background image

sure it is a nuisance alarm, press the large 

test button to silence the Alarm for 10 

minutes – the red LED will then flash every 

8 seconds for 10 minutes.

1.2. Fault Conditions

1.2.1. Low Batteries

The Alarm will emit a short beep and flash 

the yellow LED when it becomes partially 

depleted. Check the date when the Alarm 

should be replaced which is given on the 

sidewall of the Alarm. When electronic 

self testing indicates that the batteries are 

becoming low, the Alarm will beep and 

the yellow LED will flash at the same time 

(about every 48 seconds) to warn the user. 

This indicates that the batteries must be 

replaced.

2.  Location and Positioning

 

 

Introduction

You can easily install these Alarms 

throughout the property on escape routes, 

on each story, in corridors and in closed 

rooms to give warning of fire.

Heat Alarms can be installed in kitchens 

and other areas where Smoke Alarms are 

unsuitable.

NATIONAL FIRE PROTECTION 

ASSOCIATION REQUIRED PROTECTION

Smoke Detection. Where required by 

applicable laws, codes, or standards for the 

specified occupancy, approved single- and 

multiple-station Smoke Alarms shall be 

installed as follows:

(1) In all sleeping rooms and guest rooms

Indicator Summary

Normal Operation

Action

Red LED

Yellow LED

Sounder

Power Up

Insert Battery

1 Flash

1 Flash

Off

Standby

Off

Off

Off

Sensing Fire

Rapid Flashing

Off

Full Sound

Fault Mode

Action

Red LED

Yellow LED

Sounder

Low Battery

Off

1 Flash every 48 sec

1 Beep

Faulty Heat Sensor 

Off

2 Flashes every 
48 sec

2 Beeps

End of Life

Off

3 Flashes every 
48 sec

3 Beeps

Silence Sounding Alarm

Press & Release 
Button

1 Flash every 
8 sec

Off

Off for 10 mins

Silence “End of Life” 
indication (up to 30 days)

Press & Release 
Button

Off

Off for 72 hours

Off for 72 hours

Test Mode

Action

Red LED

Yellow LED

Sounder

Test Heat Alarm

Press Button

Rapid Flashing

Off

Full Sound

Alarm Memory

Action

Red Led

Yellow LED

Sounder

24 Hour Memory

2 Flashes 
every 48 sec 
for 24 hours

Off

Off

Long Term Memory

Press & Hold 
Button

Rapid Flashing

Off

Rapid Chirping

1.1. Normal Operation

1.1.1. Power Up

Twist off the Alarm from the mounting 

plate (see Quick Start Guide). Remove the 

battery tab to power the Alarm, the red LED 

will flash once followed by one flash of the 

yellow LED to indicate that the Alarm has 

been powered successfully and is now in 

standby mode.

1.1.2. Standby

In standby mode there are no active visible 

or audible indications which can be intrusive 

to the householder. To confirm that the 

Alarm is operational perform a weekly 

button test.

1.1.3. Weekly Button Test

Press and hold the test button, verify that 

the red LED flashes rapidly, and the Alarm 

ramps up to full sound.

1.1.4. Sensing Fire

When the Alarm senses a temperature 

above 135°F (57°C) or a temperature 

change greater than 15°F (8.3°C)/min and 

the temperature is above 104ºF (40ºC), 

it will go into alarm. The red LED on the 

Alarm sensing heat flashes rapidly to 

indicate this is the Alarm sensing heat / 

fire. Follow the instruction in section 3 and 

evacuate the building.

Conditions that will cause an alarm:

1. Temperature is above 135°F (57ºC).

2. Temperature is rising at a rate of 15ºF 

(8.3ºC)/min and the temperature is above 

104ºF (40ºC).

1.1.5. Silence False / Nuisance Alarm

To silence a nuisance alarm, once you are 

2

Summary of Contents for RE617

Page 1: ...st button until the Heat Alarm beeps 5 Remove the mounting plate and refer to Sections 2 and 5 for positioning and installation 6 After mounting plate is installed restore the Heat Alarm onto the mounting plate and fully test the Heat Alarm per Section 6 Alternate Enrollment Methods Scan the Heat Alarm s bar code using the Connect Installer app OR Enter the 8 character serial number on the interac...

Page 2: ...ashes every 48 sec 3 Beeps Silence Sounding Alarm Press Release Button 1 Flash every 8 sec Off Off for 10 mins Silence End of Life indication up to 30 days Press Release Button Off Off for 72 hours Off for 72 hours Test Mode Action Red LED Yellow LED Sounder Test Heat Alarm Press Button Rapid Flashing Off Full Sound Alarm Memory Action Red Led Yellow LED Sounder 24 Hour Memory 2 Flashes every 48 s...

Page 3: ...not be more than 6 4 meters 21ft from the door to any room where a fire may start and block your escape from the house Multi Story Dwellings If your home has more than one floor at least one Alarm should be fitted on each level see Figure 1 Preferably the Alarms should be interconnected if feature is present on unit so as to give sufficient warning throughout the property Figure 1 illustrates wher...

Page 4: ...ng Alarms Can Be Heard With the Alarms sounding in their intended locations check that the alarm can be heard in each bedroom with the door closed above the sound of any TV audio systems The TV audio systems should be set to a reasonably loud conversation level If you cannot hear the alarm over the sound of the TV audio system the chances are it would not wake you This unit is required to be insta...

Page 5: ...all screwdriver to release the catch push catch towards the ceiling and then twist off the Alarm see Figure 5b Figure 5a How to Tamperproof BREAK OFF SMALL PILLAR 3 Get out as fast as you can Do not stop for packing Have a prearranged meeting place outside for all family members Check everybody is there 4 Call the Fire Department from a neighbor s house or mobile phone Remember to give your name a...

Page 6: ...conds with the yellow light flashing at the same time Replace the batteries 6 3 2 Battery Replacement When the batteries power is low and replacement is necessary the Heat Alarm will beep and the yellow light will flash at the same time about once every 48 seconds for at least 7 days The batteries must then be replaced Also replace the batteries if the Alarm does not sound when the Test Button is ...

Page 7: ...y for further advice 7 Getting Your Alarm Serviced If your Alarm fails to work after you have read the sections on Installation and Testing Maintenance and Power Supply Monitoring contact Tech Support at the phone number provided at the end of this guide For product returns ensure the product is shipped with the batteries disconnected and return to Alula Attn RMA 2340 Energy Park Drive Suite 100 S...

Page 8: ... FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference that may be received including interference that may cause undesired operation Changes or modifications not expressly approved by Alula could void the user s authority to operate this equipment FCC ID U5X RE314 IC NOTICE This device complies wi...

Reviews: