PANEL ENROLLMENT
(continued)
DSC ®
A
Translator enrollment:
a) Enter Wireless Enrollment mode.
b) Trip the translator cover tamper to enroll the translator.
c)
Zone Type: 03 (instant)
• For the first 24 hours after power-up, all translator
tamper trips will send a temporary “open” for
enrollment purposes.
B
Sensor enrollment:
a)
Enter Wireless Enrollment Mode.
b) Trip each sensor to initiate enrollment.
c) Set up the sensor for the desired behavior.
•
Note, when translating to DSC, incoming sensors may
use only one input. For example, reed or external
contact, but not both.
Qolsys ®
• Qolsys IQ panel uses Interlogix 319.5MHz protocol.
• DSC Touch panel made by Qolsys uses DSC 433.92MHz
protocol.
FINISH
A
With the translator cover open, perform a panel sensor test.
• When the translator cover is open the translator will only
send sensor transmissions to the panel if the received sen-
sor transmissions have enough signal margin to be reliably
received by the translator.
•
Closing the translator cover exits translator sensor test
mode. When the translator is not in sensor test mode all
received sensor transmissions are sent to the panel.
• Translator sensor test mode is locked out 24 hours after
power up. To re-enable sensor test mode, the translator
must be power cycled by removing both 12VDC input
power and backup battery for at least 5 seconds.
B
Close the cover. Test and verify proper operation at the
panel. Ensure all sensor alarms are reported properly to the
central station.
C
Translator Locking: Locking the translator locks all
translator configuration settings and provides takeover pro
-
tection.
a) Ensure all sensors are functioning as desired.
b) Carefully review the effects of manual translator locking
before proceeding:
• Translator can not be factory defaulted.
• Existing sensor configurations can not be changed.
However, new sensors may be configured.
• Panel selection can not be changed.
• Sensor selection can not be changed.
• Manual translator
LOCKING CAN NOT BE UNDONE
.
c)
Open t
he translator cover and cut the lock wire. The
green and red LED will flash, and the sounder will beep to
confirm.
•
NOTE:
If the lock wire is not cut, the translator will
automatically lock after 30 days of continuous operation.
The effects are the same as manual locking; however,
the automatic lock can be reset by power cycling the
translator while the cover is open.
D
With the cover closed, insert the cover securing screw into the
screw hole near the cover latch.
Notes
SENSORS
•
If the translator loses both 12VDC input power and battery back
up power, sensor configuration data is retained.
• Low battery, tamper, and supervisory signals are reported by the
translator on its ID.
• Low battery signals from the translator are suppressed in the first
24 hours after power-up. However, a missing battery condition is
reported right away.
• The translator does not support multiple loops on Honeywell
sensors. Only one loop may be used, reed or external.
• When Sensor Select is set to
2GIG®, both Honeywell® and
2GIG® sensors will be translated or repeated.
• Honeywell® and Napco® Panic transmitters are not supported.
FAULT CONDITIONS
•
12VDC input overvoltage fault: Continually flashes and beeps on
the green LED and sounder.
• 12VDC input removed fault: Green LED turns off and the
sounder makes a long beep.
FACTORY DEFAULT
• To
return the translator to a factory default condition, press and
hold the configure button. After a couple seconds, the sounder
will start beeping rapidly. Continue holding the button until the
sounder stops beeping.
• Factory default is not possible if the translator is locked.
3
44