Trove CDVI Kits Installation Guide

Overview:

Altronix Trove CDVI kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/chargers and 

sub-assemblies. These kits also accommodate various combinations of CDVI Atrium A22K/A22NB/ADH10 boards for up to twenty (20) doors 

in a single enclosure.

Configuration Chart:

Altronix

Model Number

Networkable

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

120VAC 60Hz Input Current (A)

Maximum Supply

Current for Main and 

Aux. Outputs on 

Power Supply board, 

MOM5 power 

distribution module 

or ACM4/ACM8 Access 

Power Controllers’ 

outputs

Nominal DC 

Output Voltage

Fail-Safe/Fail-Secure or  Dry Form “C” Outputs

Additional Fuse or PTC  Protected Outputs

ACM4/ACM8 Board  Input Fuse Rating

ACM4 Board Output Fuse  Rating

ACM8 Board Output Fuse  Rating

PD8UL Board Output Fuse Rating

MOM5 Output  PTC Rating

Power Supply

[DC]

[Aux]

Output 

Range 

(VDC)

Output 

Range 

(VDC)

T1CVK3F4

5A/250V

15A/

32V

3.5

24VDC @ 5.7A

20.17-

26.4

20.28-

26.4

4

10A/

250V

3A/

32V

T2CVK7F10

6.3A/250V 15A/

32V

4.5

24VDC @ 9.4A

20.17-

26.4

20.28-

26.4

12

8

10A/

250V

2.5A/

250V

2.5A/

250V

3.5A/

250V

T2CVK33F10

5A/250V

15A/

32V

7.0

24VDC @ 5.9A 

24VDC @ 5.9A

20.17-

26.4

20.28-

26.4

10

2A/

250V

T2CVK33F10Q

P

5A/250V

15A/

32V

7.0

24VDC @ 5.9A 

24VDC @ 5.9A

20.17-

26.4

20.28-

26.4

10

2A/

250V

T3CVK77F20

6.3A/ 250V 15A/

32V

9.0

24VDC @ 9.4A 

24VDC @ 9.7A

20.17-

26.4

20.28-

26.4

20

8

10A/

250V

3A/

32V

2.5A/

250V

3.5A/

250V

9.7-

13.2

10.03-

13.2

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane from enclosure. Do not discard hardware.

 

If your application requires a raised backplane, re-mount it using metal spacers and screws (provided). 

2.  Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install two/three upper fasteners and screws 

 

in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; level and secure. 

 

Mark the position of the lower two/three holes. Remove the enclosure. Drill the lower holes and install the fasteners. Place the 

 

enclosure’s upper keyholes over the upper screws. Install the lower screws and make sure to tighten all screws.

3.  Mount included UL Listed tamper switch(es) (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the 

 

tamper switch bracket onto the edge of the enclosure approximately 2” from the right side 

(Fig. 1, pg. 2)

. Connect tamper switch wiring 

 

to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.

4.  Mount CDVI A22K/A22NB/ADH10 boards to backplane, 

refer to pages 3-6.

5.  Refer to the 

eFlow Power Supply/Charger Installation Guide

 (eFlow6NB, eFlow102NB, 

 

eFlow104NB) and corresponding 

Sub-Assembly Installation Guide

 (LINQ2, ACM4, ACM8, 

 

PD8UL, MOM5) for further installation instructions.

Fig. 1

Tamper Switch

(provided)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Summary of Contents for T1CVK3F4

Page 1: ...k Communication Module Two 2 eFlow6NB Power Supply Chargers Two 2 MOM5 PTC Power Distribution Modules with Fire Alarm Interface T3CVK77F20 20 Door Kit with Fused Outputs Fully assembled kit includes Trove3 enclosure with TCV3 Altronix CDVI backplane Two 2 eFlow104NB Power Supply Chargers Two 2 ACM8 Fused Access Control Modules One 1 ACM4 Fused Access Control Module One 1 PD8UL Fused Power Distribu...

Page 2: ...3 13 2 Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 ANSI and with all local codes and authorities having jurisdiction Product is intended for indoor use only 1 Remove backplane from enclosure Do not discard hardware If your application requires a raised backplane re mount it using metal spacers and screws provided 2 Mark and predrill hol...

