Alula RE114 Quick Start Manual Download Page 5

Locations to avoid

DON’T place Smoke Alarms in any of the 

following areas:

• Bathrooms, kitchens, shower rooms, 

garages or other rooms where the 

Smoke Alarm may be triggered by 

steam, condensation, normal smoke or 

fumes. Keep at least 6 metres (20ft) away 

from sources of normal smoke/fumes.

• Locate away from very dusty or dirty 

areas as dust build-up in the chamber 

can impair performance. It can also block 

the insect screen mesh and prevent 

smoke from entering the smoke detector 

chamber.

• Do not locate in insect infested areas. 

Small insects getting into the smoke 

detector chamber can cause intermittent 

alarms.

• Places where the normal temperature 

can exceed 100°F (38.7°C) or be below 

40°F (4.4°C) (e.g. attics, furnace rooms, 

directly above ovens or kettles etc.) as 

the steam could cause nuisance alarms.

• Near a decorative object, door, light 

fitting, window moulding etc., that may 

prevent smoke from entering the Alarm.

• Surfaces that are normally warmer or 

colder than the rest of the room (e.g. 

attic hatches). Temperature differences 

might stop smoke from reaching the 

Alarm.

• Next to or directly above heaters or air 

conditioning vents, windows, wall vents 

etc. that can change the direction of 

airflow.

• In very high or awkward areas (e.g. 

over stairwells) where it may be difficult 

to reach the Alarm (for testing, hushing 

or battery replacement).

• Locate the Alarm at least 1m (39”) from 

dimmer controlled lights and wiring as 

some dimmers can cause interference.

• Locate Alarm at least 1.5m (59”) and 

route wiring at least 1m away from 

fluorescent light fittings as electrical 

“noise” and/or flickering may affect the 

unit.

3. Fire Safety Advice

When using household protective 

devices, basic safety precautions should 

always be followed, including those 

listed below

•  Please read all instructions.

•  Rehearse emergency escape plans so 

everyone at home knows what to do 

in case the alarm sounds.

Figure 3

PLACE IN CENTRAL

LOCATION AND 

NOT WITHIN

305mm (12”)

OF ANY CORNER

SMOKE ALARMS

<610mm (24”) FROM APEX

DEAD AIR 

SPACE

Wall Mounting

If ceiling mounting is impractical, Smoke 

Alarms may be mounted on a wall, 

provided that:

a) the top of the detection element is 

between 150mm (6”) and 305mm (12”) 

below the ceiling (see; Figure 3a).

b) the bottom of the detection element is 

above the level of any door openings;

Wall mounting should only be considered 

where close spaced beams or similar 

obstructions may preclude ceiling 

mounting. It is considered to be the 

responsibility of the installer/client to 

determine if the presence of asbestos in 

the ceiling material would make ceiling 

mounting ‘impractical’.

Figure 3a

On a Sloping Ceiling

With a sloping or peaked ceiling install a 

Smoke Alarm within 610mm (24”) of the 

peak (measured vertically). If this height 

is less than 610mm (24”) the ceiling is 

regarded as being flat (see Figure 4).

 

Figure 4

SMOKE ALARMS

<610mm (24”)

APEX

x

x

5

Summary of Contents for RE114

Page 1: ...isted onto the smoke alarm 4 Remove the mounting plate and refer to Sections 2 and 6 for positioning and installation 5 After mounting plate is installed restore the smoke alarm onto the mounting plat...

Page 2: ...s every 48 sec 2 Beeps End of Life Off 3 Flashes every 48 sec 3 Beeps Silence Sounding Alarm Press Release Button 1 Flash every 8 sec Off Off for 10 mins Silence End of Life indication up to 30 days P...

Page 3: ...every level of a dwelling unit including basements 4 On every level of a residential board and care occupancy small facility including basements and excluding crawl spaces and unfinished attics 5 In t...

Page 4: ...Smoke Alarms must be mounted away from corners Keep at least 305mm 12 from walls and corners see Figure 3 Additionally mount the unit at least 305mm 12 from any light fitting or decorative object whic...

Page 5: ...ry replacement Locate the Alarm at least 1m 39 from dimmer controlled lights and wiring as some dimmers can cause interference Locate Alarm at least 1 5m 59 and route wiring at least 1m away from fluo...

Page 6: ...press the test hush button Do not attempt to recharge or burn the battery as it may explode If it is necessary to remove the battery for separate disposal handle carefully to avoid possible eye damag...

Page 7: ...the alarm sound or to those who may be incapable of safely evacuating the area unassisted Limitations of Heat Alarms There are various situations where a Heat Alarm may not be effective Fires where th...

Page 8: ...essary it is possible to further secure the Alarm by using a No 2 or No 4 2 to 3mm 1 8 diameter not supplied self tapping screw 6 to 8mm 1 4 long see Figure 7d to firmly lock the Alarm and its mountin...

Page 9: ...ith a damp cloth and dry thoroughly WARNING Do not paint your Alarm Other than the maintenance and stop sounding shortly after the button is released Repeat this procedure for all other Alarms in the...

Page 10: ...e chamber base 8 Fit a new chamber top and clip in place by turning clock wise 15 degrees 9 Insert the thermistor PCB into the sockets and ensure the thermistor is perpendicular to the chamber see fig...

Page 11: ...s check the replace by date marked on the side of the unit Before the Alarm is safely discarded remove from the mounting plate disconnect the batteries Do not put the Alarm into a fire The Alarm shoul...

Page 12: ...any interference including interference that may cause undesired operation of the device Le pr sent appareil est conforme aux cnr d Industrie Canada applicables aux appareils radio exempts de licence...

Reviews: