4. Configuration
139
Configurations
Description
Default
Possibilities
g3v1
– Double-bit binary input packed format
g3v2
– Double-bit binary input with flags
g40v1
–Analog output status 32 bits with flag
g40v2
–Analog output status 16 bits with flag
g40v3
–Analog output status single precision,
floating-point with flag
Event Group
and Default
Variation
Variation configuration for
events
-
g22v1
– Counter event 32 bits with flag
g22v2 - Counter event 16 bits with flag
g22v5 - Counter event 32 bits with flag and time
g22v6 - Counter event 16 bits with flag and time
g23v1 - Frozen counter event 32 bits with flag
g23v2 - Frozen counter event 16 bits with flag.
g23v5 - Frozen counter event 32 bits with flag
and time.
g23v6 - Frozen counter event 16 bits with flag
and time.
g2v1
– Binary input event without time
g2v2 - Binary input event with absolute time
g2v3 - Binary input event with relative time
g32v1
–Analog input event 32 bits without time
g32v2
– Analog input event 16 bits without time
g32v3 - Analog input event 32 bits with time
g32v4 - Analog input event 16 bits with time
g32v5
–Analog input event single precision,
floating-point without time
g4v1
– Double-bit binary input event without
time.
g4v2
– Double-bit binary input event with
absolute time.
g4v3
– Double-bit binary input event with
relative time.
None
Event Class
Event Class Configuration
-
Class 0
Class 1
Class 2
Class 3
Index
Index of the first DNP3 mapping
point
-
0 to 65535
Size
DNP3 data Size
-
1 to 86400000
Range
Address range of the data set
-
-
Dead Band
Variable
Name of the symbolic variable
that will contain the data of the
dead band. This field applies
only to the mapping of the input
analog variables
-
Variable name declared in a program or GVL
Dead Band
Type
Sets the Dead Band type to be
used in the mapping
Disabled
Absolute
Disabled
Integrated
Table 4-93. DNP3 Server Mapping Configuration
Notes:
Value Variable:
Name of the symbolic variable to be mapped. When a reading command is sent, the
return sent in response will be stored in this variable. In case of a writing command, the written value
is also stored in this variable. The variable may be simple, array or array element and may be in
structures.
Static Group and Default Variation:
The field is used to configure the variation of static data that
will be returned if the DNP3 client does not specify a variation in the request data, or in the case of
unsolicited messages.