Amana P1212701R Service Download Page 17

Troubleshooting Procedures

!

WARNING

To avoid electrical shock, personal injury, or death, disconnect power before servicing unless testing requires it.

RS4110001 Rev. 0

17

Air Conditioning Voltage Limits

This unit operates on a 115 VAC, 60 Hz power source.
Minimum voltage required to operate this unit is 103.5
VAC and maximum voltage is 126.5 VAC.

Low Voltage

Low voltage is a common cause of trouble during
operation of any room air conditioner
Improper voltage can result in one or more of the
following:
1.  Unit will not operate.
2.  Compressor motor cycling on motor protector.
3.  Premature failure of motor protector.
4. Blown fuses.
5.  Premature failure of compressor or fan motor.
6.  Noticeable dimming of lights when unit is operating.
7.  Evaporator icing, caused by low voltage reducing fan

speed resulting in an inadequate air flow over the
evaporator.

Low voltage will result from inadequately wired circuit,
extension cords, and loose fuses or connections in the
power supply. Voltage supplied by the electrical
company can also result in low power, (responsibility of
local power company.
All units will operate and run on minimum voltage stated
in "Air Conditioning Voltage Limits", and will perform
satisfactorily if voltage remains constant. Low voltage
caused by defective wiring will not remain constant under
load.
Testing for low voltage, use a reliable voltmeter with
sufficient capacity to measure the required voltage.
Verify voltage at electric power entry point and at
electrical outlet serving the unit Verify readings with the
unit off, while the unit is starting, and again while the unit
is operating. Lowest reading should not drop below the
lowest minimum value.

High Voltage

High voltage can be equally troublesome, causing motor
to overheat, cycle on their protectors, or break down
electrically. This problem can only be solved by the local
power company.

Electronic Control

Control is not repairable. If any component in the control
is defective, entire control must be replaced.

NOTE: Repair or replace any malfunctioning line voltage

component before testing or replacing the
electronic control. Do not assume service
problem is directly caused by the electronic
control system. A line voltage component
(including power cord and wiring) that has
opened, shorted, grounded or otherwise
malfunctioned, may have created a service
problem.

Summary of Contents for P1212701R

Page 1: ...nd manufacturing numbers in this manual 8V2S P1212701R 10V2S P1212702R This manual is to be used by qualified appliance technicians only Amana does not assume any responsibility for property damage or...

Page 2: ...14 Air Conditioner Features 14 Fan Control Knob 14 Temperature Control Knob 14 Vent Control Knob 14 Air Directional Louvers 15 Night Time Cooling 15 Care and Cleaning Instructions Winter Storage 16 A...

Page 3: ...t you must assume responsibility for any personal injury or property damage which may result Amana will not be responsible for any injury or property damage arising from improper service and or servic...

Page 4: ...ninsulated electrical terminals connectors heaters ect are adequately spaced away from all metal parts and panels All safety grounds are correctly and securely connected All panels are properly and se...

Page 5: ...8 8 Watts Cooling 760 1050 Fuse Breaker Delay 15 Amps 15 Amps Receptacle Code A 15 Air Flow System Capacitor MFD Volts 5 370 15 370 RPM CFM EVAP High 1100 235 1375 305 RPM CFM EVAP Medium 900 185 114...

Page 6: ...buse of the plug can result in electrical shock or overheating For your personal safety this appliance must be grounded This air conditioner includes a power supply cord with a three prong grounding p...

Page 7: ...f the window where the unit will be installed Be sure it will support the weight of the unit This appliance must be installed according to all applicable codes and ordinances Handle the air conditione...

Page 8: ...his angle installed Figures B C show alternate treatments On the sash side of the opening the leading corner of the inner sash becomes the flange You can purchase the angle strip locally Flush 1 x1 or...

Page 9: ...r track or stool Alternate screw location Platform tab Window track Window seal CAUTION To avoid risk of property damage be sure the wood stool or window track is securely attached to the building con...

Page 10: ...nt on the plastic window panel along the longer side 10 Clamp plastic window panel between a board and work table cut along the line with a fine tooth saw Remove any burrs with a file 11 Fasten side c...

Page 11: ...frame does not fit snugly to inner window sash secure panel frame to the sash with 8x3 4 inch screws or 8 32x3 4 inch self threading screws Use partially plugged holes in panel frame to drill 1 8 inc...

Page 12: ...bolt Support brace 1 4 hex flange nut NOTE If planning to use siding protection on the outside of the house hold the board in place when testing assembly in the window 2 Drill a 9 64 inch diameter pi...

Page 13: ...embly Pinch off excess length so the seal is even with the bottom of cabinet side channel 12 Remove front panel frame and filter Remove 2 screws securing front panel frame in place Press down on top e...

Page 14: ...COOL Maximum cooling speed start unit in this mode MED COOL Moderate cooling speed LOW COOL Minimum cooling speed HIGH FAN Maximum air circulation speed MED FAN Moderate air circulation speed LOW FAN...

Page 15: ...r to direct airflow either to the left or right Night Time Cooling When outside temperatures drop below 70 F 21 C and unit is cooling frost may form on coils and block air flow into room If this occur...

Page 16: ...of cabinet 2 Push front panel down and pull toward forward to release front panel from retaining lock 3 Gently pull filter forward off of clips 4 Wash filter using a liquid detergent and warm water Ri...

Page 17: ...power company All units will operate and run on minimum voltage stated in Air Conditioning Voltage Limits and will perform satisfactorily if voltage remains constant Low voltage caused by defective wi...

Page 18: ...l Fan Motor Condenser air flow restriction Condenser fins damaged Capacitor Wiring Refrigerant system Insufficient cooling Low Capacity Air filter Exhaust door open Unit undersized Excessive noise Eva...

Page 19: ...itor 8 Remove control panel 9 Remove vent door actuator arm 10 Remove screws securing control box to bulkhead 11 Remove compressor and fan motor leads from control box and remove control box 12 Remove...

Page 20: ...1 Rev 0 20 Component Location Illustrations Cabinet front panel Rear grille Cabinet wrapper Vertical louver Dial plate Control knobs Filter Control box Door vent Capacitor Capillary tube Fan control T...

Page 21: ...Disassembly Procedures RS4110001 Rev 0 21 Fan blade Fan motor Blower wheel Blower housing Fan housing Compressor Evaporator Condensor Evaporator tray...

Page 22: ...lack BR Brown R Red W White G GND Ribbed Blue R R W S BK C Start Assist Compressor Capacitor Fan Capacitor BR Compressor BK R R S W Fan Motor Compressor Overload Room Thermostat R BL BK W BK L1 3 1 2...

Reviews: