Always
O
n UPS Systems
M1201_Din_Rail_AC-DC_600VA_Manual V1.6 2012-06-12.doc
10
SPECIFICATIONS
UPC Order Code
825433 00861
Capacity 600VA
Voltage
120VAC nominal, +/-20%
Frequency
50 or 60Hz +/- 10% (auto sensing)
INPUT
Input
Hard wire - Terminal Block
Voltage (on battery)
/-5%, Modified Sine Wave
Frequency (on battery)
50 or 60Hz +/- 1Hz
Auto Voltage Regulation
(AVR Function)
Automatically regulates the output voltage to /-10% of nominal
Terminal Block
Hard wire
OUTPUT
Transfer Time
4-6ms, including detection
Spike/Noise Protection
YES
Overload Protection
YES
PROTECTION
and FILTERING
Short Circuit
Breaker protection or immediate shutdown
Type
Sealed, maintenance-free lead acid
Typical Recharge Time
6 hours (to 90% of full capacity)
BATTERY
Back up Time
10-15 minutes
Net weight kg(lbs)
6.5(14.3)
Shipping weight kg(lbs)
7.2(15.9)
PHYSICAL
DATA
Dimension(mm)WxDxH 315x97x137
LED Display
Normal / Backup / Overload
INTERFACE
Audible Alarm
YES
Elevation
3,500 meters max.
Temperature range
0-40
o
C
Humidity 0-95%
non-condensing
ENVIRONMENT
Audible Noise
<40dBA (1 meter from surface)
Safety
cUL/UL 1778, CSA C22.2, CE
EMI/RFI
FCC Class B
SAFETY
APPROVAL
Surge/Transient
IEEE C62.41 Category A
Specifications are subject to change without prior notice to reflect upgrades and improvements in technology
.
DC Power Supply Specifications:
Output Voltage:
24VDC
Regulation: +/-
1%
Ripple and Noise:
<150mV
Rated Current:
1.5A Continuous, 2 A Surge
Capacity: 58
Watts
Protection: