background image

4

A.  HIGH SIDE VALVE
B.  LOW SIDE VALVE
C.  VACUUM PUMP
D.  THERMOCOUPLE GAUGE
E.  MANIFOLD GAUGE
F.  CHARGING CYLINDER

C

A

B

E

D

HIGH VACUUM PUMP

LARGE DIAMETER

BRAIDED VACUUM

HOSES

TO

RELATED

GAUGE

PORTS OF 

COND. UNIT

HIGH VACUUM

MANIFOLD

LOW SIDE

GAUGE

HIGH SIDE

GAUGE

DIAL-A-CHARGE

CHARGING CYLINDER

THERMOCOUPLE
VACUUM
GAUGE

F

Figure 2

5. Open the high and low side valves on the gauge

manifold. Keep the valve on the charging cylinder itself
closed, but open the valve on the gauge manifold that
leads to the cylinder.

6. Evacuate the system to about 29 inches of vacuum as

measured by the compound (low side) gauge.

7. Open the valve to the thermocouple vacuum gauge.

Evacuate until the gauge reads 250 microns or less.

8. Close the valve to the vacuum pump. Wait five min-

utes, then check the pressure on the thermocouple
vacuum gauge:

a. If the pressure is not more than 1500 microns, the

system is leak-free and properly evacuated. Pro-
ceed to Step 9.

b. If the pressure rises, but holds at about 5000

microns, moisture and noncondensibles are still
present. Open the valve to the vacuum pump, and
go back to Step 7.

c. If the pressure rises above 5000 microns, a leak is

present. Go back to “Leak Testing” section on page
4.

9. Close the valve to the thermocouple vacuum gauge.

Close the valve to the vacuum pump. Shut off the
pump.

way.) Attach this gauge manifold to the service valves
on the unit. Do not open the unit service valves. Do not
use refrigerant from the unit for leak testing - it has
been precisely measured at the factory for optimum
performance.

WARNING

To avoid possible explosion, the line from
the nitrogen cylinder must include a
pressure regulator and a pressure relief
valve. The pressure relief valve must be set
to open at 175 psig or less.

2. Connect a cylinder of dry nitrogen to the center port on

the gauge manifold.

3. Open the hand valve a minimal amount on the line

coming from the nitrogen cylinder.

4. Open the high pressure valve on the gauge manifold.

Pressurize the refrigerant lines and the indoor coil to
150 psig (1034 kPA). To reach 150 psig, you may need
to further open the hand valve on the nitrogen cylinder.

WARNING

To avoid possible explosion or equipment
damage, do not exceed 150 psig when
pressure testing.

After you reach 150 psig, close the valve on the nitrogen
cylinder. Disconnect it from the gauge manifold.  If you plan
to use an electronic leak detector, add a trace of R-22 to
the system (if permitted by current EPA regulations).

5. Put a soap solution on all connections and joints. If you

see bubbles, you have a leak. Mark these locations.

6. Use the gauge manifold to carefully release the nitro-

gen from the system. If leaks were found, repair them.
After repair, repeat the above pressure test. If no leaks
exist, proceed to system evacuation.

ID COIL AND LINE SETS EVACUATION

1. To speed nitrogen release, use a core puller to remove

the valve cores from the  service valves.

2. Connect the vacuum pump, high vacuum manifold set

with high vacuum hoses, thermocouple vacuum gauge
and charging cylinder as shown. Begin with all valves
fully closed.

3. Your first step will be only to confirm proper pump and

gauge operation. Open only the shutoff valve which
leads to the vacuum pump (Figure 2)(C). Start the
pump. After the gauge manifold (low side) reading
drops to about 29 inches of vacuum, open only the
valve to the thermocouple vacuum gauge(D). Evacu-
ate until the gauge reads 250 microns or less.

4. Close the valve to the thermocouple vacuum gauge(D).

This will avoid potential gauge damage from “pegging
the meter”. Now that proper pump and gauge opera-
tion has been confirmed, you are ready to begin the
actual evacuation of the lines and indoor coil.

Summary of Contents for RHE**A2 Series

Page 1: ...nking before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual should not supersede existing practices but should be considered as supplemental information Table of Contents ATTENTION INSTALLING PERSONNEL 1 Safety Guidelines 2 General 2 SHIPPING AND HANDLING 2 LOCATION AND CLEARANCES 2 ROOFTOP INSTALLATION 2 APPLICATION...

