Altronix MOM5 Installation Instructions Download Page 2

LED Diagnostic Table:

LED

ON

OFF

Power (Green)

Normal operation

Loss of power to MOM5

Trigger (Green) MOM5 triggered (alarm condition)

MOM5 in standby (non-alarm condition)

Outputs (Red)

Output tripped due to a short circuit or overload condition

Normal operation

Terminal Identification:

Terminal

Function/Description

Legend

-- DC Input +

12 or 24VDC from power supply.

Trigger

This circuit is supervised by a 2.2 K EOL resistor. Initiating a short or open will 
cause power to be dropped to all terminals marked Pos. (+) DC output (standby)
and supply power to all terminals marked Pos (+) DC output (alarm).

Input Neg (--),

Applying voltage to terminals marked Neg(-) input Pos (+) FACP signaling output in

Pos (+)

polarity shown will yield the same results as initiating trigger (mentioned above).

Neg (--) 1 thru 5

Supplies constant negative (-) voltage.

Pos (+) DC output (alarm)

Supplies positive (+) voltage when dry input or fire alarm (wet) trigger input.

Pos (+) DC output

Supplies positive (+) voltage in normal condition. 

(standby)

Power is removed when either input trigger is activated.

N.C., C, N.O.

When the MOM5 is triggered the C and N.O. terminals will close and the

Dry output

C and N.C. terminals will open. This output is used to trip auxiliary devices.
e.g. HVAC Shutdown, Elevator Recall etc...

N.C., C, N.O.

Form “C” contacts used for signaling when no voltage is present at -- DC input +

Power Fail

terminals. Under normal conditions, terminals N.O. and C are open, N.C. and C are 
closed. A occurance of trouble condition causes N.O. and C to closed and
N.C. and C to open.

Fig. 1

Typical Application Diagrams:

TRIGGER

NEG (-) INPUT POS (+)

EOL 2.2K

(+)

(-)

DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE

N.C.  INPUT FROM
FACP OR ACCESS
CONTROL DEVICE

TRIGGER

NEG (-) INPUT POS (+)

EOL 2.2K

(+)

(-)

DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE

N.O.  INPUT FROM
FACP OR ACCESS
CONTROL DEVICE

MOM5 module shown with wet and/or dry normally closed
trigger inputs (Non-Latching):

MOM5 module shown with wet and/or dry normally
open trigger inputs (Non-Latching):

2

Reviews: