Amana PACKAGE HEAT PUMP Owner'S Manual Download Page 5

5

ON

ON

CG

Y

R

W

W

1
W2

O

Low Voltage

Terminal Strip

Low Voltage Connection

Heater Kit Control Box

Low Voltage

Terminal Strip

Low Voltage Connection

Unit Control Box

C

G

Y

R

W

W1

W2

O

1

2

3

4

5

6

7

8

9

1

3

L2

L1

4

5

THERMOSTAT

CB1

GY

BU

RD

0R

GY

BU

RD

BR

BR

BR

YL

YL

BK

VT

RD

VT

BR

BK

BK

RD

RD

BU

BK

BK

BK

BK

BK

BK

OL

OL

10KW

FIELD
CONNECTION
208/240 VAC
1

ø

USE COPPER
CONDUCTORS
ONLY-75°C MIN

RD

L2

L1

CB2

GND-75

SEQUENCER #1

RD

BK

GN

208/230 VAC 1

ø

T2

T1

TO CONTACTOR

Field Connection

Refer to the unit wiring diagram (see back of manual) for electrical
connections. When installed, the unit must be electrically grounded
in accordance with local codes or in the absence of local codes, with
the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA
C22.1 Electrical Code, if an external source is utilized.

WARNING

T

O AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE

POLARIZED AND GROUNDED.

CAUTION

T

O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE

ONLY COPPER CONDUCTORS.

CAUTION

T

O PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING

ERRORS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

CONTROLS.  

V

ERIFY PROPER OPERATION AFTER SERVICING.

The best protection for the wiring is the lowest rated fuse or circuit
breaker which will supply power to the unit during normal operation
without nuisance trips. Such a device will provide maximum circuit
protection. DO NOT EXCEED THE MAXIMUM OVERCURRENT
DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherproof
fittings.  All exterior power supply and ground wiring must be in ap-
proved weatherproof conduit. Low voltage wiring from the unit con-
trol panel to the thermostat requires coded cable.

F

LEXIBLE

 W

IRING

 S

ETUP

Line and low voltage wiring must enter the unit as shown.

ELECT.

CONTROL

BOX

EVAP

COIL

COMPRESSOR

  LOW

VOLTAGE

REAR VIEW

SIDE VIEW

    

ELECTRICAL

SIDE VIEW

BLOWER

ELECTRICAL

SUPPLY

 AIR

RETURN

AIR

HEATER

KIT

For knockout locations, see dimension drawing in the Product Data
Book applicable to your model* .  Use the Single Point wiring kit to
add further flexibility to the installation wiring.

U

NIT

 V

OLTAGE

The unit transformer is factory connected for 230V operation. If the
unit is to operate on 208V, reconnect the transformer primary lead
as shown on the unit wiring diagram.

AIR CIRCULATION AND FILTERS

D

OWNSHOT

 A

IRFLOW

 C

ONVERSION

Units are shipped from the factory ready for horizontal airflow.  These
units can be easily converted from horizontal to downshot airflow
delivery.  If conversion to vertical airflow is necessary, proceed as
follows:

Blower Rotation

1. Cut insulation around bottom openings and remove panels

from the bottom of the unit, saving the screws holding the
panels in place.

2. From the rear of the unit, remove the four (4) screws securing

the blower assembly in place and loosen the two (2) screws
directly below the duct opening.

*NOTE:  Please contact your distributor or our website for the applicable product data book referred to in this manual.

Summary of Contents for PACKAGE HEAT PUMP

Page 1: ...rt No 10730420 Printed in USA 2000 2004 Goodman Company L P Effective July 2004 is a trademark of Maytag Corporation and is used under license to Goodman Company L P All rights reserved INSTALLATION INSTRUCTIONS PACKAGE HEAT PUMP NOTE Please contact your distributor or our website for the applicable product data book referred to in this ...

Page 2: ...AL THE SERVICE MANUAL A QUALIFIED INSTALLER OR A SERVICE AGENCY WARNING THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL S WHICH MAY CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN BY THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM ATTENTION INSTALLING PERSONNEL As a professional installer you have an obligation to know the product better than the customer This incl...

Page 3: ...e design heating and cooling loads of the area to be conditioned The loads should be calculated by an approved method or in accordance with A S H R A E Guide or Manual J Load Cal culations published by the Air Conditioning Contractors of America Obtain from American National Standards Institute 1430 Broadway New York NY 10018 TRANSPORTATION DAMAGE All units are securely packed in shipping containe...

