The pressure switch is attached to the damper 
assembly 
 
Release the plastic cap via two screws. 
  
Connect the incoming cable to terminals: 
1 - normally closed contact 
3 - common contact  
 
Refer to low voltage external wiring diagram for 
control panel terminations. 
 
Replace the plastic cap via two screws. 

The fan damper is wired via a plug and socket arrangement. The socket is connected to the  
assembly via a bracket. 
 
Release the loose plug and 
remove the cap via two screws.  
 
Connect the incoming 24V 

 

 

cable from the Control panel 
onto terminals L3 and GND, 
ensuring correct orientation. 
 
Connect the incoming 4-20mA 
cable from the modulation 

 

 

thermostat onto  terminals L1 
and  GND,  ensuring  correct     
orientation. 
 
Refer to low voltage external 
wiring diagram for control panel 
and modulation thermostat 

 

terminations. 
 
Replace the cap and plug into 
socket.

 

CONTRACTORS 
CONNECTION PLUG 

FIXED CONNECTION 

SOCKET 

24V AC LINE 

VOLTAGE 

FROM PANEL 

L3 

L1 

G

4 - 20mA  
FROM  
THERMOSTAT 

PRESSURE 

SWITCH 

SCHEMATIC DIAGRAM 

8  Modulation Damper and Pressure Switches 

PRESSURE SWITCH CONNECTIONS 

Summary of Contents for SmartCom3

Page 1: ......

Page 2: ...losed circuit to enable Connect to B0 B1 for remote ON ie BMS time control REMOTE SENSOR s may be placed at a max distance of 325ft from the control unit using shielded 18 Awg cable Wiring should be k...

Page 3: ...and ONE slave configuration Wire further slaves in parallel REMOTE SWITCH INPUTS should be connected by 18 Awg cable Max length is 325ft Low voltage switching inputs to be normally open closed circuit...

Page 4: ...able Connect to B0 B1 for remote ON ie BMS time control REMOTE SENSOR s may be placed at a max distance of 325ft from the control unit using shielded 18 Awg cable Wiring should be kept separate from m...

Page 5: ...5ft from the control unit using shielded 18 Awg cable Wiring should be kept separate from mains wiring to minimize noise pick up Set within Engineers functions for any remote sensors SmartCom Mulitizo...

Page 6: ...ster and ONE slave configuration Wire further slaves in parallel REMOTE SWITCH INPUTS should be connected by 18 Awg cable Max length is 325ft Low voltage switching inputs to be normally open closed ci...

Page 7: ...a master and ONE slave configuration Wire further slaves in parallel REMOTE SWITCH INPUTS should be connected by 18 Awg cable Max length is 325ft Low voltage switching inputs to be normally open close...

Page 8: ...to enable Connect to B0 B1 for remote ON ie BMS time control REMOTE SENSOR s may be placed at a max distance of 325ft from the control unit using shielded 18 Awg cable Wiring should be kept separate...

Page 9: ...plug and remove the cap via two screws Connect the incoming 24V cable from the Control panel onto terminals L3 and GND ensuring correct orientation Connect the incoming 4 20mA cable from the modulati...

Page 10: ...nt Module In line Burner Branch Zone 2 18 Awg Shielded Cable Sensor Zone 2 In line Burner In line Burner In line Burner 2nd Branch Zone 1 End Vent Module End Vent Burner 1 phase 115V Pump 115V 60Hz Ma...

Page 11: ...driver reposition the mechanical end stop A to final bracket position 5 Reconnect power to damper Recheck correct direction of rotation i e when 4mA from controller damper fully open If this is not co...

Page 12: ...to default settings as described in the SmartCom Installation and User Manual ref US SCOM 29 The controllers will therefore operate immediately with standard Infrared Radiant heaters To alter the cont...

Page 13: ...the entire system on whereas making this connection on a slave unit will only bring on that zone 1 BMS Controlling Time only Ensure all the programmed ON times in the SmartCom are turned off i e They...

Page 14: ...0337 Facsimile 317 842 3989 Website www ambirad com us For the Distributor Nearest please call 1 888 330 4878 AmbiRad is a registered trademark of AmbiRad Limited Because of continuous product innova...

Reviews: