Ambirad HCH 100 Installation Servicing & Operating Instructions Download Page 21

 

21/30 

Figure 13b : Overview of the HCH options 

 

 

 
Note : When the option 541.4 (ducted inlet end) is required, the standard perforated end panel is not required 

 

 
4.7 Controls 
 

 

Vertical heaters are supplied with a pre-

wired control unit, comprising : 
1. time 

control 

2.  day/night temperature control 
3. heat-vent 

facility 

 
Horizontal heaters are supplied with a 
remote panel. 

 

Refer also to § 3.2 ‘Electrical connections’. 

 

 

 
 

5.0 Commissioning

 

 
5.1

 

Only suitably trained personnel or specialist 
commissioning engineers should be used to 
carry out the commissioning of the installed 
equipment.  Ensure that all relevant manuals 
and user instructions are available before 
the commissioning

 

engineer proceeds. 

 

Although the heater is test fired at the 
factory, each installation has a different 
set of site conditions.  Therefore 
commissioning is very important. 
Note:  The heater should not just be 
switched on and left to function.

 

 

The correct type of combustion analysis 
equipment, correctly calibrated, should be 
used at all times. 
 
 

 

 

 
 
Pre-Commissioning Checks

 

Always ensure electrical safety and 
soundness of the oil installation before 
commencing, and then proceed with the 
following checks:- 

 

(a)  Ensure electrical supply has been 

switched off. 

(b)  Ensure the oil supply is switched off. 
(c)  Check that the heater has been 

installed on a suitable level base and is 
supported correctly with adequate 
clearance around the inlet grilles. 

(d)  Fully open louvres on nozzled outlets 

or ductwork grilles. 

(e)  Ensure the flue system is adequately 

supported with correct termination and 
sealing of the joints. 

(f)  Check that all heater panels are 

securely fastened and correctly fitted. 

 

(g)  Locate gas sampling point and ensure 

this can be resealed on completion of 
commissioning. 

(h)  Check fan and limit stat 
 Fan 

off   

30°C 

 Fan 

on   

60°C 

 

Overheat Limit   

see table 14 

 

Ensure white button is pulled out and 
red button has been reset. 

(i) Where applicable check pulley 

alignment and belt tension. 

(j) 

Test for earth continuity between the 
heater, control panels, burner and oil 
pipe work. 

1 Standard 

 

2 Ducted inlet end 

3 Ducted inlet bottom 

4 Ducted inlet top 

5 Ducted linlet rear   

6 Ducted outlet 

Summary of Contents for HCH 100

Page 1: ...it with the user or attached to the appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or de...

Page 2: ...3 3 Electrical Connection 3 4 Ventilation Requirement 4 0 Installation 4 1 Location 4 2 Heater Clearances 4 3 Flue 4 4 Nozzled Heaters 4 5 Ducted Heaters 4 6 Filters 4 7 Controls 5 0 Commissioning 5...

Page 3: ...f conformity are available from the Quality Control department at Ambi Rad Limited 1 3 CE Approval European Directives 1 3 1 Ambi Rad cabinet heaters have been fully assessed and tested and meet the f...

Page 4: ...188 174 160 203 174 181 174 145 Smoke n 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 size 0 65 1 00 1 35 2 00 2 75 2 75 4 00 3 00 1 50 3 50 2 00 4 50 2 00 nozzle angle 60 60 60 60 45 45 60 2x 45 2x 45 2x 45...

Page 5: ...4 61 50 89 49 88 50 90 50 89 47 84 49 87 49 88 Sound level 2 for guidance only dB A 52 52 53 53 59 61 61 65 63 67 Flue spigot outside diameter mm 125 125 150 178 178 178 178 223 223 223 Minimum flue h...

Page 6: ...6 30 2 2 Dimensions Vertical heater range Figure 1a unit with discharge nozzle Front view Figure 1b unit with discharge plenum Front view...

Page 7: ...7 30 Figure 1c Side view Figure 1d Figure 1e Figure 1f burner mounting flange air inlet air inlet...

Page 8: ...8 30 Horizontal heater range Figure 2a Side view Figure 2b Front view...

Page 9: ...804 2012 2012 2073 2073 2012 2012 inside dia 1 burner inlet 110 110 120 120 140 140 155 155 155 155 H1 2088 2088 2168 2168 2376 2378 2477 2477 2466 2466 H2 2164 2164 2114 2114 2400 2400 2395 2395 2334...

Page 10: ...by the parameters of the installation i e number of heaters and length of pipeline 3 2 3 Please refer to the burner manual as to the limitations of the oil line and most suitable pipe diameters after...

Page 11: ...ated heat input for high level outlet grills 3 4 4 Air Supply Requirement for Combustion and Ventilation table 4 Frame VCH Model Heat Input kW Low Level Grill cm High Level Grill cm 2 100 38 0 171 86...

Page 12: ...s installed 4 0 Installation 4 1 Location 4 1 1 Ensure the structural elements of the building are adequate to carry the weight of the appliance and its ancillary components i e the flue system and th...

Page 13: ...0 1000 Measured from front panel 4 3 Flue 4 3 1 Ambi Rad cabinet heaters must be connected to a flue system venting the products of combustion directly to outdoors Flue systems must be installed in ac...

Page 14: ...ned in order to obtain the desired air distribution The louvres can be adjusted It is forbidden to close all louvres at a time as overheating could occur For safety reasons it is recommended to wear g...

Page 15: ...ned 1 fully open 3 fully closed louvres all directions 2 fully open 2 fully closed louvres all directions for protection of fan motor and proper heater operation do not close all louvres at a time a m...

Page 16: ...load when applying discharge ducting Duct outlets must be adjusted when necessary to meet the values mentioned in table 9 Table 9 Frame Model Nominal airflow Available outlet static pressure Motor loa...

Page 17: ...adjusted when necessary to meet the values mentioned in table 9 4 5 5 Ducted air inlet on VCH HCH units The unit is designed so that it can be installed with inlet air ducts Vertical units Option 541...

Page 18: ...556 III 400 500 541 4 end 691 1054 651 1014 541 5 top 541 7 bottom 1201 707 1161 667 541 6 rear 1082 707 1042 667 IV 600 700 541 4 end 1082 1201 1042 1161 541 5 top 541 7 bottom 1400 596 1360 556 541...

Page 19: ...ails Filters must be inspected on a regular basis as dirty filters can affect the safe working of the unit For safety reasons it is recommended to wear gloves glasses when inspecting the filters Dirty...

Page 20: ...end 1 standard 2 duct left 3 duct right 4 duct rear Figure 13a Overview of the VCH options Note When filters option 502 1 are required then the standard air intake panels must be replaced by the panel...

Page 21: ...alibrated should be used at all times Pre Commissioning Checks Always ensure electrical safety and soundness of the oil installation before commencing and then proceed with the following checks a Ensu...

Page 22: ...ust the primary air damper more open for less CO2 and more closed for more CO2 until the correct level has been obtained The CO2 level on site must be in the range of the figures given in table 2 1 h...

Page 23: ...ich could lead to overheating of the heater The limiter will trip out Consequently the duct grilles will have to be opened Typical arrangement of oil storage tank single pipe system see figure 14 5 4...

Page 24: ...Burner maintenance d Main fan and motor e Pulley and belts f Flue system g Control panel and electrical connections 6 2 Procedures Heat Exchanger a Access to the heat exchanger is made via the top rea...

Page 25: ...ition of the belts for splits or fraying if one belt in any set appears to have worn excessively then change the whole set immediately DO NOT MIX BELTS OF DIFFERENT AGES OR BATCHES As the belts stretc...

Page 26: ...Check burner motor Burner starts but goes to lockout Check oil supply Dirty cell Main oil cock open Air in oil line Photocell failure Air settings incorrect Oil valve faulty Change oil valve Purge oil...

Page 27: ...not hold on main flame Insufficient air High inlet Pressure Fan limit stat Air inlets blocked Outlet nozzles closed Duct resistance too high Fan belts slipping Remove obstruction Clean filters Open lo...

Page 28: ...ustion chamber CC air deflector 10 fixation plate HE 11 sliding bracket HE 12 over pressure relief panel 13 heat exchanger combustion chamber 14 side air deflectors 15 side inner skins 16 top side pan...

Page 29: ...es 200 300 Contactor 60 61679 D910M5 sizes 400 500 600 700 800 Contactor 60 61679 D1210M size 1000 60 61703 02 04 size 400 60 61703 04 06 size 500 60 61703 05 09 size 600 60 61703 07010 sizes 700 800...

Page 30: ...al BSEN 55014 Electromagnetic Compatibility BSEN 50165 Safety of Electrical Equipment BS 5440 Part 1 Specification Installation of Flues BS 5854 Code of Practice Flues Flue Structures BS 715 Metal Flu...

Reviews: