Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

 

in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 7, 8)

. Secure enclosure to earth ground. 

2.  Slide [Power ON/OFF] switch t o OFF position.

3.  Set SW1 on the power supply board to the desired DC output voltage 

(Fig. 1c, pg. 5) 

 

(Power Supply Voltage Output Specification Chart)

.

4.  Connect AC power to the terminals marked [L & N], connect ground to the green flying lead 

(Fig. 1, pg. 5)

.

 

Use 18 AWG or larger for all power connections (Battery, DC output).

 

Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

5.  Slide [Power ON/OFF] switch to ON position.

6.  Measure output voltage before connecting devices. This helps avoiding potential damage.

 

CAUTION: Do not touch exposed metal parts. 

 

Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel.

7.  Slide [Power ON/OFF] switch t o OFF position.

8.  Connect devices to be powered:

 

a. For Power Supply Board connect to the terminals marked [– DC +]. 

  b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked  

 

  [1P & 1N] through [4P & 4N] 

(Fig. 2, pg. 6), 

1 to 8 marked [1P & 1N] through [8P & 8N] 

(Fig. 3, pg. 6), 

  

or 1 to 16 marked [1P & 1N] through [16P & 16N] 

(Fig. 4, pg. 6)

,

 

carefully observing correct polarity.

 

Note:

 Power switch is used to disconnect the L (HOT) terminal from the rest of the board 

(Fig. 1a, pg. 5)

.

 

When servicing the unit, AC mains should be removed.

9.  When using stand-by batteries, they must be lead acid or gel type. 

 

Connect battery to the terminals marked [– BAT +] (battery leads included).

 

12VDC operation:

 Use one (1) 12VDC battery.

 

24VDC operation:

 Use two (2) 12VDC batteries connected in series.

 

Note:

 When batteries are not used, a loss of AC will result in the loss of output voltage.

For supervised models only:

10. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs 

 

marked [NC, C, NO] 

(Fig. 1b, pg. 5).

11. Slide [Power ON/OFF] switch to ON position.

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Summary of Contents for SMP3CTX Series

Page 1: ...e ___________________ SMP3CTX Series Power Supply Chargers Models Include SMP3CTX SMP3PMCTX SMP3PMCTXX Single Output SMP3PMP4 Four 4 Fuse Protected Outputs SMP3PMP8 Eight 8 Fuse Protected Outputs SMP3PMP16 Sixteen 16 Fuse Protected Outputs SMP3PMP4CB Four 4 PTC Protected Outputs SMP3PMP8CB Eight 8 PTC Protected Outputs SMP3PMP16CB Sixteen 16 PTC Protected Outputs Installation Guide ...

Page 2: ...4VDC SW1 OFF Fig 1c pg 5 2 5A Specified at 25 C ambient Agency Listings CE European Conformity Input Input 115VAC 50 60Hz 0 65A or 230VAC 50 60Hz 0 35A Output 12VDC or 24VDC selectable output 2 5A supply current Filtered and electronically regulated outputs Short circuit and thermal overload protection Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge curren...

Page 3: ...osed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel 7 Slide Power ON OFF switch t o OFF position 8 Connect devices to be powered a For Power Supply Board connect to the terminals marked DC b For Power Distribution Module s connect devices to be powered to the t...

Page 4: ...B 1P to 4P 1P to 8P 1P to16P Positive DC power outputs 1N to 4N 1N to 8N 1N to 16N Negative DC power outputs Caution Equipment to be installed serviced by authorized trained personnel only Shut branch circuit power before installing servicing equipment WARNING To reduce the risk of fire or electric shock do not expose the unit to rain or moisture This installation should be made by qualified servi...

Page 5: ...ttery OFF ON L 5A 250V Green OFF 24V ON 12V ON LOW BAT NC C NO NC C NO AC FAIL BAT DC AC DC Board 115VAC 230VAC power mains P Dist Mo Optional Rechargeable Stand by Battery Option Sta OFF 24V ON 12V ON BAT DC Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery Fig 1 Fig 1a Switch disables power mains line voltage input If stand by battery batteries are connected the DC ou...

Page 6: ...R OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED ON OFF SW1 Used on PTC Models DC Output to devices From Power Supply Board Factory Installed Power Distribution Module s common outputs protected outputs P N N P S XFM R I n pu t 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 P N 3 5A 250V For continuous protection against risk of fire replace fuses with same type and rating Used on PTC Model...

Page 7: ...re accommodates up to two 2 12VDC 7AH batteries 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm ...

Page 8: ...mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 905...

Reviews: