6
F
URNACE
O
PERATION
E
LECTRICAL
COMPONENTS
ARE
CONTAINED
IN
BOTH
COMPARTMENTS
.
T
O
AVOID
PERSONAL
INJURY
,
ELECTRICAL
SHOCK
OR
DEATH
,
DO
NOT
REMOVE
ANY
INTERNAL
COMPARTMENT
COVERS
.
C
ONTACT
A
QUALIFIED
SERVICER
AT
ONCE
IF
AN
ABNORMAL
CONDITION
IS
NOTICED
.
WARNING
Keep both doors in place except for inspection and mainte-
nance. An interlock switch prevents furnace operation if
the blower door is not in place.
F
URNACE
S
TART
-U
P
1. Close the external manual gas shut-off valve.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible set-
ting.
4. Remove the burner compartment door.
5. This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the
burner by hand.
6. Move the furnace’s gas valve ON/OFF switch to the
OFF position.
7. Wait five minutes to clear out any gas. Then smell for
gas, including near the floor as some types of gas are
heavier than air.
8. If you smell gas following the five minute waiting pe-
riod in step 7, immediately follow the instructions on
the cover of this manual. If you do not smell gas after
five minutes, move the furnace’s gas valve ON/OFF
switch to the ON position.
9. Replace the burner compartment door.
10. Open the external manual gas shut-off valve.
11. Turn on the electrical power to the furnace.
12. Adjust the thermostat to a setting above room tem-
perature.
13. After the burners are lit, set the thermostat to desired
temperature.
Gas Valve On/Off
Selector Switch
Honeywell Model VR8215 (Single-Stage)
Gas Valve On/Off
Selector Switch
Honeywell Model VR9205 (Two-Stage)
White-Rodgers Model 36G22 (Single-Stage)
OUTLET
INLET
On/Off Switch
White-Rodgers Model 36G54 (Two-Stage)
F
URNACE
S
HUT
D
OWN
To shut down your furnace, follow the steps listed below.
1. Set the thermostat to the lowest setting.
2. Integrated control closes gas valve extinguishing flame.
3. Induced draft blower is de-energized following a 15 sec-
ond delay. The circulator blower is de-energized fol-
lowing a 90, 120, 150, or 180 second delay period.
4. Remove the burner compartment door.
5. Move the furnace’s gas valve ON/OFF switch to the OFF
position.
6. Close the external manual gas shut-off valve.
7. Replace the burner compartment door.
L
OCKOUT
R
ESET
Furnace lockout is characterized by a non-functioning fur-
nace (circulator blower may be running continuously) pro-
viding a diagnostic LED code. Lockout results when a fur-
nace control detects abnormal conditions. If the furnace
is in “lockout”, it may be reset by any of the following
methods:
1. One hour automatic reset. Control will automatically
reset itself and attempt to resume normal operations
following a one hour lockout period.