background image

Model and Manufacturing
numbers listed in this manual.

MODEL

M/N

BBA24A2A

P1206401C

BBA36A2A

P1206402C

BBA48A2A

P1206403C

BBA60A2A

P1206404C

BBA24A2A

P1206415C

BBA36A2A

P1206416C

BBA48A2A

P1206417C

BBA60A2A

P1206418C

TECHNICAL INFORMATION MANUAL

BBA* Blowers

Refer to Service Manual RS6200003 for installation, op-
eration, and troubleshooting information.

All safety information must be followed as provided in
the Service Manual.

Refer to the appropriate Parts Catalog for part number
information.

®

is a trademark of Maytag Corporation and is used under license to Goodman

Company, L.P.  All rights reserved.

Copyright © 2004 Goodman Company, L.P.

RT6221002 Rev. 1

 December 2004

This manual is to be used by qualified HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury
due to improper service procedures performed by an unqualified person.

Summary of Contents for BBA24A2A

Page 1: ...g information All safety information must be followed as provided in the Service Manual Refer to the appropriate Parts Catalog for part number information is a trademark of Maytag Corporation and is used under license to Goodman Company L P All rights reserved Copyright 2004 Goodman Company L P RT6221002 Rev 1 December 2004 This manual is to be used by qualified HVAC technicians only Goodman does ...

Page 2: ... CAUSE SERIOUS INJURY OR DEATH GOODMAN WILL NOT ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU PERFORM SERVICE ON YOUR OWN PRODUCT YOU ASSUME RESPONSIBIL ITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY RESULT WARNING WARNING CAUTION Design Series A First Series Product Type B Blower Unit System Type B Multi position Blowe...

Page 3: ...x matching possibili ties providing greater flexibility The BBA blower cabinets can be positioned for upflow counterflow horizontal right or horizontal left operation All units are constructed with R 4 2 insulation In areas of extreme humidity greater than 80 consistently the installer should insulate the exterior of the blower with insulation having a vapor barrier equivalent to ductwork insulati...

Page 4: ...MCA1 MOP1 BBA24A2A 16 1 2 15 15 63 28 6 9 x 7 1 4 1 9 15 BBA36A2A 419 22 1 4 565 381 381 68 30 8 10 x 7 1 3 3 15 BBA48A2A 20 1 2 521 19 483 19 483 78 35 4 10 x 10 1 3 3 8 15 BBA60A2A 24 1 2 622 26 1 4 667 23 584 23 584 90 40 8 11 x 10 1 2 4 9 15 1 Minimum Circuit Ampacity MCA and Maximum Overcurrent Protection MOP for blower without supplemental heat installed Refer to unit nameplate for MCA and M...

Page 5: ...B20B C ECB25B C ECB30B C Model ECB05B C ECB07B C ECB10B C ECB15B C ECB20B C ECB25B C ECB30B C SPK02A SPK02A SPK03A SPK03A L1 L2 30 45 60 60 60 80 110 BBA24A2A L3 L4 30 60 L1 L2 30 45 60 60 60 60 60 90 110 150 175 BBA36A2A L3 L4 30 60 60 60 L5 L6 30 60 L1 L2 30 45 60 60 60 60 60 90 110 150 175 BBA48A2A L3 L4 30 60 60 60 L5 L6 30 60 L1 L2 35 45 60 60 60 60 60 90 110 150 175 BBA60A2A L3 L4 30 60 60 6...

Page 6: ...MUST BE PROPERLY GROUNDED USE COPPER CONDUCTORS ONLY SUITABLE FOR MINIMUM 75 C PUT DESIRED SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED RD6 BK9 YL7 YL7 VT BR VT14 BU YL OR RD BK MIB CAP L2 L1 FAN IDLE FAN FAN COM L2 L1 TRANSFORMER COM 208 240 R C Y E O G W2 L O G I C THERMISTOR 10 11 12 9 8 7 6 5 4 ...

Page 7: ...USABLE LINK 1 3 UNIT MUST BE PROPERLY GROUNDED PUT DESIRED SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FL...

Page 8: ...GY GRAY Approved Thermostats are D9945804 10636702 10636701 D9807605 With Outdoor Thermostat ATK Controlling ALL Electric Heat Morning Warmup Could be Slow 4 8 to 28 8KW ROOM THERMOSTAT 6 wires BBA or BBC BLOWER COIL 6 wires RH OUTDOOR UNIT ATK Controlling ALL Electric Heat Except In The Defrost Mode ROOM THERMOSTAT 6 wires BBA or BBC BLOWER COIL 6 wires RH OUTDOOR UNIT R Y E W 1 W 2 C X A T K 0 5...

Page 9: ...INK 1 2 3 UNIT MUST BE PROPERLY GROUNDED USE COPPER CONDUCTORS ONLY SUITABLE FOR MINIMUM 75 C PUT DESIRED SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLA...

Page 10: ...T MUST BE PROPERLY GROUNDED USE COPPER CONDUCTORS ONLY SUITABLE FOR MINIMUM 75 C PUT DESIRED SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHE...

Page 11: ...D SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME ...

Page 12: ... MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTA...

Page 13: ...CLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTAGE HIGH VOLTAGE RD26 LOW BU24 MED...

Page 14: ...INAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTAGE HIGH VOLTAGE RD26 LOW BU24 MED BK27 HI 4 12 PIN CON...

Page 15: ... FUSABLE LINK 1 3 UNIT MUST BE PROPERLY GROUNDED PUT DESIRED SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED ...

Page 16: ...UST BE PROPERLY GROUNDED PUT DESIRED SPEED TAP ON TERMINAL MARKED FAN IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 S...

Page 17: ... IF DESIRED PUT OFF CYCLE SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTAGE HIGH VOL...

Page 18: ... SPEED TAP ON TERMINAL MARKED FAN IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTAGE HIGH VOLTAGE RD26 LOW BU24 MED BK...

Page 19: ...IDLE PUT UNUSED SPEED TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTAGE HIGH VOLTAGE RD26 LOW BU24 MED BK27 HI 4 12 PIN CONNECTOR LED W2 TR...

Page 20: ... TAPS ON TERMINALS MARKED UNUSED CONTROL BOARD MALFUNCTION CONTINUOUS NONE 6 FLASHES SYSTEM ERROR 3 SECONDS THERMISTOR ERROR THERMISTOR AND OR BOARD ERROR NORMAL OPERATION MODE 4 FLASHES 2 FLASHES 1 2 SECOND ON LED ON TIME LED FLASH CODE 3 SECONDS 3 SECONDS 1 2 SECOND OFF LED OFF TIME 3A FUSE MAX 4 LOW VOLTAGE HIGH VOLTAGE RD26 LOW BU24 MED BK27 HI 4 12 PIN CONNECTOR LED W2 TRANSFORMER 208 L1 240 ...