![Altronix TROVE T3SSK7528 Installation Manual Download Page 2](http://html.mh-extra.com/html/altronix/trove-t3ssk7528/trove-t3ssk7528_installation-manual_2914208002.webp)
- 2 -
Trove3 S2 ULXB Kits Installation Guide
Overview:
Altronix T3SSK7528 and T3SSK7528D Trove S2 kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed
Altronix power supply/chargers and sub-assemblies. Both kits accommodate Lenel-S2 (S2 Security Platform) S2-INST Installation Kit for S2
Network Node for up to twenty-eight (28) (T2SSK7F8) doors in a single enclosure.
Configuration Chart:
Altronix
Model
Number
115VAC 60Hz Input Current (A)
Power Supply Board Input Fuse Rating
Power Supply Board Battery Fuse Rating
Nominal DC
Output Voltage
Range (DC)
Maximum Supply
Current for Main
Outputs on Power
Supply board and
ACM8(CB) Access
Power Controllers’
outputs
Fail-Safe/ Fail-Secure Outputs
Additional Fused (PTC) Outputs
ACM8(CB) Board Input Fuse Rating
ACM8 Board Output Fuse Rating
ACM8CB Board Output PTC Rating
ACM4(CB) Board Input Fuse Rating
ACM4 Board Output Fuse Rating
ACM4CB Board Output PTC Rating
PD16W Board Output Fuse Rating
PD16WCB Board Output PTC Rating
Power
Supply 1
Power
Supply 2
T3SSK7528
6.8
5A/
250V
15A/
32V
20.17-
26.4
9.7-
13.2
24VDC @ 9.4A
12VDC @ 10A
28
16
10A/
250V
3.5A/
250V
–
10A/
32V
3A/
32V
–
3.5A/
250V
–
T3SSK7528D
–
2.5A
–
2.5A
–
2.5A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and
screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws;
level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three
fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the three lower screws and make sure to
tighten all screws.
3. Mount included UL Listed tamper switches (Altronix Model TS112 or equivalent) in desired
locations, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure
approximately 2” from the right side
(Fig. 1, pg. 2)
. Connect tamper switch wiring to the
Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount S2-INST Installation Kit to backplane, refer to
page 3
.
5. Refer to the
ULXB Power Supply/Charger Installation Guide
for AL1024ULXB2 and
AL1012ULXB and corresponding
Sub-Assembly Installation Guides
for ACM4(CB),
ACM8(CB) and PD16W(CB) for further installation instructions.
Hardware:
Fig. 1
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Lock Nut