Page 4: ... voltage field connection Fork Lift From Back Of Unit Rigging DUCT CONNECTIONS HORIZONTAL AIRFLOW INSTALLATIONS 24 30 36 42 AND PHB48 MODELS Two three inch collar connections and two square flanges are shipped with the unit The collar connections are located in the return air opening of the unit The square flanges are inside the unit blower compartment The square flanges can be used for either con...

Page 5: ...O NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE All line voltage connections must be made through weatherproof fittings All exterior power supply and ground wiring must be in ap proved weatherproof conduit Low voltage wiring from the unit con trol panel to the thermostat requires coded cable FLEXIBLE WIRING SETUP Line and low voltage wiring must enter the unit as shown EL...

Page 6: ...quare Flanges are shipped with these units to complete this conversion Models PHD48 60 and PHB60 supply and return air openings are square and do not require a flange conversion They do however require that cover clips included with the unit be installed to en sure a secure fit of the Horizontal Duct Covers 24 30 36 42 AND PHB48 Models 1 Remove and set aside the four 4 supply air side screws 2 Rem...

Page 7: ...OPERATE FURNACE WITHOUT A FILTER INSTALLED BECAUSE DUST AND LINT WILL BUILD UP ON INTERNAL PARTS RESULTING IN LOSS OF EFFICIENCY EQUIPMENT DAMAGE AND POSSIBLE FIRE Even though a return air filter is not supplied with this unit there must be a means of filtering all return air Refer to the following table or the Product Data Book applicable to your model for filter size information MODEL DISPOSABLE...

Page 8: ...n ON the electrical power supply to the unit 2 Place the room thermostat selector switch in the COOL or HEAT position or AUTO if available and if automatic changeover from cooling to heating is desired 3 Set the room thermostat to the desired temperature MAINTENANCE WARNING TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DISCONNECT ELECTRICAL POWER BEFORE PERFORMAING ANY MAINTENANCE REPL...

Page 9: ...it specific application needs Accessories can be ordered by the part numbers in the table and each accessory includes its own separate instructions REPLACEMENT PARTS Refer to the description in the Parts Catalog when ordering any part Be sure to provide the unit model manufacturing and serial num bers with the order NOTE Details for installing and wiring electric heater kits and single point wirin...

Page 10: ...N HERM CAPACITOR YL 12 VT 16 BK 27 BR 11 GND L2 T2 L1 T1 ELECTRIC HEAT RELAY COOLING SWITCH RELAY RD 11 ELECTRIC HEAT RELAY 24V CAP L2 START CAP 5 2 1 START RELAY HI MD HI LO CAP 2 4 5 ACB VT 7 RD 6 GY 9 GY 9 RD 22 RD 31 RD 27 BK 19 BK 20 BK 24 BK 13 230 208 VT 14 GY 8 BU 1 RD 27 VT 62 RD 31 VT 20 RD 10 VT 62 BU 23 RD 31 RD 24 BU 23 MODEL NUMBER COOLING BLOWER SPEED TAP ELECTRIC HEAT BLOWER TAP PH...

Page 11: ...LAY COOLING SWITCH RELAY RD 11 ELECTRIC HEAT RELAY 24V CAP L2 START CAP 5 2 1 START RELAY HI LO CAP 2 4 5 ACB VT 7 RD 6 GY 9 GY 9 RD 22 RD 31 RD 27 BK 19 BK 20 BK 24 BK 13 230 208 VT 14 GY 8 YL BK RD 27 VT 62 RD 31 VT 20 RD 10 VT 62 BU 23 RD 31 RD 24 BU 23 MODEL NUMBER COOLING BLOWER SPEED TAP ELECTRIC HEAT BLOWER TAP PHCB07C1 PHCB10C1 PHCB15C1 PHCB20C1 PHB42C02 PHB48C02 LOW MED USE COPPER CONDUCT...

Page 12: ...ERM CAPACITOR YL 12 BK 27 BR 11 GND L2 T2 L1 T1 W1 G E C R W O Y CAP L2 START CAP 5 2 1 START RELAY VT 7 RD 6 GY 9 RD 27 230 208 VT 14 GY 8 VT 62 VT 20 RD 10 TO HEATER KIT W2 USE COPPER CONDUCTORS ONLY HEATER KIT LO W PR ES SU R E S W ITC H LP S RD 27 RD 31 VT 16 VT 62 RD 33 BK 19 BK 20 C2 C1 R 3 O ADJUST NORM T EST HEAT A B C D COOL A B C D CU T TO EN ABLE DE HUM ID IFY R2 EM W2 W1 Y Y2 G VT 14 R...

Page 13: ...C 10 RD 20 VT L2 GND L1 F IE L D C O N N E C T IO N R S C MOTOR FAN O D 1Ø WIRING COMPRESSOR RD 10 VT 20 YL BK RD 31 16 VT GY 9 RD 6 VT 7 LINE LOAD 230 208 COM GND TR AN SFO R M ER G C XFMR C XFMR R R COM NC NO HI YL YELLOW OR ORANGE VT VIOLET GN GREEN BK BLACK BR BROWN WH WHITE BU BLUE GY GRAY RD RED COLOR CODE LOW VOLTAGE LOW VOLTAGE FIELD HI VOLTAGE HI VOLTAGE FIELD 22304001 REV 1 R S C FAN COM...

Page 14: ...CITOR YL 12 BK 27 BR 11 GND L2 T2 L1 T1 W1 G E C R W O Y CAP L2 START CAP 5 2 1 START RELAY VT 7 RD 6 GY 9 RD 27 230 208 VT 14 GY 8 VT 62 VT 20 RD 10 TO HEATER KIT W2 USE COPPER CONDUCTORS ONLY HEATER KIT LO W PR E SS UR E S W IT CH LP S RD 27 RD 31 VT 16 VT 62 RD 33 BK 19 BK 20 C2 C1 R 3 O ADJUST NORM T EST HEAT A B C D COOL A B C D CU T TO EN ABLE DE HUM ID IFY R2 EM W2 W1 Y Y2 G VT 14 RD 31 BLO...

Page 15: ...4 PIN 5 PIN 6 PIN 7 PIN 8 PIN 9 GY 70 TO HEATER KIT BU 34 RD 13 BR 21 OR 49 YL 29 COM FAN HERM CAPACITOR YL 12 BK 27 BR 11 GND L2 T2 L1 T1 W1 G E C R W O Y CAP L2 START CAP 5 2 1 START RELAY VT 7 RD 6 YL BK RD 27 230 208 VT 14 BU VT 62 VT 20 RD 10 TO HEATER KIT W2 USE COPPER CONDUCTORS ONLY HEATER KIT LO W PR ES SU R E S W ITC H LP S RD 27 RD 31 VT 16 VT 62 RD 33 BK 19 BK 20 C2 C1 R 3 O ADJUST NOR...

Page 16: ...E MADE 208 VOLT INSTALLATION MOVE RD6 WIRE FROM TRANSFORMER 230 TERMINAL TO 208 TERMINAL VT 14 COMMON RD 24 COOL BU 23 HEAT VT 20 RD 10 BR BR 4 3 2 1 5 6 C O N T A C T O R C C 1 2 3 5 4 REVERSING SOLENOID RS DEFROST THERMOSTAT DT PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 PIN 6 PIN 7 PIN 8 PIN 9 GY 70 TO HEATER KIT BU 34 RD 13 BR 21 OR 49 YL 27 VT 18 BK 26 COM FAN HERM CAPACITOR YL 12 VT 16 BK 27 BR 11 GND L2 ...

Page 17: ... 70 PIN 9 PIN 8 PIN 7 PIN 6 PIN 5 PIN 4 PIN 3 PIN 2 PIN 1 DT THERMOSTAT DEFROST RS SOLENOID REVERSING 4 5 3 2 1 6 5 1 2 3 4 BR BR BU 23 HEAT RD 24 COOL VT 14 COMMON CAP CAPACITOR A C B B L O W E R C IR C U L A T IO N A IR COM NC NO G C XFMR C R XFMR R 1 75 C MIN ONLY CONDUCTORS USE COPPER 31 RD 31 RD 62 VT RD 27 RD 6 VT 7 RELAY HEAT ELECTRIC T1 L1 L2 GND BR 11 BK 27 12 YL CAPACITOR HERM FAN COM C ...

Page 18: ...WN MUST BE OBSERVED CLEARANCES 36 Maximum Overhang 48 Minimum Overhang 36 Side Clearance for Servicing Recommended Minimum 9 Clearance to Combustibles 36 Clearance for Service Required 0 Minimum Clearance to Combustibles Vinyl Coated Canvas Connections Insulate Return Duct Insulated Supply Duct 24 Clearance Condenser End ...

Page 19: ...19 ...

Page 20: ...20 2000 2004 Goodman Company L P Effective July 2004 ...

Reviews: