WayPoint30A Series Installation Guide
- 3 -
Installation Instructions:
Unit shall be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Remove back plane from enclosure prior to mounting (do not discard hardware).
2. Mark and drill desired inlets on the enclosure to facilitate wiring
(Fig. 1, pg. 4).
3. Mount unit in desired location. Mark and drill holes to line up with the top and bottom holes of the
enclosure flange. Secure enclosure with appropriate fasteners
(Fig. 5, pg. 8 and Fig. 11, pg. 12)
.
4. Mount back plane to enclosure with hardware.
5. Set the input voltage selector switch for 115VAC or 230VAC operation
(Figs. 2-4, pgs. 5-7)
6. To facilitate wire entry utilize weather-tight NEMA 4 rated connectors, bushings, and cable.
7. Set illuminated master power disconnect circuit breaker to the [OFF] position
(Figs. 2-4, pgs. 5-7)
.
8. Connect unswitched AC power (115VAC/230VAC 50/60 Hz) to terminals marked [L, N]
(Figs. 2-4, pgs. 4-6)
. Green branch wire connects to earth (safety) ground lug .
Wire gauge range of connectors is 14 AWG to 11 AWG (1.6 mm to 2.5 mm diameter).
9. Set illuminated master power disconnect circuit breaker to the (RESET/ON) position
(Figs. 2-4, pgs. 5-7)
.
10. WayPoint30A4U/A4DU, WayPoint30A8U/A8DU are factory set for 24VAC operation.
For 28VAC operation adjust unit prior to mounting and applying power as follows:
Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and
the yellow wire [24V] is connected to the terminal marked [S].
11. Measure output voltage on terminals marked [COM, 24V, 28V] on WayPoint30AU or WayPoint30ADU
(Fig. 2, pg. 5)
or [1-4] or [1-8 COM] on WayPoint30A4U, WayPoint30A4DU, WayPoint30A8U and
WayPoint30A8DU before connecting devices
(Fig. 3, pg. 6, Fig. 4, pg. 7)
.
This helps avoiding potential damage.
12. Set illuminated master power disconnect circuit breaker to the [OFF] position
(Figs. 2-4, pgs. 5-7)
.
13.
Connecting devices to WayPoint30AU or WayPoint30ADU:
For 24VAC output connect devices to terminals marked [COM, 24V]
(Fig. 2, pg. 5)
.
For 28VAC output connect devices to terminals marked [COM, 28V]
(Fig. 2, pg. 5)
.
Connecting devices to WayPoint30A4U or WayPoint30A4DU:
Connect device to terminals marked [1-4] and [COM]
(Fig. 3, pg. 6).
Connecting devices to WayPoint30A8U or WayPoint30A8DU:
Connect device to terminals marked [1-8] and [COM]
(Fig. 4, pg. 7).
14. Set illuminated master power disconnect circuit breaker to the [RESET/ON] position
(Figs. 2-4, pgs. 5-7)
.
15. LEDs will illuminate indicating each output is powered
(Figs. 2-4, pgs. 5-7)
.
16. Upon completion of wiring secure enclosure door with latches and optional lock.
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: When installing in a non-restricted service area use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to all local
codes and in accordance with the National Electrical Code.
XFMR*
INPUT
CAUTION
HIGH VOLTAGE
COM 24V 28V
COM 24V 28V
28V 24V COM
PD2WP
Input Voltage
Power Input
115V
115
230
L
G
N
10
10
10
10
Ground
Lug
ALTRONIX CORP.
www.altronix.com
BROOKLYN, NY 11220
PD2WP
COM 24V 28V
COM 24V 28V
28V 24V COM
Input Voltage
Power Input
115V
115
230
L
G
N
ALTRONIX CORP.
www.altronix.com
BROOKLYN, NY 11220
Circuit board incorporated in WayPoint30ADU (PTCs)