AMC-1ACOs One Channel CO Monitor with DSI
8
4
INSTALLATION
Follow the guidelines in this section for proper locations and installation of the AMC-1ACOs. In
addition to these instructions, ensure installation is compliant with local building and electrical
codes. This section covers topics related to installation location, mounting, cable selection, and
wiring instructions the AMC-1ACOs.
4.1 MOUNTING INSTRUCTIONS
4.1.1 MONITOR MOUNTING
Securely fasten the AMC-1ACOs unit on a solid, non-vibrating surface or structure. Install the
unit where it is not exposed to rain or water spray. Install in an area where the local
concentration of gas is unaffected by the presence of ventilation systems and away from
sources of interference gases. Mount the monitor where the unit can be observed periodically.
For most applications the monitor should be mounted 1.2 -1.8 m (4-6 ft) from the floor. See
Figure 3 for mounting hole locations.
CAUTION: All cable entry MUST BE through the BOTTOM of the monitor enclosure only.
Other entry locations will allow foreign materials to enter the enclosure, causing possible
damage to the internal components.
4 HOLES
(8.875")
(5.500")
(Ø0.375")
225 mm
140 mm
Ø9.5 mm
!
ALARM
WARNING
CALIBRATE REGULARLY FOR SAFETY
1
2
(800)-465-5777
GAS MONITOR
RUN/ FAULT/ OFF
www.armstrongmonitoring.com
FIGURE 3: Locations of Mounting Holes.