Amana AVH09 Installation Instructions & Owner'S Manual Download Page 17

Final Installation Checklist

WARNING

HIGH VOLTAGE

DISCONNECT ALL POWER BEFORE SERVICING 

OR INSTALLING THIS UNIT.  MULTIPLE POWER 

SOURCES MAY BE PRESENT.  FAILURE TO DO SO 

MAY CAUSE PROPERTY DAMAGE, PERSONAL 

INJURY OR DEATH.

Inspect and ensure that all components and

accessories have been installed properly and that

they have not been damaged during the installation

process.

Ensure that all installation instructions concerning

clearances around the unit have been adhered

to.

Check to ensure that the unit air filte , indoor coil, and

outdoor coil are free from any obstructions.

Ensure that the circuit breaker(s) or fuse(s)

and supply circuit wire size have been sized

correctly.

Check the condensate water drain(s) to ensure that

they are adequate for the removal of condensate

water and that they meet approval of the end

user.

Ensure that the entire installation is in compliance

with all applicable national and local codes and

ordinances having jurisdiction.

ENSURE THAT THE SUPPLY VOLTAGE TO THE

UNIT IS WITHIN THE OPERATING RANGE

Secure all access panels (i.e. front cover and/

or control box), apply power to the unit. The unit

commissioning should be done at this time to ensure

unit function.

NOTE: Maintaining a log for recording the dates of 

maintenance and/or service is recommended, and 

should be suggested to the owner or operator of the 

equipment.

Present the owner or operator of the equipment with

the Installation & Operation Manual, all accessory

installation instructions, and the name, address and

telephone number Warranty Service Company in the

area for future reference if necessary.

NOTE: The unit is not designed to guarantee 

continuous operation with outdoor ambient conditions 

greater than 110°F.

Chassis Operation

Fresh Air Door

The fresh air door is an “intake” system. It is opened via 

a slide mechanism on the front of the chassis located just 

above the indoor coil.  Move the slide left to open and right 

to close the door.  The system is capable of delivering up to 

60 CFM of outdoor air.

Low Ambient Compressor Cut Out

Each chassis is equipped with low ambient protection 

that is determined by thermistor feedback.  The feedback 

will prevent the compressor from operating at low suction 

temperatures.

Room Freeze Protection

This feature will monitor the indoor room conditions and in 

the event that the room falls below 40°F, the unit will cycle 

on high fan with the electric heater.  This occurs regardless 

of mode.

Chassis Final Connections

With the chassis in place, you are now ready to begin 

chassis connections:

A. Move the thermostat switches to “OFF” and  “AUTO”.

This will keep the thermostat from cycling the chassis

until final connections are complete

B. Connect the duct work onto the 10” collar. Plastic

wire ties (field supplied) are suggested to secur

the duct work in place. Use 2 wire ties, one for each

inner and outer flex duct sleeve

C. Review the Final Installation Checklist before

replacing the power quick disconnect, reconnecting

power to the chassis, or operating the chassis.

WARNING

HIGH VOLTAGE

DISCONNECT ALL POWER BEFORE SERVICING 

OR INSTALLING THIS UNIT.  MULTIPLE POWER 

SOURCES MAY BE PRESENT.  FAILURE TO DO SO 

MAY CAUSE PROPERTY DAMAGE, PERSONAL 

INJURY OR DEATH.

Service & Warranty

Servicing / Chassis Quick Changeouts

The chasis is designed for quick disconnect and change 

out. For minor electrical service, the control box cover 

lifts straight up after the screws & disconnect head are 

removed. For major electrical, refrigeration and fan service 

the chassis may be removed from utility closet.

16

Summary of Contents for AVH09

Page 1: ...e equipment specified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting t...

Page 2: ...ntent of this manual the precautions listed here take precedence Important Note to the Servicer Read this manual and familiarize yourself with the specific items which must be adhered to before attemp...

Page 3: ...Y Wire sizes are per NEC Recommended Branch Circuit Sizes Nameplate Maximum Circuit Breaker Size AWG Wiring Size 15A 14 20A 12 30A 10 AWG American Wire Gauge Single circuit from main box Based on 100...

Page 4: ...the HIGH speed output to the GH terminal VTAC Required Minimum Clearances Building Exterior Unit Opening Requirements VTAC units must be installed on an outside wall Confined spaces and or covered are...

Page 5: ...ation Overview and Dimensional Data Closet View NOTE It is recommened that 6 of clearance is provided on the side where the primary condensate is plumbed 3 4 Exterior Wall Adapter Cut Out Dimensions W...

Page 6: ...1 8 26 1 8 CLOSET INSTALLATIONS 5 Access Door Cutout 27 Min 3 Required 23 1 8 23 1 8 30 5 8 Min Required Inside Closet Dimension 23 1 8 Access Door Cutout 27 23 1 8 23 1 8 30 5 8 Min Required Inside...

Page 7: ...x 24 1 8 W x 30 3 8 H Large Chassis Unit Unit height 47 Filter 14 x 20 Small Chassis Unit Unit height 32 Filter 14 x 20 AVDK18 2401B drain pan required Sold Shipped Separately Architectural Grille AV...

Page 8: ...ry any structural load A load bearing header must be built above the rough opening 1 Prepare the rough opening The rough opening should be lined with metal or wood The Wall Adapter will warp if sealed...

Page 9: ...pilot holes on the interior of the inside Wall Adapter half Part B as show in Detail B Pilot holes should be located approximately 4 from the top and bottom of the inside Wall Adapter half on both th...

Page 10: ...safety tether Final Wall Adapter and Architectural Louver Installation NOTE Ensure that the weather strip is undamaged and provides a continuous seal around the inner perimeter of the Wall Adapter App...

Page 11: ...tem drain waste vent may result in staining of the outside wall 2 Insert the provided 3 4 nipple into the determined connection using field supplied Teflon tape or pip joint compound 3 With the slip e...

Page 12: ...of the removed gasket The secondary overflow lip must extend into the plenum to prevent water leaks The pan should be mounted against the 3 4 flange of the plenum refer to view A Figure 2 Install Dra...

Page 13: ...ndensate line as shown in Option 4 below as the drain line will come into contact with the factory installed isolators beneath the unit Figure 5 Option 1 Run condensate line to left of unit Option 3 R...

Page 14: ...ERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT CAUTION TO AVOID RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS CAUTION TO AVOID...

Page 15: ...for a maximum friction rate of 3 water column taking into consideration all fittings registers and or diffusers NOTE Do not operate the unit without a supply duct attached The return air to the VTAC...

Page 16: ...ation will stop NOTE The desk control system and switches must be field supplied Maximum Wire Length for Desk Control Switch AWG Wire Size Maximum Length ft 24 400 22 600 20 900 18 1500 16 2000 Auxili...

Page 17: ...with outdoor ambient conditions greater than 110 F Chassis Operation Fresh Air Door The fresh air door is an intake system It is opened via a slide mechanism on the front of the chassis located just a...

Page 18: ...hrough the filter and collect on the indoor ai These minor accumulations can be carefully vacuumed away with a brush attachment on a vacuum claner Care must be taken to avoid bending the aluminum finn...

Page 19: ...ration after lockout time 8 Unit Cycles greater than 9 Times per hour The unit will continue to operate and be monitored 9 Unit Cycles less than 3 Times per Hour The unit will continue to operate and...

Page 20: ...anization To obtain an authorized servicer contact your sales representative is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company L P H...

Reviews: