   Installation  Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local 

codes and authorities having jurisdiction. All units should be installed by a trained service personnel.

NetWaySP3WP/SP3WPN/SP3WPX Enclosure Mounting and Installation:

1.  Remove backplane from enclosure prior to drilling. Do not discard hardware. 

 

Note: Make sure that hardware will not interfere with components of the circuit board.

2.  Mark and drill desired inlets on the enclosure to facilitate wiringMaximum NEMA type 4X rated fittings to 

  be used are 0.5”. Follow manufacturer’s specifications for the appropriate size opening. 

 

Note: Inlets for conduit fittings should only be made on the bottom of the enclosure. 

  UL Listed NEMA type 4X rated conduit connector/hubs shall be used for the appropriate size inlets.

3.  Clean out the inside of enclosure before remounting circuit board.

4. Mounting NEMA4/4X rated enclosure (Enclosure Dimensions, pgs. 11-12):

 

Wall mount: Mount unit in desired location. Mark and drill holes to line up with the top and bottom holes of 

     

the enclosure flange. Secure enclosure with appropriate fasteners (e. g. screws and anchors; 

     

bolts and locking nuts, etc.) that are compatible with mounting surface and are of sufficient 

     

length/construction to ensure a secure mount (Fig. 4, pg. 8).

 

Pole Mount: Refer to Figs. 5 - 9, pg. 8

 

Note: All inlets for conduit fittings should be on the bottom of the enclosure.

5.  Mount backplane in enclosure with hardware.

6.  To facilitate wire entry utilize weather-tight NEMA rated connectors (supplied), bushings, and cable.

NetWaySP3X Enclosure Mounting and Installation:

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two (2) upper fasteners and screws in the wall with the screw heads protruding. 

  Place the enclosure’s upper keyholes over the two (2) upper screws; level and secure. Mark the position of 

  the lower two (2) holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the 

  enclosure’s upper keyholes over the two (2) upper screws. Install the two (2) lower screws and make sure to 

  tighten all screws (Enclosure Dimensions, pg. 9). Secure enclosure to earth ground. 

NetWaySP3B/SP3PL Mounting and Installation:

1. Mount board/backplane in the desired location/enclosure 

  with hardware supplied.

2. 

NetWaySP3B: Connect 56VDC/120W max power source 

  to terminal marked [+] and [–].

Note: For proper earth ground connections on NetWaySP3B 

fasten metal standoffs (provided) to threaded studs at indicated

board mounting holes (shown on the right)

This is recommended for better environmental immunity.

Installation:

1. 

For NetWaySP3WP, NetWaySP3WPX, NetWaySP3X, and NetWaySP3PL: 

  Before powering unit, set input voltage selection switch to proper Input Voltage position (Fig. 2a, pg. 6). 

  Units are factory set for 115VAC.

2. Secure cabinet to earth ground. Connect AC power from overcurrent protective device circuit breaker 

  (20A @ 115VAC, 60Hz, 16A @ 230VAC, 50/60Hz) to the terminals marked [L, N] on power supply board 

  (Fig. 2, pg. 6). Use 14AWG or larger for all power connections (Battery, DC output, AC input). 

 Connect 

ground lug      to earth or green branch wire (12AWG min.).

  Note: For NetWaySP3WPN use external 48-55V UL Listed ITE power supply, carefully observing 

  correct polarity (Fig. 3, pg. 7).

 

Keep power-limited wiring separate from non power-limited wiring by utilizing separate knockouts/

  inlets. Minimum 0.25” spacing must be provided.

  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

  service personnel.

3.  Connect structured cables from port marked [Port 1], [Port 2] or [Port 3] on NetWay unit to PoE compliant 

  cameras/edge devices (Fig. 2, pg. 6)

 

Note: All interconnected devices must be UL Listed.

4.  Insert SFP module into port marked [SFP], then connect cable to the SFP module on NetWaySP3B to the 

  corresponding input of an SFP switch (Fig. 2, pg. 6).

5. 

Battery Backup (if desired): Connect four (4) 12VDC batteries wired in series to terminals marked 

  [+ BAT –] (Fig. 2, pg. 6), carefully observing polarity. 

  When use of stand-by batteries is desired, they must be lead acid or gel type. 

 

Note: When batteries are not used, a loss of AC will result in the loss of output voltage. 

6.  Please ensure that the cover is secured with:

  Key lock and screws for 

NetWaySP3X

  Security bolt for 

NetWaySP3WP, NetWaySP3WPN and NetWaySP3WPX.

NetWaySP3B

Metal Standoffs

Input:

48V-56VDC

3.3V PWR

+ --

Summary of Contents for Netway Spectrum Series

Page 1: ...rt PoE switch and power supply NEMA4 4X IP66 rated Outdoor enclosure Accommodates up to four 4 12VDC 4AH batteries NetWaySP3X Includes Fiber Optic SFP 1G Link 3 port PoE switch and power supply NEMA1 rated Indoor enclosure NetWaySP3WPN Includes Fiber Optic SFP 1G Link and 3 port PoE switch uses external power supply NEMA4 4X IP66 rated Outdoor enclosure NetWaySP3PL Includes Fiber Optic SFP 1G Link...

