S
peCifiCAtionS
ASX14
0181D
ASX14
0241C
ASX14
0301C
ASX14
0361C
ASX14
0421D
ASX14
0481B
ASX14
0481C
ASX14
0601B
Cooling Capacity
Nominal Cooling (BTU/h)
18,000
24,000
28,800
34,600
40,000
45,000
46,000
56,800
Decibels
70
71
72
73
73
74
74
75
Compressor
RLA
9.0
13.5
12.8
14.1
16.7
19.8
19.9
26.4
LRA
48.0
58.3
64.0
77.0
79.0
109.0
109.0
134.0
Condenser Fan Motor
Horsepower (RPM)
⅛
¹⁄₁₂
¹⁄₆
¹⁄₆
¹⁄₆
¼
¼
¼
FLA
0.70
0.60
1.10
0.90
0.90
1.60
1.50
1.60
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
¾"
⅞"
1
⅛"
1
⅛”
1
⅛”
1
⅛”
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.)
¾"
¾"
¾"
⅞"
⅞"
⅞"
⅞"
⅞"
Valve Connection Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
70
88
93
98
120
183
147
268
Shipped with Orifice Size
0.052
0.055
0.065
0.068
0.070
0.079
0.078
0.088
Electrical Data
Voltage-Phase
208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Minimum Circuit Ampacity ²
12
17.5
16.9
18.5
21.8
26.4
26.4
34.6
Max. Overcurrent Protection ³
20
30
25
30
35
45
45
60
Min / Max Volts
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
197 / 253
Electrical Conduit Size
Power Supply
½”
or
¾” ½”
or
¾” ½”
or
¾
” ½”
or
¾” ½”
or
¾” ½”
or
¾” ½”
or
¾” ½”
or
¾”
Low Voltage
½"
½"
½"
½"
½"
½"
½"
½”
Equipment Weight (lbs)
141
144
162
154
188
220
220
290
Ship Weight (lbs)
178
161
180
172
184
242
242
312
¹ Line sizes denoted for 25’ line sets, tested and rated in accordance with AHRI Standard 210/240. For other line-set lengths or sizes, refer
to the installation & Operating instructions and/or the long line-set guidelines.
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.