SS-AACNF www.amana-hac.com 

5

4

 

www.amana-hac.com SS-AACNF

P

roduCt

 S

PeCiFiCAtioNS

P

roduCt

 S

PeCiFiCAtioNS

S

PeCiFiCAtioNS

 (

CoNt

.)

ACNF24

081

ACNF24

101

ACNF30

001

ACNF30

051

ACNF30

061

ACNF30

081

ACNF30

101

Performance Ratings
Cooling (BTU/h)

24,000

24,000

30,000

30,000

30,000

30,000

30,000

Airflow Rate CFM (High/ Low)¹

880/840

880/840

1005/890

1005/890

1005/890

1005/890

1005/890

Blower
Diameter

6.31

6.31

6.75

6.75

6.75

6.75

6.75

Width

8.25

8.25

8.25

8.25

8.25

8.25

8.25

Coil Drain Connect FPT

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

Refrigerant Line Connection Size
Liquid 

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

Suction

¾"

¾"

¾"

¾"

¾"

¾"

¾"

Electrical Data
Voltage

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Min Circuit Ampacity @ 230V

41.3

54.9

1.68

27.8

34.3

41.3

54.9

Min Circuit Ampacity @ 208V

36.1

47.8

1.68

24.3

29.9

36.1

47.8

Max. Overcurrent Device @ 230V

45

60

15

30

35

45

60

Max. Overcurrent Device @ 208V

40

50

15

25

30

40

50

Minimum Voltage VAC

197

197

197

197

197

197

197

Maximum Voltage VAC

253

253

253

253

253

253

253

Electric Heat
kW @ 230 Volts

7.3

9.8

0.0

4.8

6.0

7.3

9.8

BTU/h @ 230 Volts

24,900

33,500

0

16,400

20,500

24,900

33,500

Blower Motor
FLA

1.34

1.34

1.34

1.34

1.34

1.34

1.34

HP

 1/4

 1/4

 1/4

 1/4

 1/4

 1/4

 1/4

Ship Weight (lbs)

64

64

65

68

68

68

68

¹   CFM @ .2 static

Note:  When the room thermostat calls for second stage heat, the first stage (heat pump) operation must be locked out. When matching the “AC” unit that 
has electric heat with a heat pump, order “HEAT PUMP SHUT OFF KIT HPSK-01.” The ACXX-00 units do not require this kit.

Summary of Contents for American Pride ACNF Series

Page 1: ...evaporator coil Quiet operation Available with and without heat AHRI Certified ETL Listed Cabinet Features Primary secondary drain connection in a high temperature plastic drain pan Suitable for free return installation non ducted return air Galvanized steel construction Factory installed pull type disconnect Easy service access Complete warranty details available from your local dealer or at www ...

Page 2: ...22 only E Multi Position Variable Speed Motor 6 R 410A or R 22 R Multi Position PSC Motor S Multi Position EEM Motor W Wall Mount PSC Motor Electrical 1 208 240 V 1 Phase 60 Hz Cabinet Finish U Unpainted P Painted Nominal Capacity Range 13 SEER N Uncased Nominal Factory Installed Electric Heat kW 1805 1 Tons Cooling 5 kW Electric Heat Expansion Device 2405 2 Tons Cooling 5 kW Electric Heat F Flowr...

Page 3: ...acity 230V 0 9 27 33 5 40 6 1 68 27 8 34 3 Min Circuit Ampacity 208V 0 9 23 5 29 2 35 3 1 68 24 3 29 9 Max Overcurrent Device 230V 15 30 35 45 15 30 35 Max Overcurrent Device 208V 15 25 30 40 15 25 30 Minimum Voltage VAC 197 197 197 197 197 197 197 Maximum Voltage VAC 253 253 253 253 253 253 253 Electric Heat kW 230 Volts 0 0 4 8 6 0 7 3 0 0 4 8 6 0 BTU h 230 Volts 0 16 400 20 500 24 900 0 16 400 ...

Page 4: ...acity 230V 41 3 54 9 1 68 27 8 34 3 41 3 54 9 Min Circuit Ampacity 208V 36 1 47 8 1 68 24 3 29 9 36 1 47 8 Max Overcurrent Device 230V 45 60 15 30 35 45 60 Max Overcurrent Device 208V 40 50 15 25 30 40 50 Minimum Voltage VAC 197 197 197 197 197 197 197 Maximum Voltage VAC 253 253 253 253 253 253 253 Electric Heat kW 230 Volts 7 3 9 8 0 0 4 8 6 0 7 3 9 8 BTU h 230 Volts 24 900 33 500 0 16 400 20 50...

Page 5: ...4 0 82 Multiply the 230 volt capacity by factors Model Motor Speed CFM delivered against External Static Pressure 0 1 0 2 0 3 0 4 0 5 ACNF180 High 710 660 590 515 435 Low 650 595 540 480 390 ACNF240 High 955 880 820 740 675 Low 885 840 775 725 620 ACNF300 High 1 075 1 005 920 820 730 Low 945 890 835 760 650 Note Airflow data for 240 Vac with dry coil and no filter in place ...

Page 6: ...6 www amana hac com SS AACNF Product Specifications Dimensions Model A B C D ACNF18 37 3411 16 30 6 ACNF24 43 4011 16 36 6 ACNF30 49 4611 16 42 6 ...

Page 7: ...ubject to change Always refer to the wiring diagram or the unit for the most up to date wiring W arning High Voltage Disconnect all power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death ...

Page 8: ...man Company L P All rights reserved Our continuing commitment to quality products may mean a change in specifications without notice 2011 Goodman Company L P Houston Texas Printed in the USA Accessories Model Description HPSK 01 Heat Pump Shut off Relay Kit Louvered Ceiling Access Panels CAP 1 1L Fits ACNF18 CAP 2 2L Fits ACNF24 CAP 3 3L Fits ACNF30 ...

Reviews: