8) INSTALLER SETTINGS
NOTE: Waiting 1-Minute with no button presses will exit
the installer settings menu with all items saved as they
were last shown on the display screen.
TO ENTER INSTALLER SETTINGS MENU:
With thermostat powered,
press System Mode button
until
OFF
is underlined.
After OFF mode is confirmed,
press and hold BOTH the Up
and Down buttons for at least
5 seconds until the screen
changes.
TO CHANGE AN ENTRY:
Use the Up or Down buttons
to change the setting option.
TO ADVANCE TO THE NEXT MENU ITEM:
Press the Mode button one
time to advance to the next
item in the menu.
TO RETURN TO THE MAIN THERMOSTAT SCREEN:
While at the last menu item,
press the System Mode
button one more time to exit
the Installer Settings menu.
SOFTWARE CONFIGURATION SETTINGS
MENU# SETTING
OPTIONS
01
Scale
F
, C
02
Temp. Calibration
Zero
, -5F to +5F
(-3C to +3C)
03
Available Modes
01: Heat, Cool, Auto
02: Heat, Cool
03: Heat Only
04: Cool Only
04
Max. Heat
60F to 90F
(80F)
(16C to 32C)
05
Min. Cool
60F to 80F
(65F)
(16C to 27C)
06
System Type
HP=Heat Pump
Con=Conventional
07
HP Valve Type
B: Valve on in Heat
O: Valve on in Cool
08
Auto Dead-Band
2.0F (1.11C)
3.0F (1.67C)
4.0F (2.22C)
5.0F (2.78C)
09
Swing /
Temp. Differential
±0.25F (±0.14C)
±0.50F (±0.28C)
±1.00F (±0.56C)
±2.25F (±1.25C)
10
Aux. Stage Offset
(for Heat Pumps only)
Off
1: 1.0F (0.5C)
2: 2.0F (1.0C)
3: 3.0F (1.5C)
4: 4.0F (2.0C)
5: 5.0F (2.5C)
--
12
High Fan
On: Available
Off: Disabled
13
Programming
Off: Manual
On: Programmable
14
Clock Format
(see note #1)
12: AM/PM
24: 24 Hr. Military
15
Periods per/Day
(see note #1)
4: 4-Periods
2: 2-Periods
1: 1-Period
16
Auto Daylight
Savings (see note #1)
On: Auto DST
Off: Manual
17
Backlight Always On
Off=Turn off 10 sec
On=Always On
18
Use default set temp.
after mode change
(see note #2)
ON: Uses default
temps
OFF: Use last temp per
mode
19
Default heat mode set
temp (see note #2)
70F (21C)
60F to max heat set temp
20
Default cool mode set
temp (see note #2)
74F (23C)
80F to min cool set temp
--
98
Compressor
Protection Bypass
No=Delays Remain
Yes=Suspend Delay
99
RESET
No=Save and Exit
Yes=Full Reset
NOTES: (#1) For Programmable operation only.
(#2) For Non-Programmable operation only.