Page 3: ...correctly as shown in Fig 2 below 3 Fasten backplane to Trove2 enclosure utilizing pan head screws provided Fig 2 RJ45 Jack CDVI A22K A22NB ADH10 RJ45 Jack CDVI A22K A22NB ADH10 NC C NO NC C NO AC FAIL BAT FAIL TRIGGER AC DC AC1 EOL NO GND SUPERVISED RESET AUX BAT DC Altronix eFlow6NB L G N OFF 24V ON 12V ON Control Power NO C NC FACP INTERFACE INP T RET TRG TRIGGER INPUT IN GND 1 NC C NO COM OUTP...

Page 4: ...NC C NO COM NC C NO COM NC C NO COM IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Altronix ACM8 Control Power NO C NC FACP INTERFACE INP T RET TRG TRIGGER INPUT IN GND 1 NC C NO COM OUTPUT 1 NC C NO COM OUTPUT 2 NC C N...

Page 5: ... AUX BAT DC L G N OFF 24V ON 12V ON NC C NO NC C NO AC FAIL BAT FAIL TRIGGER AC DC AC1 EOL NO GND SUPERVISED RESET AUX BAT DC L G N OFF 24V ON 12V ON DC INPUT POS DC OUTPUT ALARM POS DC OUTPUT STANDBY 6 7 8 9 10 1 2 3 4 5 TRIGGER LED POWER ON LED NEG1 NEG2 NEG3 NEG4 NEG5 TRIGGER NC C NO NC C NO DRY OUTPUT POWER FAIL INPUT DC INPUT POS DC OUTPUT ALARM POS DC OUTPUT STANDBY 6 7 8 9 10 1 2 3 4 5 TRIG...

Page 6: ...1 2 3 4 1 2 3 4 O N O N OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 ...

Page 7: ...MR LINQ2 Features UL Listed in the U S and Canada Local or remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state change and unit temperature Access control and user managment Restrict read write Restrict users to specific resources Two 2 integral...

Page 8: ... 8 Trove CDVI Kits Installation Guide Notes ...

Page 9: ... 9 Trove CDVI Kits Installation Guide Notes ...

Page 10: ...7mm x 368mm x 118mm 4 5 114 3mm 4 5 114 3mm 2 75 69 9mm 1 115 28 3mm 1 36 34 5mm 1 25 31 8mm 1 25 31 8mm 1 5 38 1mm 8 5 215 9mm 6 5 165 1mm 1 5 38 1mm 8 5 215 9mm 6 5 165 1mm 4 5 114 3mm 13 0 330 2mm 0 6 15 2mm 14 5 321 3mm 1 45 36 8mm 7 25 184 2mm 1 95 49 5mm 1 1 27 9mm 0 6 15 2mm 0 57 14 5mm 18 0 457 2mm 1 25 31 8mm ...

Page 11: ...2mm 2 00 50 8mm 2 00 50 8mm 1 25 31 8mm 1 25 31 8mm 5 25 133 4mm 5 25 133 4mm 7 00 177 8mm 1 25 31 8mm 6 25 158 8mm 19 80 502 9mm 1 00 25 4mm 27 685 8mm 1 5 38 1mm 2 00 50 8mm 2 00 50 8mm 3 5 88 9mm 3 5 88 9mm 21 50 546 1mm 5 25 133 35mm 5 25 133 35mm 6 25 158 8mm 1 25 31 8mm 0 85 21 6mm 0 5625 14 3mm 2 415 61 3mm 0 685 17 4mm 1 77 45mm 0 885 22 5mm 1 125 28 3mm Knockouts 2 00 50 8mm 2 00 50 8mm ...

Page 12: ...mm 30 12 768 1mm 14 01 355 9mm 14 01 355 9mm 1 25 31 8mm 1 55 39 4mm 1 78 45 2mm 1 25 31 8mm 1 07 27 2mm 1 10 27 9mm 2 50 8mm 10 75 273 1mm 10 75 273 1mm 10 62 269 8mm 2 00 50 8mm 10 75 273 1mm 10 75 273 1mm 10 62 269 8mm 36 12 917 5mm 33 63 854 2mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 web site www ...

Reviews: