

     

 

 

Jumper J12=    

 

jumper on A

     

 

 

Jumper LAUNCHING =  

jumper on OFF

Start with positive

”   

Jumper J11=   

 

open

     

 

 

Jumper J12=    

 

jumper on A

      

 

 

Jumper LAUNCHING =  

jumper on OFF

Connect a 10 Kohm resistor between terminal “START” and terminal “-12 V”         

Start with negative

” 

Jumper J11=    

 

open

     

 

 

Jumper J12=    

 

jumper on B

     

 

 

Jumper LAUNCHING =  

jumper on OFF

Connect a 10 Kohm resistor between terminal “START” and terminal “+12 V”      

ENGLISH

- Configure jumpers J11, J12  (leave LAUNCHING=OFF) according to sounder starting mode.

- Connect the 12 Vdc, 2 Ah buffer battery to the red and black wires with faston;

- Connect external 24 Vdc power supply to the terminals “24 Vdc no polarity” (polarity is not important);

- Connect sounder start wire from the alarm panel to the START terminal;

- The anti-opening and anti-tearing contacts must be connected to the relevant circuit of the alarm unit 

through the TAMPER contacts;

- Time the trimmer to desired sound and flash;

- Close the metal cover using the provided screws;

- Close the sounder by means of the plastic cover.