Page 2: ...servicing the unit s must be provided If installing two or more units at the same location allow at least 24 inches between the units when using the 6 12 12 guidelines in Figure 1 The space between two units may be reduced to 12 if the clearances in Figure 1 are increased to 12 24 24 12 12 6 MINIMUM CLEARANCES SIDE VIEW 5 Figure 1 DO NOT locate the unit Directly under a vent termination for a gas ...

Page 3: ...ak 3 After brazing quench the joints with water or a wet cloth This will also help prevent overheating of the service valve SWEAT CONNECTIONS AT THE INDOOR COIL Check the indoor coil liquid and vapor line diameter A bushing or coupling may be needed to match with the line sizes used If mix matching to a restrictor orifice indoor coil check the Specification Sheet for the proper orifice size to be ...

Page 4: ...psig or less 2 Connect a cylinder of dry nitrogen to the center port on the gauge manifold 3 Open the hand valve a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the gauge manifold Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach 150 psig you may need to further open the hand valve on the nitrogen cylinder WARNING To...

Page 5: ... the wiring diagram or Specifications sheet to determine if this unit has a crankcase heater If it does you must connect electrical power to the unit for four hours before operating the compressor Failure to do so could result in compressor damage IMPORTANT During all installation and service work follow all regulations of the Environmental Protection Agency This system uses R 22 R 22 is an HCFC H...

Page 6: ...F Indoor 7 0 F I n d o o r 75 F Indoor 80 F Indoor 85 F Indoor THE RETAINER TO AVOID LOSS OF REFRIGERANT DO NOT APPLY PRESSURE TO THE RETAINER The outdoor unit is factory charged with enough R 22 for the matching indoor blower coil or matching A coil plus 25 feet of 3 8 inch liquid line Add or subtract 0 60 oz of R 22 per foot of 3 8 liquid line for any difference from 25 feet IMPORTANT Use only r...

Page 7: ...ld be 350 to 450 CFM per ton of cooling based on the size of the outdoor unit The most common way of establishing indoor airflow is heating temperature rise Indoor airflow will then be Heating output of equip ment 1 1 x temp rise In other cases measurement of external static pressure is helpful For details see the Installation Manual for your indoor equipment If further information is needed see t...

Page 8: ...riods is automati cally adjusted with every defrost cycle minimum of 30 minutes and maximum of 360 minutes WARNING To avoid electrical shock or death disconnect the electrical power When servicing it may be necessary to rapidly advance the system through a defrost cycle To do this 1 If the outdoor coil temperature is above 30 F place a jumper wire from R on the low voltage terminal strip to one of...

Page 9: ...d normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do controls function properly Are manual reset switches in the reset position high pressure cutouts relays etc 18 Check the voltage with unit running Does it check within the tolerance of 207 to 253V for 230V or 198 to 228V If using...

Page 10: ... 6 to 28 8 KW Notes 1 BHA TB blowers may require additional wire s here See BHA TB wiring diagram for details 2 Emergency Heat will stop the compressor but it will not bypass the outdoor thermostat Only the amount of heat controlled by W2 will be energized above the ATK setpoint 3 See notes on page 12 regarding connector GY42 wire and staging of electric heat Approved Thermostats are THSMEC1H2BA T...

Page 11: ...WITH INDOOR BLOWER COIL Approved Thermostats are THSMEC1H2BA THSMDC1H2BA THSADC1H2BA THSMDC1H3BA THSADC1H3BA THPMFC1H2BA C ATK Controlling ALL Electric Heat Morning Warmup Could be Slow 4 8 to 28 8KW ROOM THERMOSTAT 6 wires BHA BLOWER COIL 5 wires RH OUTDOOR UNIT Notes 1 BHA TB blowers may require additional wire s here See BHA TB wiring diagram for details Thermostats shown with required connecti...

Page 12: ... Load at an outdoor temperature of 20 F It is usually desirable to provide a small amount of extra capacity Therefore for this instal lation the outdoor thermostat ATK05 should be set at 25 F This example is for purposes of illustration only Actual selection and application of equipment remains the sole responsibility of the installer If an outdoor thermostat not controlling the first group of ele...

Reviews: