Figure 15

Main Duct with Duct Extension

6. In the room where the main duct kit is attached to the

chassis, cut a hole in the wall at the same height from the
floor that the main duct is located. Cut the hole 1/8”
larger than the width and height (10” x 5”) dimensions of
the extension duct (Figure 16).

BRACKET

TRANSITION
     DUCT

MAIN DUCT

MINIMUM

5"

BOTH SIDES

42-27/32"

6" TO 42-1/2"

BRACKET

5"

PARTITION
WALL

DUCT EXTENSION

AIR FLOW

DUCT

TERMINATION

KIT

AIR FLOW

1" to
adjoining
wall
surface

Figure 16

Main Duct and Duct Extension Dimensions

7. Measure from the end of the main duct where the

extension duct will be connected to the hole in the wall.
If necessary cut the extension duct to a length where the
cut end protrudes into the wall’s inner space and one
inch from the adjoining room’s wall surface.

8. Insert the extension duct into the opening in the wall.

Install the extension duct by placing the slotted flange
over the two screws in the main duct. Using two #8 round
Phillips head screws, mount bottom of extension duct to
mounting bracket through the bracket slot (Figure 14).

NOTE:  The  EDK02 can be cut into two sections and used
with two MDK02s if the needed length does not exceed
21-1/4”.

Terminal Duct Kit (TDK02) Installation

The sheet metal collar of the terminal duct kit must be
mounted in the wall of the adjoining room opposite the room
where the main duct kit is attached to the PTAC chassis.

1. Cut a hole in the wall of the adjoining room such that the

hole is centered on the extension duct that is currently
in the wall of the opposite room. See Figure 17 for proper
wall hole dimensions for sheet metal collar.

11-1/4"

6-

1/

4

"

Figure 17

Wall Hole Dimension

2. Insert the sheet metal collar into the wall so that the

flanges will mount flush to the wall after the collar is
pushed all the way into the wall. While pushing the collar
into the wall make sure the extension duct is inside the
collar. Use four #8 screws to attach metal collar to wall
(Figure 18).

Gasket

11"

6"

Figure 18

Sheet Metal Collar

3. Center the metal grille over the sheet metal collar and

use two #8 screws (provided) to attach the grille to the
metal collar (Figure 19).

Use

Two  #8

Screws

Figure 19

Metal Grille

NOTE:  If the grille is field-supplied, it must have fixed louvers
that cannot be closed.

Summary of Contents for TDK02

Page 1: ...ATTENTION INSTALLING PERSONNEL Asaprofessionalinstalleryouhaveanobligationto know the product better than the customer This includes all safety precautions and related items Prior to actual installation thoroughly familiarize yourself with this Instruction Manual Pay special attention to all safety warnings Often during installation or repair it is possible to place yourself in a position which is...

Page 2: ...Disconnect power source before removing the chassis 5 Unplug and remove chassis from wall sleeve Drill two 1 8 holes on left and right sides of wall sleeve in proper locations See Figure 8 for hole dimensions and Figure 9 for template Wall Sleeve Indoor 11 16 2 3 8 5 8 1 8 Holes Wall Sleeve Indoor 11 16 2 3 8 5 8 1 8 Holes Figure 8 Wall Sleeve Hole Dimensions and Placement Note If there is not eno...

Page 3: ...front bracket holes Figure 12 Air Flow Baffle Dimensions Main Duct Ext Duct Small 3 11 16 x 31 3 4 80 20 Large 4 5 16 x 31 3 4 65 35 Table 1 Grille Support Brackets Figure 12 Front Bracket 3 Install discharge air grille Figure 13 on top of the air baffle Securethegrilletotheductwithpalnuts provided by reaching through the opening in the bottom of the duct Figure 13 Air Grille 4 Place main duct ass...

Page 4: ...et through the bracket slot Figure 14 NOTE The EDK02 can be cut into two sections and used with two MDK02s if the needed length does not exceed 21 1 4 Terminal Duct Kit TDK02 Installation The sheet metal collar of the terminal duct kit must be mounted in the wall of the adjoining room opposite the room where the main duct kit is attached to the PTAC chassis 1 Cut a hole in the wall of the adjoinin...