Trove2 S2 Kits Installation Guide

Overview:

Altronix T2SSK7F8 and T2SSK75F14 Trove S2 kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix 

power supply/chargers and sub-assemblies. Both kits accommodate Lenel-S2 (S2 Security Platform) S2-INST Installation Kit for S2 Network 

Node for up to eight (8) (T2SSK7F8(D)) or fourteen (14) (T2SSK75F14(D)) doors in a single enclosure.

Configuration Chart:

Altronix

Model 

Number

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

120VAC 60Hz Input Current (A)

Maximum Supply

Current for Main and 

Aux. Outputs on 

Power Supply board 

and ACM8(CB) Access 

Power Controllers’ 

outputs

Nominal DC 

Output Voltage

Fail-Safe/Fail-Secure  Outputs

Additional Fused (PTC)  Outputs

ACM8(CB) Board  Input Fuse Rating

ACM8(CB) Board Output Fuse(PTC) Rating

PDS8(CB) Board Input Fuse (PTC) Rating

PDS8(CB) Board Output Fuse (PTC) Rating

PD8UL(CB) Board Output Fuse (PTC) Rating

[DC]

[Aux]

Output 

Range 

(VDC)

Output 

Range 

(VDC)

T2SSK7F8

6.3A/250V

15A/

32V

4.5

24VDC @ 9.7A

20.17-

26.4

20.28-

26.4

8

8

10A/

250V

3.5A/

250V

10A/

32V

3A/

32V

T2SSK7F8D

2.5A

9A

2.5A

T2SSK75F14

eFlow104NB

6.3A/ 250V

15A/

32V

7.5

24VDC @ 9.4A

20.17-

26.4

20.28-

26.4

16

16

10A/

250V

3.5A/

250V

3.5A/

250V

T2SSK75F14D

eFlow102NB

5A/ 250V

12VDC @ 10A

9.7-

13.2

10.03-

13.2

2.5A

2.5A

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane from enclosure. Do not discard hardware.

2.  Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and 

 

screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; 

 

level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three 

 

fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the three lower screws and make sure to 

 

tighten all screws.

3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired

 

location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure 

 

approximately 2” from the right side 

(Fig. 1, pg. 2)

. Connect tamper switch wiring to the 

 

Access Control Panel input or the appropriate UL Listed reporting device. 

 

To activate alarm signal open the door of the enclosure.

4.  Mount S2-INST Installation Kit to backplane, refer to

 pages 3, 4

.

5.  Refer to the 

eFlow Power Supply/Charger Installation Guide

 for eFlow102NB, 

 

eFlow104NB and corresponding 

Sub-Assembly Installation Guides

 for ACM8, 

 

PDS8, VR6 and PD8UL for further installation instructions. 