Altronix Trove Plus T2M7LCK1 Installation Manual Download Page 2

 

- 2 -  

T2M7LCK Kit Series Installation Guide

Overview:

Altronix Trove Plus kits are pre-wired, pre-assembled and consist of Trove2M2 enclosure/backplane with factory installed Altronix power supply/

charger and sub-assemblies, wire harnesses and finger duct. 

Configuration Chart:

Altronix

Model 

Number

115VAC 

60Hz

Input 

Current 

(A)

Power 

Supply 

Board

Input 

Fuse 

Rating

Power 

Supply 

Board

Battery 

Fuse 

Rating

Nominal DC Output 

Voltage

Maximum Supply

Current for Main 

Outputs on Power 

Supply board and 

ACMS8(CB) Access 

Power Controller’s 

outputs

Fail-Safe/Fail-Secure or  Dry Form “C” Outputs

Current Per ACMS8(CB) and PDS8(CB) Output 

(A)

ACMS8(CB) Board  Input Fuse (PTC) Rating

ACMS8(CB) Board Output Fuse (PTC) Rating

PDS8(CB) Board Input Fuse (PTC) Rating

PDS8(CB) Board Output Fuse (PTC) Rating

Power 

Supply 1

Power 

Supply 2

Output 

Range

(VDC)

Output 

Range

(VDC)

T2M7LCK1

4.2

5A/

250V

15A/

32V

20.17-

26.4

20.17-

26.4

24VDC @ 9.4A

8

2.5

15A/

250V

3A/

250V

10A/

250V

3A/

250V

T2M7LCK2

T2M7LCK3

T2M7LCK1D

2.0

9A

2.5A

9A

2.5A

T2M7LCK2D

T2M7LCK3D

Hardware and Accessories:

•  One(1) tamper switch (Altronix Model TS112 or equivalent).

•  Cam lock.

•  Battery leads.

Mechanical:

•  16 Gauge enclosure with ample knockouts for convenient access.

•   Enclosure Dimensions (H x W x D): 27.25” x 21.75” x 6.5” (692.2mm x 552.5mm x 165.1mm).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane from enclosure. Do not discard hardware.

2.  Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the 

 

wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position 

 

of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes 

 

over the three upper screws. Install the three lower screws and make sure to tighten all screws.

3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired 

 

location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure 

 

approximately 2” from the right side 

(Fig. 1, pg. 2)

. Connect tamper switch wiring to the 

 

Access Control Panel input or the appropriate UL Listed reporting device. 

 

To activate alarm signal open the door of the enclosure.

4.  Refer to the 

ULXB Power Supply/Charger Installation Guide

 for AL1024ULXB2 

 

and corresponding 

Sub-Assembly Installation Guides

 for PDS8(CB) and ACMS8(CB) for 

 

further installation instructions.

5.  Position Mercury access controller modules over corresponding spacers and depress onto 

 

snap on spacers 

(Fig. 2, pg. 3)

.

6.  Connect wire harnesses to Mercury access controller modules

(Fig. 2-4, pg. 3-5)

.

7.  Mount backplane to enclosure with hardware.

Fig. 1

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Summary of Contents for Trove Plus T2M7LCK1

Page 1: ...ssembled kit includes Trove2 enclosure with TM2 Altronix Mercury backplane One 1 AL1024ULXB2 Power Supply Charger One 1 ACMS8 Dual Input Output Fuse Protected Access Power Controller One 1 VR6 Voltage Regulator One 1 PDS8 Dual Input Output Fuse Protected Power Distribution Module One 1 Rocker Switch Bracket with One 1 Rocker Switch Not evaluated by UL Wire harnesses and management 8 Door Kits with...

Page 2: ...ocal codes and authorities having jurisdiction Product is intended for indoor use only 1 Remove backplane from enclosure Do not discard hardware 2 Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure Install three upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the three upper screws level and s...

Page 3: ...M K3 NO NC C3 C2 COM K5 NO NC C3 C2 COM K2 NO NC C3 C2 COM K4 NO NC C3 C2 COM K6 NO NC D1 D2 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 GND IN10 INPUTS IN 5V OUT 12V J4 J2 RDR POWER REG UNREG GND DAT CLK BZR LED V0 CLK GND DAT BZR LED V0 READER 1 READER 2 PN REV SN TR TR R R SG AC GND ACDC RS 485 12V J5 J6 TERMINATOR J5 J6 2W 4W RS 485 J3 NO C NC NO C NC RLY 1 RLY 2 RLY 3 RLY 4 NO C NC NO C NC RLY 5 RLY ...

Page 4: ...5 J6 2W 4W RS 485 J3 NO C NC NO C NC RLY 1 RLY 2 RLY 3 RLY 4 NO C NC NO C NC RLY 5 RLY 6 NO C NC NO C NC 6 5 4 3 2 1 8 7 S1 OFF ON READER INTERFACE U10 COM C2 C3 NO NC K1 C3 C2 COM K3 NO NC C3 C2 COM K5 NO NC C3 C2 COM K2 NO NC C3 C2 COM K4 NO NC C3 C2 COM K6 NO NC D1 D2 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 GND IN10 INPUTS IN 5V OUT 12V J4 J2 RDR POWER REG UNREG GND DAT CLK BZR LED V0 CLK GND DAT B...

Page 5: ...2 COM K2 NO NC C3 C2 COM K4 NO NC C3 C2 COM K6 NO NC D1 D2 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 GND IN10 INPUTS IN 5V OUT 12V J4 J2 RDR POWER REG UNREG GND DAT CLK BZR LED V0 CLK GND DAT BZR LED V0 READER 1 READER 2 PN REV SN TR TR R R SG AC GND ACDC RS 485 12V J5 J6 TERMINATOR J5 J6 2W 4W RS 485 J3 NO C NC NO C NC RLY 1 RLY 2 RLY 3 RLY 4 NO C NC NO C NC RLY 5 RLY 6 NO C NC NO C NC 6 5 4 3 2 1 8 7 ...

Page 6: ... 6 T2M7LCK Kit Series Installation Guide Notes ...

Page 7: ...T2M7LCK Kit Series Installation Guide 7 Notes ...

Page 8: ...5 25 133 35mm 5 25 133 35mm 7 00 177 79mm 2 00 50 8mm 2 00 50 8mm 27 00 685 8mm 3 50 88 9mm 0 5625 14 29mm 2 Conduit 0 685 17 399mm 1 77 44 96mm 3 50 88 9mm 21 50 546 1mm 19 80 502 92mm 5 25 133 35mm 5 25 133 35mm 1 2 Conduit 3 4 Conduit 1 2 Conduit 3 4 Conduit 1 2 Conduit 3 4 Conduit 1 2 Conduit 3 4 Conduit Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York...

Reviews: