background image

Power Supply/Charger Boards Installation Guide

Rev. ULXB-020419

Overview:

Altronix ULXB power supply/chargers convert a 115VAC / 60Hz input to a 12VDC or 24VDC output.

Agency Listings:

Altronix 
Model Number

UL Listed Sub-Assembly for 
US Installations

UL Listed Sub-Assembly 
for Canadian Installations

UL294*

Access

Control

UL603

Burglar

Alarm

UL1069

Hospital Signaling

and Nurse Call

UL1481

Fire Alarm

CSA C22.2 No.205-M1983

Signal Equipment

AL400ULXB2

P

P

P

P

P

AL600ULXB

N/A

AL1012ULXB

N/A

N/A

N/A

AL1024ULXB2

P

N/A

P

Altronix 
Model Number

* ANSI/UL 294 7th Ed. Access Control Performance Levels

Destructive Attack

Endurance Test

Line Security

Standby Power

AL400ULXB2

N/A - sub-assembly

IV

I

II

AL600ULXB

N/A - sub-assembly

IV

I

IV

AL1012ULXB

I

I

I

II

AL1024ULXB2

N/A - sub-assembly

IV

I

IV

Specifications:

Altronix 
Model Number

Input Rating

115VAC 60Hz

Output Voltage (Current)

Power-Limited

Output

Maximum

Charge Current

12VDC

24VDC

AL400ULXB2

3.5A

4A

3A

P

0.7A

AL600ULXB

3.5A

6A

6A

–*

0.7A

AL1012ULXB

2.6A

10A

–*

0.7A

AL1024ULXB2

4.2A

10A

–*

3.6A

All of the above UL Listed Sub-Assembly Power Supply/Chargers can be installed in Trove1 and Trove2 Access 

and Power Integration Systems and Maximal Series.

*For UL603 applications, or if a power-limited output is required in the end-product application, the DC output 

from the power supply must be connected to a separately Listed control unit or accessory board that provides 

power-limited outputs. The product(s) providing the power-limited output(s) must be listed as appropriate for the 

particular end-product application (fire alarm, burglar alarm, access control) and wired in accordance with the 

products installation instructions. Class 1 wiring methods, separation of circuits, and proper fire-rated enclosures 

all must be considered when connecting the DC output of the power supply to the end-product devices. 

The auxiliary outputs of these units are power-limited.

Output:

•  Filtered and electronically regulated output.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Automatic switch over to stand-by battery 

  when AC fails.

•  Zero voltage drop when switched over to 

  battery backup. 

Supervision:

•  AC fail supervision (form “C” contacts). 

•  Low battery and battery presence supervision

  (form “C” contacts).

Visual Indicators:

•  AC input, DC output and BAT trouble 

  LED indicators.

Additional Features:

•  Short circuit and thermal overload protection.

Board Dimensions 

(L x W x H approximate)

:

AL400ULXB2:

  7.1” x 4.5” x 1.44” (180mm x 114mm x 37mm).

AL600ULXB:

  7.1” x 4.5” x 2” (180.3 mm x 114.3 mm x 50.8 mm).

AL1012ULXB:

  7.25” x 4.5” x 1.75” 

  (184.2mm x 114.3mm x 44.5mm).

AL1024ULXB2:

  8.4” x 4.5” x 1.9” (213.4mm x 114.3mm x 48.3mm).

Altronix 
Model Number

Input 

Rating

115VAC 

60Hz

Output Voltage 

(Current)

Power-

Limited

Output

Maximum

Charge 

Current

UL294 Access Control Performance Levels

12VDC 24VDC

Destructive 

Attack

Endurance 

Test

Line 

Security

Standby 

Power

AL400ULXB2

3.5A

4A

3A

P

0.7A

N/A - sub-

assembly

IV

I

IV

AL600ULXB

3.5A

6A

6A

–*

0.7A

N/A - sub-

assembly

IV

I

IV

AL1012ULXB

2.6A

10A

–*

0.7A

N/A - sub-

assembly

IV

I

IV

AL1024ULXB2

4.2A

10A

–*

3.6A

N/A - sub-

assembly

IV

I

IV

Summary of Contents for ULXB Series

Page 1: ... a power limited output is required in the end product application the DC output from the power supply must be connected to a separately Listed control unit or accessory board that provides power limited outputs The product s providing the power limited output s must be listed as appropriate for the particular end product application fire alarm burglar alarm access control and wired in accordance ...

Page 2: ...tand By 500mA Alarm 10A 4 hrs 8A Not evaluated by UL Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI the Canadian Electrical Code and with all local codes and authorities having jurisdiction Product is intended for indoor use only 1 Refer to Sub Assembly Installation Instructions for mounting Rev MS020119 2 Set desired DC outpu...

Page 3: ...ON OFF Loss of AC Stand by is battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Terminal Identification Terminal Legend Function Description L G N Connect 115VAC to these terminals L to hot N to neutral Fig 1a pg 4 DC AL400ULXB2 12VDC 4A or 24VDC 3A continuous output Power Limited output Fig 1d pg 4 AL600ULXB 12VDC or 24VDC 6A continuous ...

Page 4: ... Maximal77 BC300 BC400 BC800 Maximal Trove1 and Trove2 Fig 1 ULXB configuration Output Voltage Selection Dip Switch Not applicable for AL1012ULXB and AL1024ULXB2 AL1012ULXB terminals marked DC AL1024ULXB2 terminals marked BAT DC BAT FAIL NC C NO NC C NO BAT AC FAIL DC AC BAT L G N 5A 250V OFF 24V ON 12V 1a 1b 1c 1d 1e ON Altronix is not responsible for any typographical errors 140 58th Street Broo...