Page 2: ...Specifications Chart on page 4 for Environmental Conditions Applications Provides PoE PoE Hi PoE for cameras devices Altronix Spectrum switches can be used as a switching node in daisy chain and ring network configurations Spectrum switches can pass VLAN 802 IQ protocol Spectrum switches can pass SNMP protocol LINQ Technology Remote network management allows for camera device reset and monitoring ...

Page 3: ...nd make sure to tighten all screws Enclosure Dimensions pg 9 Secure enclosure to earth ground NetWaySP3B SP3PL Mounting and Installation 1 Mount board backplane in the desired location enclosure with hardware supplied 2 NetWaySP3B Connect 56VDC 120W max power source to terminal marked and Note For proper earth ground connections on NetWaySP3B fasten metal standoffs provided to threaded studs at in...

Page 4: ...1 kg 11 7 lbs 5 3kg 10 0 lbs 4 54kg 17 5 lbs 7 9kg 7 55 lbs 3 42kg 4 0 lbs 1 81kg 0 75 lbs 0 34kg Configuring Units for Network Connection Please be sure to visit altronix com for latest firmware and installation instructions Factory Default Settings IP Address 192 168 168 168 User Name admin Password admin 1 Set the static IP address for the laptop to be used for programming to the same network I...

Page 5: ...P is not encrypted and unsecure Even though HTTP can be used for remote access it is recommended primarily for use with LAN connections Secure Network Setup HTTPS In order to setup HTTPS for a Secure Network Connection a Valid Certificate and Key must be used Certificates and Key should be in a PEM format Self Certifications should only be used for testing purposes as no actual authentication is b...

Page 6: ...E_SPR PoE_SPR Factory Reset PoE_Data Spd Input 48V 56VDC PORT3 Uplink Spd 10 100 1000 PoE 30W Altronix Cor Brooklyn NY US www altronix com PORT1 Spd 10 100 1000 PoE 30W 60W PORT2 Spd 10 100 1000 PoE 30W 60W Link 3 3V PWR Link Link NetwaySP3B PoE ALOS 5A 250VA DC BAT 115VAC 230VAC 115VAC 230VAC Input Voltage Selection Switch L G N 5A 250VA DC BAT 115VAC 230VAC 115VAC 230VAC L G N Fig 2a Fig 2b Fig ...

Page 7: ...d distances based on starting voltage of 56VDC and accounts for a 10 volt drop All distances are per IEEE 802 3at standard for device power requirements of minimum 44VDC and leave an approximate 2 volts for safety and flexibility Carefully observe polarity Carefully observe polarity Composite Cable Fiber Switch 48 55V UL Listed ITE Power Supply IP PoE PoE or Hi PoE Device IP PoE PoE or Hi PoE Devi...

Page 8: ...red height of the top Pole Mount bracket is achieved tighten the straps down by sliding open end of the strap through the locking mechanism on the strap then tighten the screw with flat head screwdriver or 5 16 hex socket driver Fig 6 pg 8 and Fig 8 pg 8 3 Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the bracket tightening bolts with a ...

Page 9: ...2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm ...

Page 10: ... 10 NetWaySP3 Series NetWaySP3PL Mechanical Drawing and Dimensions H x W x D approx 10 75 x 8 875 x 2 375 273 1mm x 225 4mm x 60 3mm 8 875 225 4mm 8 25 209 5mm 0 25 6 4mm 10 75 273 1mm 10 25 260 3mm ...

Page 11: ... 3 96 100 6mm 5 59 142mm 10 32 X 0 375 9 6mm BRASS INSERT X4 STAINLESS STEEL PIANO HINGE 11 31 287 3mm 13 31 338 1mm PADLOCK LATCH ATTACHED WITH RIVETS Ø 0 375 9 5mm PADLOCK EYE 10 75 273 1mm 10 00 254mm 8 25 209 6mm 10 25 260 4mm 12 00 304 8mm 13 50 342 9mm 10 32 X 0 25 6 4mm BRASS INSERT X2 Ø 0 32 8 1mm MOUNTING HOLE TYP 4 PLACES 12 75 323 9mm 8 00 203 2mm ...

Page 12: ...EW SECTION A A A A 316 STAINLESS STEEL PADLOCK LATCH ATTACHED WITH RIVETS Ø 375 PADLOCK EYE 17 36 441 mm 12 00 304 8mm 6 41 162 8mm 10 32 X 250 BRASS INSERT 4 PLCS 14 54 369 3mm 16 74 425 2mm 0 125 3 2mm 14 25 362mm 14 00 355 6mm 12 23 310 6mm 17 53 445 3mm 16 00 406 4mm 1 67 42 4mm 5 00 127mm 16 73 425mm 15 3 388 6mm 6 67 169 4mm 4 94 125 5mm 5 77 146 6mm 0 75 19 1mm MOUNTING PLATE Ø 32 8 1mm WAL...

Reviews: