SERVICING
21
SECTION 4. OUTDOOR UNIT IS BELOW THE INDOOR UNIT
1. The maximum elevation (vertical) difference between the outdoor unit and the indoor unit is 90 feet.
2. Suction line must be installed in a manner to prevent liquid migration to the outdoor unit from the indoor unit.
The heat pump condenser unit is shipped with a predetermined factory charge level as shown in the following chart. For
longer line sets greater than 15 feet, add 0.6 ounces of refrigernat per foot.
Oil Trap Construction
45°
ELL
SHORT RADIUS
STREET ELL
45°
STREET
ELL
LONG RADIUS
STREET ELL