Compact Voice Alarm System 

User Manual

20

7.  Mounting instructions

STEP 1

Remove 4 × M4 TORX screws from part A and take off the front panel.

STEP 2

Remove 5 × M3 screws from part B.

Summary of Contents for miniVES 2001L

Page 1: ...EN 54 16 2008 EN 54 4 1997 AC 1999 A1 2002 A2 2006 User Manual EN Compact Voice Alarm System www ambientsystem eu ver 04 2020 ...

Page 2: ...1 4 miniVES Charger_______________________________________________________________________ 12 4 1 miniVES Charger_________________________________________________________________ 12 4 2 Batteries________________________________________________________________________ 13 5 Instructions for performing basic functions____________________________________________ 14 5 1 Alarm mode______________________...

Page 3: ...erating instructions should be adhered to 4 Follow all instructions All instructions for installation or use operating should be followed 5 Do no use this apparatus near water Do not use this apparatus near water or a moist envi ronment for example near a bath tub wash bowl kitchen sink or laundry tub in a wet basement near a swimming pool in an unprotected outdoor installation or any area which i...

Page 4: ...appliance and cart combination to overturn 14 Unplug this apparatus during lighting storms or when unused for long periods of time Not applicable when special functions are to be maintained such as evacuation systems 15 Refer all servicing to qualified service personnel Servicing is required when the apparatus has been damaged in any way such as power supply cord or plug is damaged liquid has been...

Page 5: ...tem should not be located in the vicinity of overhead power lines or other electric light or power circuits or where it can fall into such power lines or circuits When installing an outdoor system extreme care should be taken to keep from touching such power lines or circuits as contact with them might be fatal Danger Object and Liquid entry never push objects of any kind into this appa ratus thro...

Page 6: ...e disconnect device is the mains plug of the power cord set If an AC DC adapter is provided and the mains plug that is part of the direct plug in device the AC DC adapter is the disconnect device The socket outlet shall be near the apparatus and shall be easily accessible Old electrical and electronic appliances Electrical or electronic devices that are no longer serviceable must be collected sep ...

Page 7: ...utton 5 Configurable function buttons 6 Function button activation LEDs 7 Handheld microphone LED 8 CPU off section a CPU off function LED yellow b CPU off function switch 9 Display shows control unit s menu 10 Functional keys support auxillary functions when navigating the menu a HOME press to return to the fers menu b ENTER press to enter value select control unit in menu c Up arrow press to nav...

Page 8: ...nual 8 2 2 LED colors on the control unit front panel Graphic symbol Color miniVES Control Units green POWER yellow FAILURE red ALARM yellow Battery power active green Handheld microphone active yellow CPU off function active CPU bypass ...

Page 9: ... C L R C L R 24VDC 150mA 48VDC 350mA TEMP SENSOR LINEA LINEB HV AUDIOIN C H C H C H LINEA LINEB HV AUDIOIN C H C H C H LINEA LINEB HV AUDIOIN C H C H C H LINEA LINEB HV AUDIOIN C H C H C H 2 4 1 3 OUT3 OUT2 OUT1 OUT3 OUT2 OUT1 OUT3 OUT2 OUT1 2 Control Card slots Charger slots 5 8 1 6 7 4 3 9 10 2001 units 4001 units 4002 units Line control card arrangement for miniVES systems 1 ABT xCtrLine 4 cont...

Page 10: ...UT3 OUT2 OUT1 1 4 5 3 7 6 9 8 10 2 Diagram of the connector panel for miniVES series 2001L 4001L and 4002L units 1 Local audio bus outputs for 4 line control card operation 2 Audio input and output 3 Logic inputs 4 Auxillary power outputs 5 Battery temperature sensor input jack 6 Main Battery connector 7 Logic outputs 8 10 100 Mbps Lan Wan port PC connection 9 10 100 1000 Mbps Lan port 10 10 100 1...

Page 11: ...AN RS485 LAN LAN PoE IN1 IN2 B A FIBER OUT3 OUT2 OUT1 1 4 5 11 8 13 14 3 7 6 9 10 12 2 Diagram of the connector panel for miniVES series 2001LN 4001LN and 4002LN units 1 Local audio bus outputs for 4 line control card operation 2 Audio input and output 3 Logic inputs 4 Auxillary power outputs 5 Battery temperature sensor input jack 6 Main Battery connector 7 Logic outputs 8 10 100 Mbps Lan Wan por...

Page 12: ...ng date may be connected Fig 5 BUS1 BUS2 IN7 IN6 IN5 IN4 IN3 IN2 IN1 48VDC BATT Audio IN AudioOUT C L R C L R 24VDC 150mA 48VDC 350 mA TEMP SENSOR LINEA LINEB LINEC LINED HVAUDIO IN C H C H C H C H C H LINEA LINEB LINEC LINED HVAUDIO IN C H C H C H C H C H LAN WAN RS485 LAN LAN PoE IN1 IN2 B A FIBER 2 1 OUT3 OUT2 OUT1 Connection between VRLA batteries temp sensor and miniVES Charger module c NOTE ...

Page 13: ... seconds after the power cord was unplugged from AC socket located on the miniVES main unit Never connect negative cable in the first place as in the case of short circuit between battery positive wire and a device frame or rack cabinet element a device damage may occur Connect battery negative cable to negative terminal c NOTE Battery bank has to be connected before connecting main power supply c...

Page 14: ...ring alarm state press Cancel Alarm button VASCU enters standby mode all alarm messages are muted and background music is restored Sending evacuation messages Activate alarm and select zones A green LED next to the zone name means the zone is ready to transmit Press Evacuation button A constant red indicator next to green zone selection indicator means that evacuation message is being sent The eva...

Page 15: ...ition The CPU OFF LED will light up with a steady green light Press push to talk button and speak to the microphone c NOTE When the switch is in the CPU OFF position playback of the alarm messages recorded in the miniVES memory does not work The processor is bypassed A direct connection between devices is created microphone amplifiers loudspeakers Microphone input is broadcasted to the entire syst...

Page 16: ...included 512 MB SLC SDHC card provides more than 20 min of message time LCD display 4 5 LCD touch screen DSP Implemented 3 band parametric EQ Number of audio inputs 1 Type of audio inputs Differential Connector type 3 pin phoenix connector Frequency response 40 Hz 20 kHz 1 dB 400 Hz 8 kHz 0 1 dB Input impedance 10 kΩ Maximum input voltage 3 Vrms Number of outputs 1 Type of outputs Balanced Connect...

Page 17: ...ernal network Communication with PC PC software RJ45 twisted pair connection TIA EIA568 B via Ethernet protocol Operating temperature 0 C 60 C Operating humidity 15 to 80 non condensing Storage temperature 20 C 70 C Storage humidity 15 to 80 non condensing Case material and finish Steel with powdercoat finish Dimensions 440mm W 525mm H 350mm D Mount options 4 10 mm wall mount holes in the back of ...

Page 18: ...C SDHC card provides more than 20 min of message time LCD display 4 5 LCD touch screen DSP Implemented 3 band parametric EQ Number of audio inputs 1 Type of audio inputs Differential Connector type 3 pin phoenix connector Frequency response 40 Hz 20 kHz 1 dB 400 Hz 8 kHz 0 1 dB Input impedance 10 kΩ Maximum input voltage 3 Vrms Number of outputs 1 Type of outputs Balanced Connector type 3 pin phoe...

Page 19: ... module connector type fiber type SFP modules SC LC connector Multimode or single mode E30 or E90 OM or OM2 Communication with PC PC software RJ45 twisted pair connection TIA EIA568 B via Ethernet protocol Operating temperature 0 C 60 C Operating humidity 15 to 80 non condensing Storage temperature 20 C 70 C Storage humidity 15 to 80 non condensing Case material and finish Steel with powder coat f...

Page 20: ...Compact Voice Alarm System User Manual 20 7 Mounting instructions STEP 1 Remove 4 M4 TORX screws from part A and take off the front panel STEP 2 Remove 5 M3 screws from part B ...

Page 21: ...s C and pull the drawer towards you D STEP 4 Drawer release lever 1 To release push down on lever on left hand side and pull up on lever on the right hand side 2 With levers depressed pull drawer towards you to remove it completely ...

Page 22: ...the wall with four screws Use screws and anchors suiting your type of wall not provided c Due to the mass of the product up to 80 kg with the batteries it is important that the wall mounted system is safely installed in accordance with local building regulations 260 mm 340 mm ...

Page 23: ...atteries to the dedicated compartment Check that the battery compartment holds the type of battery selected by the installer A 220 mm B 340 mm C 430 mm STEP 7 Slide the drawer back in position and tighten the screws A B C ...

Page 24: ...iVES 4001 miniVES 4002 miniVES 2001L miniVES 4001L miniVES 4002L miniVES 2001N miniVES 400LN miniVES 4002N miniVES 2001LN miniVES 4001LN miniVES 4002LN Declared intended use of product Fire safety Optional functions Delays to entering the voice alarm condition Phased evacuation Manual silencing of the voice alarm condition Manual reset of the voice alarm condition Voice alarm condition output Indi...

Reviews: