TROUBLESHOOTING
46
PCBBF134 CONTROL BOARDS
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
Associated
LED Code
2
4
4 FLASHES
• Circulator blower runs
continuously. No
furnace operation.
• Integrated control
module diagnostic
LED
is flashing
FOUR
(4) flashes.
6
6 FLASHES
7 FLASHES
• Furnace fails to operate.
• Integrated control module
diagnostic
LED
is
flashing
SIX
(6) flashes.
• Normal furnace
operation.
• Integrated control
module diagnostic
LED
is flashing
SEVEN
(7)
flashes.
• Rollout limit
open.
• Integrated
control module
fuse is blown.
• Flame sense
microamp signal is
low.
• Flame sensor is coated/
oxidized.
• Flame sensor incor-
rectly positioned in
burner flame.
• Lazy burner flame due
to improper gas
pressure or combustion
air.
• Turn power OFF
prior to repair.
• Clean flame
sensor with steel
wool.
• See rating plate
for proper gas
pressure.
• See “Vent/Flue
Pipe” section for
piping details.
• Replace induced
draft blower with
proper replace-
ment part.
• Replace inte-
grated control
module fuse with
3A automotive
fuse.
• Read precautions
in “Electrostatic
Discharge”
section of manual.
• Replace rollout
limit with correct
replacement part.
• Primary limit
circuit is
open.
• Check burners for
proper alignment.
• Check flue and air inlet
piping for blockage,
proper length, elbows,
and termination. Correct
as necessary.
• Check rollout limit.
Replace if necessary.
• Check heat exchanger.
• Check induced draft
blower for proper
performance. Replace,
if necessary.
• Check position of orifice
plate/heat exchanger
shield.
• Tighten or correct wiring
connection.
• Repair short in 24 volt
AC control/safety
circuit(s).
• Replace integrated
control module fuse
(3A).
• Flame rollout.
• Misaligned burners,
blocked flue and/or air
inlet pipe, or failed
induced draft blower.
• Loose or improperly
connected wiring.
• Short in 24 volt AC
control circuits or
safety circuits.
• Faulty rollout limit.
• Induced draft blower
and circulator blower
runs continuously. No
furnace operation.
• Integrated control
module diagnostic
LED
is flashing
FIVE
(5)
flashes.
5
5 FLASHES
• Flame sensed
with no call
for heat.
• Short to ground in flame
sense circuit.
• Correct short at flame
sensor or in flame
sensor wiring.
• Turn power
OFF prior to
repair.
• Insufficient conditioned air
over the heat exchanger.
Blocked filters, restrictive
ductwork, improper
circulator blower speed,
or failed circulator blower.
• Faulty primary limit switch.
• Loose or improperly
connected wiring.
• Check primary limit.
Replace if necessary.
• Check filters and
ductwork for blockage.
Clean filters or remove
obstruction.
• Check circulator blower
speed and perfor-
mance. Correct speed
or replace blower if
necessary.
• Turn power OFF
prior to repair.
• Replace primary
switch with
proper replace-
ment part.
• Replace blower
with correct
replacement part.
Cautions
& Notes
Corrective Action
Possible Causes
Fault
Description(s)
Symptoms of
Abnormal Operation
• No furnace
operation.
• Inspect for proper
sensor alignment.
• Compare current gas
pressure to rating
plate info. Adjust as
needed.
7